American Standard AccuLink Platinum 850 Скачать руководство пользователя страница 5

 

850 Communicating Wi-Fi Comfort Control

 11-HD14D1-9-EN 5

6.  Place the Sub-base against the wall in the desired 

location and mark the wall through the mounting 
holes. If you are using a wired Internet connection, be 
sure to mark the cutout for the RJ-45 connector (see 
Figure 2 on page 5).

7.  Drill the holes in the wall where marked.

If you are using a wireless Internet connection, skip to 
step 9.

8.  When using a wired Ethernet connection, follow these 

step and refer to Figure 3 on page 5.
a.  With the Sub-base and RJ-45 holder oriented as 

shown, press the holder into the Sub-base.

b.  Slide the holder to the right so it snaps in place.
c.  Secure the holder with the provided screw.
d.  Insert the RJ-45 Connector into the RJ-45 

 

holder until it snaps into place.

9.  Mount the Sub-base to the wall using included 

mounting screws and drywall anchors. An optional 
mounting hole is available for more secure mounting, 
if needed. Make sure all wires extend through the hole 
in the Sub-base see Figure 4 on page 5.

4.4  Wiring

1.  Adjust the length and position of each wire to reach 

the proper terminal on the connector block of the 
Sub-base. Strip 1/4” of insulation from each wire. 
Do not allow adjacent wires to short together when 
connected. 

2.  Match and connect control wires to the proper 

terminals on the connector block. Refer to Field Wiring 
Diagrams included in this document.

3.  Push excess wire back into the wall and seal the 

hole to prevent air leaks. NOTE: Air Leaks in the wall 

behind the Control can cause improper operation. 

4.  Attach the Control to the Sub-base.
5.  Turn ON power to the heating and cooling equipment.

B/C R

D ODT ODT RS1 RS1

Mounting Holes

Optional Mounting Hole

Wall

Thermostat Wiring

Ethernet
Wiring

Thermostat

Wires

RJ-45

Plug

RS1 RS1 ODT ODT W3 W2 W1 BK

G

Y2 Y1

O B/C RH RC AUX2 AUX2 AUX1 AUX1

Mounting Holes

Optional Mounting Hole

Wall

Thermostat Wiring

Ethernet
Wiring

Thermostat

Wires

RJ-45

Plug

FIGure 2. 

MARK THE MOUNTING HOLES

FIGure 3. 

ATTACH RJ-45 HOLDER TO SUB-BASE

This side mounts to wall

Wall

a

b

c

d

FIGure 4. 

MOUNT THE SUB-BASE TO THE WALL

Содержание AccuLink Platinum 850

Страница 1: ...property and is to remain with this unit These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation Should furthe...

Страница 2: ...3 1 Overview 3 3 2 Contents 3 3 3 Accessories 3 4 Installation 4 4 1 Location 4 4 2 Network Connections 4 4 3 Mounting 4 4 4 Wiring 5 4 5 Field Wiring Connection Diagrams 6 5 System Setup 7 5 1 Power...

Страница 3: ...e 0 to 100 1 resolution Minimum Cycle Off Time Delay Compressor 5 minutes Indoor Heat 1 minute On every application 24VAC loads should be reviewed to be sure the indoor unit control power transformer...

Страница 4: ...e Control s communication i e wireless phones security systems wireless Internet cameras Do not mount the Control in recessed areas near metal objects or near structures i e doors appliances entertain...

Страница 5: ...s extend through the hole in the Sub base see Figure 4 on page 5 4 4 Wiring 1 Adjust the length and position of each wire to reach the proper terminal on the connector block of the Sub base Strip 1 4...

Страница 6: ...r Optional Remote Sensor Communicating Indoor w Non Communicating Outdoor COMMUNICATING INDOOR UNIT excluding TAM8 24V SINGLE STAGE COOLING OUTDOOR 850 COMFORT CONTROL Caution Do not run Outdoor Remot...

Страница 7: ...the navigational steps and screen prompts installer s are guided through the Time and Date Installer Setup see 5 4 Installer Setup Screens on page 8 for detailed descriptions of each of the Installer...

Страница 8: ...ment Settings MENU ITEM OPTIONS DEFAULT DESCRIPTION Compressor Cooling Cycles Per Hour 2 6 Cph 3 Select of cycles per hour during cooling operation 1st Stage Compressor Cooling Cycles Per Hour 2 6 Cph...

Страница 9: ...elect whether the indoor blower operates on a call for ventilation Ventilation Minimum Outdoor Temperature 10 F 50 F 0 Select the minimum outdoor temperature that ventilation is allowed Ventilation Ma...

Страница 10: ...or additional information Aggressive Recovery 2 Setpoint Change Enable Disable Select whether the 10 minute staging inhibit is disabled heating or cooling mode with a setpoint change greater than 2 Se...

Страница 11: ...minutes at 80 then 100 Non VS Blower On Delay Comp Htg No Delay 15 Seconds 30 Seconds Select the blower on delay for compressor heating operation VS Blower Off Delay Comp Htg No Delay 1 5 Minutes 100...

Страница 12: ...frost above this temperature Compressor Cooling 1st Stage Lockout Disable Enable Enable compressor cooling 1st stage lockout Compressor Cooling 1st Stage Lockout Setting 80 F 120 F Select an outdoor t...

Страница 13: ...0 475 Two Stage Heat Pump 3 Stage Gas Oil Heat 6 3 Load Value Cooling 0 100 Single Stage Compressor 0 200 Two Stage Compressor A Load Value of 50 represents a request of 50 demand for single stage co...

Страница 14: ...STAGE 3 AUX WET HEAT STAGING THRESHOLDS 100 125 100 125 200 215 200 215 Compressor to W1 Compressor to W1 W1 to W2 W1 to W2 6 7 Stage Inhibits When the stage threshold is exceeded a stage inhibit is...

Страница 15: ...only limit Daytime operation only limit Nighttime or limit Daytime and Nighttime to different demands Night mode affects operation from 10 PM until 9 AM at which point Day settings for Quiet Mode take...

Страница 16: ...hen indoor humidity exceeds the desired cooling RH This feature can be enabled in the Installer Settings Comfort Settings Smart Continuous Fan settings 7 3 Dehumidifier Operation The 850 has the abili...

Страница 17: ...outs The 850 has the following lockouts AN OUTDOOR TEMPERATURE SENSOR MUST BE ENABLED FOR LOCKOUT SETTINGS TO BE AVAILABLE Lockouts can be enabled in Installer Setup Lockout Settings Auxiliary Heat Lo...

Страница 18: ...ASHRAE 62 2 standards A temperature override can be set to prevent ventilation operation when the outdoor temperature exceeds the minimum or maximum outdoor temperature selections If outdoor temperat...

Страница 19: ...ated indoor blower speed to set verify sytem charge Use sub cooling tables in the outdoor unit Service Facts to determine correct charge levels Outdoor temperature must be within 55F to 120F and indoo...

Страница 20: ...Normal alerts are only displayed in the Diagnostic screen Diagnostics can be accessed by navigating to Service Menu Diagnostics 8 3 2 Summary Table The 850 Control has a Summary Table which lists all...

Страница 21: ...eens Operating State Stage Requested Capacity Delivered Compressor Speed Load Value Fan Mode Air Flow Indoor Outdoor Temperatures Heating Cooling Set Points Indoor RH Heating Cooling RH Set Points 8 6...

Страница 22: ...ating or Cooling is displayed but no warm or cool air is coming from the registers 1 There is a fan delay as the heating or cooling equipment turns on 2 Equipment is not working properly 1 Wait a minu...

Страница 23: ...cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the...

Страница 24: ...D1 9 EN The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Representative only illustrations...

Отзывы: