background image

29

Before You Call For Service…

Troubleshooting Tips
Save time and money! Review the charts on the following pages first and you may not need to call for service.

This water heater incorporates a combustion shut off device that shuts the operation of the water heater 

down if undesirable combustion conditions occur, such as the presence of flammable vapors or blockage of 

the combustion air inlet openings.  Please contact a Qualified Service Technician if this occurs.

CAUTION: For your safety DO NOT attempt repair of gas piping, gas control (thermostat), burners, vent connectors or other safety 

devices. Refer repairs to qualified service personnel.

Problem

 

Possible Causes

 

 

What To Do

Condensation 

This usually happens when   

  This is normal. After the water in the tank warms 

 

a new water heater is  

  up, the condensation will disappear. If, however, the  

 

filled for the first time.  

  condition persists, examine the piping and fittings  

 

 

  for possible leaks.

 

Moisture from the products 

  This is normal and will disappear in time. Excessive 

 

of combustion condensing  

  condensation can cause main burner outage. 

 

on the tank surface.

 

An undersized water  

  Use a water heater size that meets the requirements 

 

heater will cause  

  of your needs. 

 

condensation. 

Yellow flame

 

 

Scale on top of the burner. 

  Contact a qualified service technician to remove scale.

or soot 

Flue or Combustion air inlet  

  Remove obstruction or debris from flue or

 

openings are restricted.  

  combustion air inlet openings on water heater jacket. 

 

Not enough combustion or 

  Proper operation of the water heater requires air for 

 

ventilation air supplied to 

  combustion and ventilation. See the Combustion and 

 

the water heater location. 

  Ventilation Air information in the “Installing The    

 

 

  Water Heater” section of this manual.

Unable to light  

Air in gas line. 

  Contact a qualified service technician to purge the air  

the main burner 

 

 

from the gas line.

 

Blocked Exhaust 

 

Contact a qualified service technician to evaluate vent  

 

 

   pipe for blockage.

 

Pressure Switch 

  Make sure the pressure switch hose is not "kinked".

 

Wire Connection not fully 

  Contact a qualified service technician to confirm wire  

 

secured. 

  connections.

 

Combustion Shut-off Device

 

  Combustion shut-off device should be inspected by a  

 

tripped, 

  qualified service technician.

 

Gas Control Problem 

  Contact a qualified service technician.

Main burner does not

  

Combustion Shutoff Device 

  The combustion shutoff device should be inspected

stay lit

 

Tripped. 

  by a qualified service technician.

Содержание PowerVent

Страница 1: ...r This manual also includes a parts list It is very important that all persons who are expected to install operate or adjust this water heater read the instructions carefully so they may understand ho...

Страница 2: ...re on your part can save you time and money over the life of your water heater You ll find many answers to common problems in the Troubleshooting Guide If you review the chart of Troubleshooting Tips...

Страница 3: ...nts paint thinners etc and the vapors they produce are extremely dangerous DO NOT handle use or store gasoline or other flammable or combustible materials anywhere near or in the vicinity of a water h...

Страница 4: ...for Hot Water SCALDS The illustration below details the approximate water temperature for each mark on the Gas Control Thermostat Temperature Dial D A N G E R HOT Water temperature over 125 can cause...

Страница 5: ...LP gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level Before attempting to light the water heater make sure to look...

Страница 6: ...installation For residential water heaters of a capacity greater than 52 gallons consult the local building jurisdiction for acceptable bracing procedures Have the installer show you the location of t...

Страница 7: ...r heater to ignite until examined by a Qualified Service Technician DO NOT obstruct or block the flammable vapor sensor Rheem Water Heating FVIR certified gas water heaters can be installed on a resid...

Страница 8: ...than one square inch per 4000 Btuh of the total input rating of all the appliances in the enclosure If horizontal ducts are used to communicate with the outdoors each opening must have a minimum net...

Страница 9: ...dition and eliminating the repeated operation of the relief valve Other methods of controlling thermal expansion are also available Contact your installing contractor water supplier or plumbing inspec...

Страница 10: ...cealed and should be protected from freezing No valve of any type restriction or reducer coupling should be installed in the discharge line To Fill the Water Heater Make certain that the drain valve i...

Страница 11: ...pe gas shut offs are used they shall be T Handle type Compound used on the threaded joints of the gas piping must be of the type resistant to the action of LP gas Use compound sparingly on male thread...

Страница 12: ...detailed in this manual have been met Carefully inspect the entire venting system for any signs of cracks or fractures particularly at the joints between elbows or other fittings and the straight len...

Страница 13: ...rtical pipe one 1 90 elbow and two 2 feet of horizontal pipe Number of 90 elbows with Vent Number of 45 Elbows Maximum Vent Pipe Length in Feet ft 0 Maximum Altitude See chart on upper left One 1 None...

Страница 14: ...reeze on the exterior wall under the eaves and on surrounding objects Some discoloration to the exterior of the building is to be expected However improper location or installation can result in sever...

Страница 15: ...nal fitting and connect it as shown to the vent pipe on the exterior of the building Complete the rest of the vent pipe installation to the water heater s vent connector fitting on the blower outlet I...

Страница 16: ...the joint with a rag Allow 15 minutes before handling Cure time will vary according to fit temperature and humidity NOTICE Stir the solvent cement frequently while using Use a natural bristle brush or...

Страница 17: ...local codes or in the absence of local codes in accordance with latest edition of the National Electric Code ANSI NFPA No 70 Refer to the figures below for water heater internal wiring NOTE It is not...

Страница 18: ...om the use of such unauthorized devices CAUTION If local codes require the application of an external insulation blanket to this water heater pay careful attention to the following so as not to restri...

Страница 19: ...tion Air holes see diagram to the left DON T remove the Burner Access Door unless absolutely necessary This should only be done by a qualified service technician A new burner access door gasket must b...

Страница 20: ...and free of leaks Gas line equipped with shut off valve union and sediment trap Approved pipe joint compound used Soap and water solution used to check all connections and fittings for possible gas l...

Страница 21: ...Heating Installation Spring loaded check valve in heating unit hot water supply line and cold water return line not supplied with water heater NOTE This check valve is incorporated in some heating un...

Страница 22: ...e Set the valve thermostat dial to LOW This appliance has an automatic spark ignition system DO NOT attempt to light the pilot by hand Wait five 5 minutes to clear out any gas If you smell gas stop Fo...

Страница 23: ...ermostat setting to prevent contact with HOT water Water Temperature Setting The temperature of the water in the water heater can be regulated by turning the knob on the front of the gas control therm...

Страница 24: ...ise young children or others who are incapacitated The gas control thermostat is constructed with a built in safety shut off device designed to shut off the gas supply to the burner if the main burner...

Страница 25: ...er flames 8 The blower motor will stay energized for an additional 30 seconds after the control verifies that the burner flame is extinguished in order to clear combustion gases from the water heater...

Страница 26: ...and pressure relief valve on the water heater discharges periodically this may be due to thermal expansion in a closed water system Contact the water supplier or your plumbing contractor on how to cor...

Страница 27: ...d leak testing The burner chamber is a sealed area If the burner access door is removed the burner access door gasket must be replaced For cleaning remove the burner from the water heater A vacuum cle...

Страница 28: ...Gas Caution in the Operating Instructions Anode Rod This water heater is equipped with an anode rod designed to prolong the life of the glass lined tank The anode rod is slowly consumed thereby elimin...

Страница 29: ...Use a water heater size that meets the requirements heater will cause of your needs condensation Yellow flame Scale on top of the burner Contact a qualified service technician to remove scale or soot...

Страница 30: ...ion Shutoff System Contact a qualified service technician tripped Water is too hot The gas control thermostat See the Water Temperature Setting of The Water is set too high Heater section of this manu...

Страница 31: ...open 1 Replace gas valve control Six One Flash three second pause Failed trial for ignition Insufficient gas supply unstable pilot carbon buildup on electrode or wire pilot tube damage 1 Check gas sup...

Страница 32: ...the rating plate Specify type of gas natural or LP as marked on the rating plate Part description as noted below and number of parts desired CAUTION For your safety DO NOT attempt repair of gas piping...

Страница 33: ...arts The kit provides extra speed clips and tamper resistant screws Burner Access Door Assembly Burner Access Door Gasket Burner Pilot Bracket Screws Pilot Bracket Pilot Screw Burner Hex Nuts Pilot Tu...

Страница 34: ...34 Notes...

Страница 35: ...35 Notes...

Страница 36: ...rbon monoxide detec tor with alarm and battery back up may be installed on the next adjacent floor level b In the event that the requirements of this subdivision can not be met at the time of completi...

Отзывы: