WARNING: Do not attempt to convert this water heater for use with a different type of gas other than the type 

shown on the rating plate. Such conversion could result in hazardous operating conditions.

Leak Testing

The water heater and its gas connections 

must be leak tested at normal operating 

pressures before it is placed in operation.

   Turn on the manual gas shut-off 

valve near the water heater.

   Use a soapy water solution to test for 

leaks at all connections and fittings. 

Bubbles indicate a gas leak that must 

be corrected. 

The factory connections to the gas 

control (thermostat) should also be leak 

tested after the water heater is placed in 

operation.

Pressure Testing the Gas Supply System

The water heater and its manual gas 

shut-off valve must be disconnected from 

the gas supply piping system during any 

pressure testing of that system at 

pressures in excess of 3/8 psi (10.5” w.c.) 

for natural gas.

The water heater must be isolated from 

the gas piping system by closing the 

manual gas shut-off valve during any 

pressure testing of the gas supply piping 

at pressures equal to or less than  

3/8 psi (10.5” w.c.) for natural gas

Gas Supply

The branch gas supply line to the water 

heater should be clean 1/2” black steel 

pipe or other approved gas piping 

material.
A ground joint union or ANSI design 

certified semi-rigid or flexible gas 

appliance connector should be installed 

in the gas line close to the water heater. 

The National Fuel Gas Code (NFGC) 

mandates a manual gas shut-off valve: See 

(NFGC) for complete instructions.
If flexible connectors are used, the 

maximum length shall not exceed 36” 

and must meet the requirements in ANSI 

Z21.24-Connectors for Gas Appliances.
If lever type gas shut-offs are used, 

they  shall be T-Handle type.
Compound used on the threaded joints of 

the gas piping must be of the type resistant 

to the action of LP gas. Use compound 

sparingly on male threads only. 

Where a sediment trap is not incorporated 

as part of the appliance, a sediment trap 

shall be installed downstream of the 

equipment shutoff valve as close to the 

inlet of the appliance as practical at the 

time of the appliance installation. The 

sediment trap shall be either a tee fitting 

with a capped nipple in the bottom outlet 

or other device recognized as an effective 

sediment trap.
Do not use excessive force (over 31.5 ft 

lbs.) in tightening the pipe joint at the gas 

control (thermostat) inlet, particularly if 

teflon pipe compound is used, as the valve  

body may be damaged.
The inlet gas pressure to the water heater 

must not exceed 10.5” w.c. for natural 

gas. For purposes of input adjustment, the 

minimum inlet gas pressure (with main 

burner on) is shown on the water heater 

rating plate. If high or low gas pressures 

are present, contact your gas supplier for 

correction.

WARNING: Never use 

an open flame to test for 

gas leaks, as property 

damage, personal injury, or 

death  could result.

High Altitude

Input rating of this water heater is 

based on sea level operation.  At higher 

elevations the actual input rate may be 

lower than the value listed on the rating 

label due to the derating of natural gas.  

This water heater can be installed at 

elevation up to 2,000 feet without any 

change or modification.

Installations above 2,000 feet are not 

authorized.
Contact the local gas supplier for more 

information.

WARNING: Failure to 

install a water heater 

suitable for the altitude at 

the location it is intended to 

serve, can result in improper 

operation of the appliance 

resulting in property 

damage and/or producing 

carbon monoxide gas, which 

could result in personal 

injury, or death.

11

Содержание PowerVent

Страница 1: ...r This manual also includes a parts list It is very important that all persons who are expected to install operate or adjust this water heater read the instructions carefully so they may understand ho...

Страница 2: ...re on your part can save you time and money over the life of your water heater You ll find many answers to common problems in the Troubleshooting Guide If you review the chart of Troubleshooting Tips...

Страница 3: ...nts paint thinners etc and the vapors they produce are extremely dangerous DO NOT handle use or store gasoline or other flammable or combustible materials anywhere near or in the vicinity of a water h...

Страница 4: ...for Hot Water SCALDS The illustration below details the approximate water temperature for each mark on the Gas Control Thermostat Temperature Dial D A N G E R HOT Water temperature over 125 can cause...

Страница 5: ...LP gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level Before attempting to light the water heater make sure to look...

Страница 6: ...installation For residential water heaters of a capacity greater than 52 gallons consult the local building jurisdiction for acceptable bracing procedures Have the installer show you the location of t...

Страница 7: ...r heater to ignite until examined by a Qualified Service Technician DO NOT obstruct or block the flammable vapor sensor Rheem Water Heating FVIR certified gas water heaters can be installed on a resid...

Страница 8: ...than one square inch per 4000 Btuh of the total input rating of all the appliances in the enclosure If horizontal ducts are used to communicate with the outdoors each opening must have a minimum net...

Страница 9: ...dition and eliminating the repeated operation of the relief valve Other methods of controlling thermal expansion are also available Contact your installing contractor water supplier or plumbing inspec...

Страница 10: ...cealed and should be protected from freezing No valve of any type restriction or reducer coupling should be installed in the discharge line To Fill the Water Heater Make certain that the drain valve i...

Страница 11: ...pe gas shut offs are used they shall be T Handle type Compound used on the threaded joints of the gas piping must be of the type resistant to the action of LP gas Use compound sparingly on male thread...

Страница 12: ...detailed in this manual have been met Carefully inspect the entire venting system for any signs of cracks or fractures particularly at the joints between elbows or other fittings and the straight len...

Страница 13: ...rtical pipe one 1 90 elbow and two 2 feet of horizontal pipe Number of 90 elbows with Vent Number of 45 Elbows Maximum Vent Pipe Length in Feet ft 0 Maximum Altitude See chart on upper left One 1 None...

Страница 14: ...reeze on the exterior wall under the eaves and on surrounding objects Some discoloration to the exterior of the building is to be expected However improper location or installation can result in sever...

Страница 15: ...nal fitting and connect it as shown to the vent pipe on the exterior of the building Complete the rest of the vent pipe installation to the water heater s vent connector fitting on the blower outlet I...

Страница 16: ...the joint with a rag Allow 15 minutes before handling Cure time will vary according to fit temperature and humidity NOTICE Stir the solvent cement frequently while using Use a natural bristle brush or...

Страница 17: ...local codes or in the absence of local codes in accordance with latest edition of the National Electric Code ANSI NFPA No 70 Refer to the figures below for water heater internal wiring NOTE It is not...

Страница 18: ...om the use of such unauthorized devices CAUTION If local codes require the application of an external insulation blanket to this water heater pay careful attention to the following so as not to restri...

Страница 19: ...tion Air holes see diagram to the left DON T remove the Burner Access Door unless absolutely necessary This should only be done by a qualified service technician A new burner access door gasket must b...

Страница 20: ...and free of leaks Gas line equipped with shut off valve union and sediment trap Approved pipe joint compound used Soap and water solution used to check all connections and fittings for possible gas l...

Страница 21: ...Heating Installation Spring loaded check valve in heating unit hot water supply line and cold water return line not supplied with water heater NOTE This check valve is incorporated in some heating un...

Страница 22: ...e Set the valve thermostat dial to LOW This appliance has an automatic spark ignition system DO NOT attempt to light the pilot by hand Wait five 5 minutes to clear out any gas If you smell gas stop Fo...

Страница 23: ...ermostat setting to prevent contact with HOT water Water Temperature Setting The temperature of the water in the water heater can be regulated by turning the knob on the front of the gas control therm...

Страница 24: ...ise young children or others who are incapacitated The gas control thermostat is constructed with a built in safety shut off device designed to shut off the gas supply to the burner if the main burner...

Страница 25: ...er flames 8 The blower motor will stay energized for an additional 30 seconds after the control verifies that the burner flame is extinguished in order to clear combustion gases from the water heater...

Страница 26: ...and pressure relief valve on the water heater discharges periodically this may be due to thermal expansion in a closed water system Contact the water supplier or your plumbing contractor on how to cor...

Страница 27: ...d leak testing The burner chamber is a sealed area If the burner access door is removed the burner access door gasket must be replaced For cleaning remove the burner from the water heater A vacuum cle...

Страница 28: ...Gas Caution in the Operating Instructions Anode Rod This water heater is equipped with an anode rod designed to prolong the life of the glass lined tank The anode rod is slowly consumed thereby elimin...

Страница 29: ...Use a water heater size that meets the requirements heater will cause of your needs condensation Yellow flame Scale on top of the burner Contact a qualified service technician to remove scale or soot...

Страница 30: ...ion Shutoff System Contact a qualified service technician tripped Water is too hot The gas control thermostat See the Water Temperature Setting of The Water is set too high Heater section of this manu...

Страница 31: ...open 1 Replace gas valve control Six One Flash three second pause Failed trial for ignition Insufficient gas supply unstable pilot carbon buildup on electrode or wire pilot tube damage 1 Check gas sup...

Страница 32: ...the rating plate Specify type of gas natural or LP as marked on the rating plate Part description as noted below and number of parts desired CAUTION For your safety DO NOT attempt repair of gas piping...

Страница 33: ...arts The kit provides extra speed clips and tamper resistant screws Burner Access Door Assembly Burner Access Door Gasket Burner Pilot Bracket Screws Pilot Bracket Pilot Screw Burner Hex Nuts Pilot Tu...

Страница 34: ...34 Notes...

Страница 35: ...35 Notes...

Страница 36: ...rbon monoxide detec tor with alarm and battery back up may be installed on the next adjacent floor level b In the event that the requirements of this subdivision can not be met at the time of completi...

Отзывы: