9
IOM (Safety) -
Installation, Operation and Maintenance
Optical Oxygen Analyzer
2.7 Hazardous Area Agency Certification & Markings - [Recapitulation]
2.7.1 Zone 1 Group IIC with Specific Conditions of Use
2.7.2 Zone 2 Group IIC with Specific Conditions of Use
OXYvisor
is certified as
Process Control Equipment
for use in
Zone Classified Hazardous Locations
(
QVAJ
and
QVAJ7
) - Zone 1, Group IIC
Specific Conditions of Use
- Consult Drawing No. 2P0345 for complete installation details.
•
Unused entries shall be closed with suitable certified Ex db blanking elements with a minimum IP66 rating
•
Flameproof joints are not intended to be repaired. For repair or replacement of any part, contact Barben Analytical.
0539
II 2 G Ex db op is IIC T4 Gb
Ex db op is IIC T4 Gb
Ta = -20 C to +55 C
Ta = -20 C to +55 C
Ta = -20 C to +55 C
Ta = -20 C to +55 C
Class 1 Zone 1 AEx db op is IIC T4 Gb
Ex db op is IIC T4 Gb
Certificate Number:
DEMKO 19 ATEX 2031, issued by UL DEMKO International A/S
Certificate Number:
IECEx UL 19.0040 issued by UL LLC
ATEX Zone 1, Group IIC Markings:
IECEx Zone 1, Group IIC Markings:
North American Zone 1, Group IIC Markings:
Standards:
EN 60079-0:2012+A11:2013
EN
60079-1:2014
EN
60079-28:2015
Standards:
IEC 60079-0,
6th Edition, Issued 2011-06
IEC 60079-1,
7th Edition, Issued 2014-06
IEC 60079-28,
2nd Edition, Issued 2015-05
US NEC Standards:
UL 60079-0,
6
th
Edition, Dated 2013-07-26
UL 60079-1,
7
th
Edition, Dated 2015-09-18
UL
60079-28,
2
nd
Edition, Dated 2017-09-15
CAN CEC Standards:
CSA C22.2 No. 60079-0,
3rd Edition, Dated 2015-10
CSA C22.2 No. 60079-1,
3rd Edition, Dated 2016-05
CSA C22.2 No. 60079-28,
1st Edition, Dated 2016-12
2.8 Product Label / Name Plate
2.8.1 - Product Label / Name Plate Overview
2.7.3 Class I, Division 2 Groups A,B,C, & D
The Product Label (Name Plate) is found at the top of the analyzer (Figure 1). The product label identifies important information and attributes of the
specific model and should be reviewed in detail prior to installation.
Class I, Division 2, Groups A, B, C, & D T4A
US NEC Standards:
UL 12.12.01 - Edition 9 Issued 2017/09/15
CAN CEC Standards:
CSA C22.2 No. 213-17 - Edition 3 Issued 2017/09/15
The
OXYvisor
is certified as
Process Control Equipment
for use in hazardous locations (
QUZW
,
QUZW7
)
Class I, Division 2 Groups A, B, C, & D
!
WARNING
!
WARNING
Section 2
Technical Product Specification
The
OXYvisor
is certified as
Process Control Equipment
for use in
Zone Classified Hazardous Locations
- Zone 2, Group IIC
Specific Conditions of Use
- Consult Drawing No. 2P0346 for complete installation details.
•
Transient protection shall be provided that is set at a level not exceeding 140% of the peak rated voltage value at the supply terminals to the equipment.
•
The equipment shall only be used in an area of not more than Pollution Degree 2, as defined in IEC/EN 60664-1.
II 3 G Ex ec [ic] op is IIC T4 Gc
Ta = -20 C to +55 C
Certificate Number:
DEMKO 19 ATEX 2036
ATEX Zone 2 Markings:
Standards:
CENELEC
EN 60079-0 +A11
2012, 2013
CENELEC
EN
60079-7
+A1
2015,
2018
CENELEC
EN
60079-11
2012
CENELEC
EN 60079-28
2015
Ex ec [ic] op is IIC T4 Gc
Class 1 Zone 2 AEx ec [ic] op is IIC T4 Gc
Class 1 Zone 2 Ex ec [ic] op is IIC T4 Gc
Certificate Number:
IECEx UL 19.0072
North American Zone 2, Group IIC Markings:
Standards:
IEC 60079-0,
Edition 6,
Issued 2014-10
IEC
60079-7, Edition
5.1,
Issued
2014-06
IEC
60079-11,
Edition
6,
Issued
2014-10
IEC
60079-28,
Edition
2,
Issued
2015-05
IEC
61010-2-201
Edition
1,
Issued
2013
US NEC Standards:
UL 60079-0,
Edition 6,
Dated 2017/10/20
UL 60079-7,
Edition 5.1, Dated 2017/04/21
UL 60079-11,
Edition 6,
Dated 2014/03/28
UL 60079-28,
Edition 2,
Dated 2017/12/08
CAN CEC Standards:
CSA C22.2 No. 60079-0, Edition 3,
Issue Date 2015/10/01
CSA C22.2 No. 60079-7, Edition 2,
Issue Date 2016
CSA C22.2 No. 60079-11, Edition 2,
Issue Date 2014/02/01
CSA C22.2 No. 60079-28, Edition 1,
Issue Date 2016