American Standard AccuLink Platinum 850 Скачать руководство пользователя страница 16

Installation Guide

16  

11-HD14D1-9-EN

7.  Advanced Operation

7.1  Control response rate 

Allows the user to select a set of higher proportional-
integral control constants to increase the responsiveness 
of the Control. Selecting “Fast” will cause the Control to 
generate load value at a faster rate. Control Response rate 
can be adjusted in Installer Setup>Comfort Settings. 

7.2  Dehumidification

The 850 utilizes the following methods for dehumidification:

• 

Air flow reduction (applies only to variable speed 
blowers) – The 850 can reduce the system air flow 
by 30% anytime the indoor RH is higher than the 
cooling RH target. Air flow reduction is disallowed if 
the indoor temperature is more than 2°F above the 
cooling setpoint. Dehumidification is factory enabled 
in the Installer Setup>Comfort Settings.
All “Fan Off” delays are also defeated when 
dehumidification is enabled and the indoor RH 
exceeds the cooling RH target.

• 

Overcooling (applies to variable speed and non-
variable speed blowers) - If overcooling is enabled, 
the Control will allow a 0.1°F of overcooling for each 
1% of RH error. A maximum amount of overcooling 
can be configured for 1°, 2° or 3°F. 

EXAMPLE OF OVERCOOLING

WITH MAXIMUM CONFIGURED AT 2

°

TARGET 

HUMIDITY

ACTUAL 

HUMIDITY

PERCENT 

OF RH 

ERROR

DEGREES OF 

OVERSHOOT

40%

45%

5%

0.5

° Overshoot

40%

55%

15%

1.5

° Overshoot

40%

65%

25%

2.0

° Overshoot

40%

70%

30%

2.0

° Overshoot

When the system is actively overcooling, 
Dehumidification will be displayed on the 850 home 
screen. The maximum amount of overcooling is 
configured in Installer Setup>Comfort settings.

• 

Smart Continuous Fan (applies to variable speed and 
non-variable speed blowers) – If enabled, continuous 
fan operation will be interrupted when indoor RH 
exceeds desired cooling RH target. A humidity icon 
will be displayed along with the fan icon to indicate 
that continuous fan operation has been disabled due 
to high humidity conditions. Smart Continuous Fan 
will also interrupt the fan circulate mode when indoor 
humidity exceeds the desired cooling RH.  This feature 
can be enabled in the Installer Settings>Comfort 
Settings>Smart Continuous Fan settings.

7.3  Dehumidifier Operation

The 850 has the ability to control a Whole-House 
Dehumidifier through the normally open dry AUX Contacts 
on the optional Relay Paned. Control options are:

• 

Stand Alone Operation – Dehumidifier can operate 
independent from cooling operation as long as the 
850 Control is in Cooling mode or Auto mode and the 
last call was cooling.
If Stand Alone Operation is selected, the 850 Control 
allows the user to select whether the indoor fan 
operates with dehumidifier request.

• 

With Active Call for Cooling Only – Dehumidifier can 
only operate during an active call for cooling.

All dehumidifier control options are located in the 
Installer Setup>Accessories  Settings.

7.4  Dual Fuel Operation

The 850 can control a dual fuel system without the need of 
an external dual fuel kit. An Outdoor Temperature Sensor 
must be installed and enabled for Restricted Modes to be 
available. The 850 Control options are: 

• 

Non Restricted Mode – The Control will determine 
which mode of heat will operate to maintain comfort 
based on the calculated system load value. With a load 
value in compressor heating range the heat pump will 
operate and if the load value climbs to auxiliary heat 
range, the heat pump will cycle off and the auxiliary 
heat source will cycle on. Once the load value falls 
below the auxiliary heat range, the auxiliary heat will 
cycle off, and the heat pump will cycle back on.

• 

Restricted Mode (compressor heat only) – Once 
enabled an outdoor temperature lockout can be set 
to disable compressor heating operation. When the 
outdoor temperature falls below the compressor 
heat lockout the system will operate on auxiliary 
heat source only. At any temperature above the 
compressor heat lockout the system will operate 
the same as non-restricted mode, heat pump or 
auxiliary heat would be allowed based on system 
load value. Once the compressor heat is locked out, 
the outdoor temperature must rise at least 4° above 
the compressor heat lockout setting before allowing 
compressor heat again.

Содержание AccuLink Platinum 850

Страница 1: ...property and is to remain with this unit These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation Should furthe...

Страница 2: ...3 1 Overview 3 3 2 Contents 3 3 3 Accessories 3 4 Installation 4 4 1 Location 4 4 2 Network Connections 4 4 3 Mounting 4 4 4 Wiring 5 4 5 Field Wiring Connection Diagrams 6 5 System Setup 7 5 1 Power...

Страница 3: ...e 0 to 100 1 resolution Minimum Cycle Off Time Delay Compressor 5 minutes Indoor Heat 1 minute On every application 24VAC loads should be reviewed to be sure the indoor unit control power transformer...

Страница 4: ...e Control s communication i e wireless phones security systems wireless Internet cameras Do not mount the Control in recessed areas near metal objects or near structures i e doors appliances entertain...

Страница 5: ...s extend through the hole in the Sub base see Figure 4 on page 5 4 4 Wiring 1 Adjust the length and position of each wire to reach the proper terminal on the connector block of the Sub base Strip 1 4...

Страница 6: ...r Optional Remote Sensor Communicating Indoor w Non Communicating Outdoor COMMUNICATING INDOOR UNIT excluding TAM8 24V SINGLE STAGE COOLING OUTDOOR 850 COMFORT CONTROL Caution Do not run Outdoor Remot...

Страница 7: ...the navigational steps and screen prompts installer s are guided through the Time and Date Installer Setup see 5 4 Installer Setup Screens on page 8 for detailed descriptions of each of the Installer...

Страница 8: ...ment Settings MENU ITEM OPTIONS DEFAULT DESCRIPTION Compressor Cooling Cycles Per Hour 2 6 Cph 3 Select of cycles per hour during cooling operation 1st Stage Compressor Cooling Cycles Per Hour 2 6 Cph...

Страница 9: ...elect whether the indoor blower operates on a call for ventilation Ventilation Minimum Outdoor Temperature 10 F 50 F 0 Select the minimum outdoor temperature that ventilation is allowed Ventilation Ma...

Страница 10: ...or additional information Aggressive Recovery 2 Setpoint Change Enable Disable Select whether the 10 minute staging inhibit is disabled heating or cooling mode with a setpoint change greater than 2 Se...

Страница 11: ...minutes at 80 then 100 Non VS Blower On Delay Comp Htg No Delay 15 Seconds 30 Seconds Select the blower on delay for compressor heating operation VS Blower Off Delay Comp Htg No Delay 1 5 Minutes 100...

Страница 12: ...frost above this temperature Compressor Cooling 1st Stage Lockout Disable Enable Enable compressor cooling 1st stage lockout Compressor Cooling 1st Stage Lockout Setting 80 F 120 F Select an outdoor t...

Страница 13: ...0 475 Two Stage Heat Pump 3 Stage Gas Oil Heat 6 3 Load Value Cooling 0 100 Single Stage Compressor 0 200 Two Stage Compressor A Load Value of 50 represents a request of 50 demand for single stage co...

Страница 14: ...STAGE 3 AUX WET HEAT STAGING THRESHOLDS 100 125 100 125 200 215 200 215 Compressor to W1 Compressor to W1 W1 to W2 W1 to W2 6 7 Stage Inhibits When the stage threshold is exceeded a stage inhibit is...

Страница 15: ...only limit Daytime operation only limit Nighttime or limit Daytime and Nighttime to different demands Night mode affects operation from 10 PM until 9 AM at which point Day settings for Quiet Mode take...

Страница 16: ...hen indoor humidity exceeds the desired cooling RH This feature can be enabled in the Installer Settings Comfort Settings Smart Continuous Fan settings 7 3 Dehumidifier Operation The 850 has the abili...

Страница 17: ...outs The 850 has the following lockouts AN OUTDOOR TEMPERATURE SENSOR MUST BE ENABLED FOR LOCKOUT SETTINGS TO BE AVAILABLE Lockouts can be enabled in Installer Setup Lockout Settings Auxiliary Heat Lo...

Страница 18: ...ASHRAE 62 2 standards A temperature override can be set to prevent ventilation operation when the outdoor temperature exceeds the minimum or maximum outdoor temperature selections If outdoor temperat...

Страница 19: ...ated indoor blower speed to set verify sytem charge Use sub cooling tables in the outdoor unit Service Facts to determine correct charge levels Outdoor temperature must be within 55F to 120F and indoo...

Страница 20: ...Normal alerts are only displayed in the Diagnostic screen Diagnostics can be accessed by navigating to Service Menu Diagnostics 8 3 2 Summary Table The 850 Control has a Summary Table which lists all...

Страница 21: ...eens Operating State Stage Requested Capacity Delivered Compressor Speed Load Value Fan Mode Air Flow Indoor Outdoor Temperatures Heating Cooling Set Points Indoor RH Heating Cooling RH Set Points 8 6...

Страница 22: ...ating or Cooling is displayed but no warm or cool air is coming from the registers 1 There is a fan delay as the heating or cooling equipment turns on 2 Equipment is not working properly 1 Wait a minu...

Страница 23: ...cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the...

Страница 24: ...D1 9 EN The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Representative only illustrations...

Отзывы: