American Standard AccuLink Platinum 850 Скачать руководство пользователя страница 9

 

850 Communicating Wi-Fi Comfort Control

 11-HD14D1-9-EN 9

5.4.3 Group 4 Accessories Settings

MENU ITEM

OPTIONS [DEFAULT] DESCRIPTION

Filtration Type Installed

Air Cleaner, [Media 
Filter], Comm Air Cleaner 
Discovered

Select the filter type installed

Number Of Air Cleaners installed

[1], 2

Select the number of Comm Air Cleaners installed

Humidifier Installed

[No], Yes

Select whether a humidifier is installed

Humidifier Type

[Powered/Bypass], Steam

Select what type of humidifier is installed

Humidifier Control

[RH Control], Frost Control

Select how the humidifier will be controlled (Outdoor temperature 
sensor must be connected and enabled to allow this setting to be 
selected)

Humidifier Fan Action

[Humidify with Active Heat 
Call], Humidify without 
Active Heat Call

Select when the humidifier is allowed to operate (Humidification is 
disallowed during cooling mode or when the System Mode is Auto but 
the last call was cooling)

Airflow During Humidifier Only Mode

35% - [100%] 50

Select the desired airflow when the humidifier is operating without an 
active call for heat

UV Light Installed

[No], Yes

Select whether a UV Light is installed

Ventilation Installed

[No], Yes

Select whether a ventilation system is installed

Ventilation - Select Aux Contact

Aux 1, Aux 2

Select which set of aux contacts is controlling the ventilation system

Outdoor Temperature Ventilation Override

[Disable], Enable

Select whether an outdoor temperature override is allowed  (Outdoor 
temperature sensor must be connected and enabled to allow this 
setting to be selected)

Ventilator Fan Action

[Ventilate with Blower], 
Ventilate without Blower

Select whether the indoor blower operates on a call for ventilation

Ventilation - Minimum Outdoor Temperature

-10°F - 50°F [0°]

Select the minimum outdoor temperature that ventilation is allowed

Ventilation - Maximum Outdoor Temperature

80°F - 110°F [100°F]

Select the maximum outdoor temperature that ventilation is allowed

Minimum Ventilation Runtime

0 - 60 Minutes [5 Minutes]

Select the minimum runtime per hour for ventilation system

Acculate Overridden Runtime

[No], Yes

Select whether the overridden ventilation runtime will be made up

Acculate Period

[4 hrs -recover based on 
OD conditions], 
24 hrs - recover based on 
OD conditions, 
4 hrs - recover to maintain 
min ventilation, 
24 hrs - recover to maintain 
min ventilation

Select when to recover missed ventilation runtime due to outdoor 
conditions exceeding the minimum/maximum outdoor temperate for 
ventilation (The first two options will not meet AHRAE 62.2 standard for 
minimum ventilation requirements)

Dehumidifier Installed

[None], Yes

Select whether a dehumidifier is installed

Dehumidifier - Select AUX Contact

Aux 1, Aux 2

Select which set of aux contacts is controlling the dehumidifier

Run System Fan With Dehumidifier Request

[Yes], No

Select whether the indoor blower operates with a call for 
dehumidification

5.4.4 Group 3 Sensor Settings

MENU ITEM

OPTIONS [DEFAULT]

DESCRIPTION

Select Outdoor Temperature Sensor

No ODT Sensor
Thermostat ODT Sensor
Communicating ODT Sensor
Relay Panel ODT Sensor

Select whether an outdoor temperature sensor has been connected 

Calibrate Outdoor Temperature Sensor

-5°F to 5°F

Calibrate the outdoor temperature sensor 

Select Indoor Temperature Sensor

[Onboard IDT Sensor]
Remote IDT Sensor

Select whether to use the onboard IDT or a remote IDT

Calibrate Indoor Temperature Sensor

-5% to 5%

Calibrate the onboard humidity sensor 

Содержание AccuLink Platinum 850

Страница 1: ...property and is to remain with this unit These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation Should furthe...

Страница 2: ...3 1 Overview 3 3 2 Contents 3 3 3 Accessories 3 4 Installation 4 4 1 Location 4 4 2 Network Connections 4 4 3 Mounting 4 4 4 Wiring 5 4 5 Field Wiring Connection Diagrams 6 5 System Setup 7 5 1 Power...

Страница 3: ...e 0 to 100 1 resolution Minimum Cycle Off Time Delay Compressor 5 minutes Indoor Heat 1 minute On every application 24VAC loads should be reviewed to be sure the indoor unit control power transformer...

Страница 4: ...e Control s communication i e wireless phones security systems wireless Internet cameras Do not mount the Control in recessed areas near metal objects or near structures i e doors appliances entertain...

Страница 5: ...s extend through the hole in the Sub base see Figure 4 on page 5 4 4 Wiring 1 Adjust the length and position of each wire to reach the proper terminal on the connector block of the Sub base Strip 1 4...

Страница 6: ...r Optional Remote Sensor Communicating Indoor w Non Communicating Outdoor COMMUNICATING INDOOR UNIT excluding TAM8 24V SINGLE STAGE COOLING OUTDOOR 850 COMFORT CONTROL Caution Do not run Outdoor Remot...

Страница 7: ...the navigational steps and screen prompts installer s are guided through the Time and Date Installer Setup see 5 4 Installer Setup Screens on page 8 for detailed descriptions of each of the Installer...

Страница 8: ...ment Settings MENU ITEM OPTIONS DEFAULT DESCRIPTION Compressor Cooling Cycles Per Hour 2 6 Cph 3 Select of cycles per hour during cooling operation 1st Stage Compressor Cooling Cycles Per Hour 2 6 Cph...

Страница 9: ...elect whether the indoor blower operates on a call for ventilation Ventilation Minimum Outdoor Temperature 10 F 50 F 0 Select the minimum outdoor temperature that ventilation is allowed Ventilation Ma...

Страница 10: ...or additional information Aggressive Recovery 2 Setpoint Change Enable Disable Select whether the 10 minute staging inhibit is disabled heating or cooling mode with a setpoint change greater than 2 Se...

Страница 11: ...minutes at 80 then 100 Non VS Blower On Delay Comp Htg No Delay 15 Seconds 30 Seconds Select the blower on delay for compressor heating operation VS Blower Off Delay Comp Htg No Delay 1 5 Minutes 100...

Страница 12: ...frost above this temperature Compressor Cooling 1st Stage Lockout Disable Enable Enable compressor cooling 1st stage lockout Compressor Cooling 1st Stage Lockout Setting 80 F 120 F Select an outdoor t...

Страница 13: ...0 475 Two Stage Heat Pump 3 Stage Gas Oil Heat 6 3 Load Value Cooling 0 100 Single Stage Compressor 0 200 Two Stage Compressor A Load Value of 50 represents a request of 50 demand for single stage co...

Страница 14: ...STAGE 3 AUX WET HEAT STAGING THRESHOLDS 100 125 100 125 200 215 200 215 Compressor to W1 Compressor to W1 W1 to W2 W1 to W2 6 7 Stage Inhibits When the stage threshold is exceeded a stage inhibit is...

Страница 15: ...only limit Daytime operation only limit Nighttime or limit Daytime and Nighttime to different demands Night mode affects operation from 10 PM until 9 AM at which point Day settings for Quiet Mode take...

Страница 16: ...hen indoor humidity exceeds the desired cooling RH This feature can be enabled in the Installer Settings Comfort Settings Smart Continuous Fan settings 7 3 Dehumidifier Operation The 850 has the abili...

Страница 17: ...outs The 850 has the following lockouts AN OUTDOOR TEMPERATURE SENSOR MUST BE ENABLED FOR LOCKOUT SETTINGS TO BE AVAILABLE Lockouts can be enabled in Installer Setup Lockout Settings Auxiliary Heat Lo...

Страница 18: ...ASHRAE 62 2 standards A temperature override can be set to prevent ventilation operation when the outdoor temperature exceeds the minimum or maximum outdoor temperature selections If outdoor temperat...

Страница 19: ...ated indoor blower speed to set verify sytem charge Use sub cooling tables in the outdoor unit Service Facts to determine correct charge levels Outdoor temperature must be within 55F to 120F and indoo...

Страница 20: ...Normal alerts are only displayed in the Diagnostic screen Diagnostics can be accessed by navigating to Service Menu Diagnostics 8 3 2 Summary Table The 850 Control has a Summary Table which lists all...

Страница 21: ...eens Operating State Stage Requested Capacity Delivered Compressor Speed Load Value Fan Mode Air Flow Indoor Outdoor Temperatures Heating Cooling Set Points Indoor RH Heating Cooling RH Set Points 8 6...

Страница 22: ...ating or Cooling is displayed but no warm or cool air is coming from the registers 1 There is a fan delay as the heating or cooling equipment turns on 2 Equipment is not working properly 1 Wait a minu...

Страница 23: ...cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the...

Страница 24: ...D1 9 EN The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Representative only illustrations...

Отзывы: