background image

 

Section 1. Features and Specifications

 

Electrical Specifications 

 

Electrical Specifications

 

Specifications are warranted over a temperature range of 0 to 30 °C with default 
local sensing. Above 30 °C, the output voltage needs to be derated linearly to zero at 
70 °C. Specifications are subject to change without notice. 

Table 1.2  

Electrical Specifications for 15 V to 60 V Models 

Models 15–20 

30–10 60–5

 

Output Ratings: 

Output Voltage 

Output Current 

Output Power 

Line Regulation: 

1

 

Voltage (0.01% of Vmax + 2 mV) 
Current (0.01% of Imax + 2 mA) 

Load Regulation: 

2

 

Voltage (0.01% of Vmax + 2 mV) 
Current (0.01% of Imax + 2 mA) 

Meter Accuracy: 

Voltage (1% of Vmax + 1 count) 
Current (1% of Imax + 1 count) 

Output Noise and Ripple:

Voltage (p-p) 
Voltage (rms) 
Current (rms) 

4

 

Drift (60 minutes): 

Voltage (0.02% of Vmax) 
Current (0.03% of Imax) 

Drift (8 hours): 

6

 

Voltage (0.02% of Vmax) 
Current (0.08% of Imax) 

Temperature Coefficient 

Voltage (0.015% of Vmax/°C) 
Current (0.02% of Imax/°C) 

0

15 V 

0

20 A 

300 W 

 

3.5 mV 
4 mA 

 

3.5 mV 
4 mA 

 

250 mV 
300 mA 

 

100 mV 
5 mV 
20 mA 

 

3 mV 
6 mA 

 

3 mV 
16 mA 

 

2.25 mV 
4 mA 

0

30 V 

0

10 A 

300 W 

 

5 mV 
3 mA 

 

5 mV 
3 mA 

 

400 mV 
200 mA 

 

100 mV 
5 mV 
10 mA 

 

6 mV 
3 mA 

 

6 mV 
8 mA 

 

4.5 mV 
2 mA 

0

60 V 

0

5 A  

300 W 

 

8 mV 
2.5 mA 

 

8 mV 
2.5 mA 

 

700 mV 
60 mA 

 

100 mV 
5 mV 
5 mA 

 

12 mV 
1.5 mA 

 

12 mV 
4 mA 

 

9 mV 
1 mA 

 

 

1.  For input voltage variation over the AC input voltage range, with constant rated load. 
2.  For 0 to 100% load variation, with constant nominal line voltage. 
3.  Points of measurement are at the positive (+) and return (-) output terminal screws of the 

output terminal block; RMS values are measured at bandwidth of 20fHz to 300kHz; PK-PK 
values are measured at bandwidth of 20Hz to 20MHz. 

4.  Current mode noise is measured from 10% to 100% of rated output voltage, full current. 
5.  Maximum drift over 60 minutes with constant line, load, and temperature, after 60-minute 

warm-up. 

6.  Maximum drift over 8 hours with constant line, load, and temperature, after 60-minute 

warm-up. 

7.  Change in output per °C change in ambient temperature, with constant line and load. 

 
 

 

Operating Manual for HPD Series Power Supply 

Содержание sorensen hpd series

Страница 1: ...HPD Series Programmable DC Power Supply OperationManual TM 30OP 01XN Rev E www programmablepower com...

Страница 2: ......

Страница 3: ......

Страница 4: ......

Страница 5: ...cation purposes only Notice of Copyright HPD Series Programmable DC Power Supply Operation Manual 2007 AMETEK Programmable Power Inc All rights reserved Exclusion for Documentation UNLESS SPECIFICALLY...

Страница 6: ...This page intentionally left blank ii...

Страница 7: ...and equipment safety Always ensure that facility AC input power is de energized prior to connecting or disconnecting any cable In normal operation the operator does not have access to hazardous volta...

Страница 8: ...This page intentionally left blank iv...

Страница 9: ...o the instructions of AMETEK is opened modified or disassembled in any way without AMETEK s consent or is used in combination with items articles or materials not authorized by AMETEK The Buyer may no...

Страница 10: ...This page intentionally left blank vi...

Страница 11: ...ical Specifications 7 Chassis Dimensions and Weight 8 Introduction 9 Basic Setup Procedure 9 Initial Inspection 9 Periodic Cleaning 9 Rack Mounting 10 Location and Ventilation 10 AC Input Power Connec...

Страница 12: ...22 Automatic Mode Crossover 23 Constant Power Loads 23 Using Multiple Supplies 24 Connecting Multiple Supplies in Series Voltage Mode Only 24 Connecting Multiple Supplies in Parallel 25 Split Supply...

Страница 13: ...power density providing increased power output in a small light package The power supply delivers simultaneous digital displays for both voltage and current andbargraphdisplaysformonitoringtransientch...

Страница 14: ...interface for serial instrument programming using RS 232 protocol Internal GPIB interface for complete remote digital programming IEEE 488 standard Optional 200 250 Vacinput Option AC200 Standard is...

Страница 15: ...ng Interface Indicators Rear Panel Connectors and Outputs Figure 1 3 shows the connectors and outputs available at the rear panel Figure 1 3 shows the 15 V or 30 V low voltage model Figure 1 3 Rear Pa...

Страница 16: ...of Imax C 0 15 V 0 20 A 300 W 3 5 mV 4 mA 3 5 mV 4 mA 250 mV 300 mA 100 mV 5 mV 20 mA 3 mV 6 mA 3 mV 16 mA 2 25 mV 4 mA 0 30 V 0 10 A 300 W 5 mV 3 mA 5 mV 3 mA 400 mV 200 mA 100 mV 5 mV 10 mA 6 mV 3 m...

Страница 17: ...y from power on until output stable 500 s 1 5 s maximum Input Conditions Rated AC Input Voltage 120 Vac standard 230 240 Vac AC200 option Maximum AC Input Power 625 VA Operational AC Input Voltage Ran...

Страница 18: ...n Line drop must be deducted from the supply s maximum output voltage Input to output 1350 Vac 1 5 V line EnvironmentalSpecifications Operating Ambient Temperature 0 to 30 C with default local sensing...

Страница 19: ...appropriate power cord for destination country Front Panel Output Connector Three binding posts positive negative and ground Rear Panel Output and Sense Connector Four terminal barrier strips The 60 V...

Страница 20: ...res and Specifications Chassis Dimensions and Weight Chassis Dimensions and Weight Height 5 25 in 132 mm Width 4 25 in 109 mm Depth 11 7 in 297 mm Weight 7 7 lb 3 5 kg 8 Operating Manual for HPD Serie...

Страница 21: ...ower supply was shipped with an IEC power cord set appropriate to the destination country two 2 position terminal block jumpers and an operating manual When you first receive your unit perform a quick...

Страница 22: ...r about the rack mount kit Option RM For Rack Mount Installation Instructions see Appendix A Location and Ventilation Whether you place the power supply in a rack or on a bench allow cooling air to re...

Страница 23: ...urned on the output voltage or current previously set is applied to loads The AC input connector is a standard IEC 320 male connector located on the power supply s rear panel Table 2 2 Operational AC...

Страница 24: ...Set the power switch to ON 3 Rotate the current control one half turn clockwise Slowly rotate the voltage control clockwise and observe the digital meter Minimum control range should be from zero to m...

Страница 25: ...nd being applied CAUTION When making load connections be sure to observe correct polarity or the power supply may be damaged You can obtain reliable performance from your power supply if you take cert...

Страница 26: ...nimum load wiring must have a current capacity greater than the output current rating of the power supply This ensures that the wiring will not be damaged even if the load is shorted See Table 3 1 for...

Страница 27: ...5 V drop in each line1 Figure 3 1 Maximum Wire Length for 100 mV Line Drop Noise and Impedance Effects To minimize noise pickup or radiation use shielded pair wiring of the shortest possible length fo...

Страница 28: ...ropriate terminal screw Tighten the screw High Voltage Models To make load connections to high voltage models attach an appropriate gauge wire1 maximum 12 wire following the steps below 1 Strip load w...

Страница 29: ...tput terminals Without sense line connections the supply regulates the voltage at the output terminals of the power supply For improved local sensing connect jumpers between the sense terminals and th...

Страница 30: ...e shipped unattached with 60 V models If your application requires precisely regulated output voltage at the rear output terminals install the jumpers by inserting the jumper wires into the jumper ter...

Страница 31: ...supply from the output terminals to the load or other distribution point terminals Thepowersupply provides sense connections beside the output terminals at the front and rear panels Use 22 24 AWG twis...

Страница 32: ...Section 3 Load Connection and Sensing Remote Sensing 20 Operating Manual for HPD Series Power Supply...

Страница 33: ...iven time depends on the combination of Output voltage setting VSET Output current limit setting ISET Resistance or impedance of the attached load RL Figure 4 1 represents the relationships between th...

Страница 34: ...current limit setting ISET VSET ISET RL In CI mode the power supply maintains the output current at the selected value ISET while the output voltage varies with the load requirements Setting the Curre...

Страница 35: ...rease above the setting of the current adjust control the unit switches automatically from CV to CI mode If you lower the load requirements the supply automatically returns to CV mode Constant Power L...

Страница 36: ...of one supply to the positive terminal of the next supply The total voltage available is the sum of the maximum voltages of each supply add voltmeter readings The maximum current available to the loa...

Страница 37: ...with the diodes as shown Damage to the sense circuits may occur As described below you can connect power supplies in parallel to obtain a single output supply with a higher output current limit Set al...

Страница 38: ...e output terminal of one supply to the positive terminal of the second supply as shown in Figure 4 5 The positive output terminal of the first supply now provides a positive voltage relative to the co...

Страница 39: ...ture which will allow one knob control of both supplies in a split supply configuration 27 Postive Sense Positive Output Terminal Negative Output Terminal Return Sense Load Lines Use the largest gauge...

Страница 40: ...APPENDIX RACK MOUNT INSTALLATION INSTRUCTIONS 28...

Страница 41: ...40 29 4X 9 ITEMS 10 AND 13 NOT USED FOR HPD...

Отзывы: