American Standard AccuLink Platinum 850 Скачать руководство пользователя страница 18

Installation Guide

18  

11-HD14D1-9-EN

7.6  Humidifier Operation

The 850 has the ability to control a humidifier. Humidification 
is only enabled while in heating mode of operation. Control 
options are:

• 

RH Control – When the indoor humidity is less than 
the heating target relative humidity, a request for 
humidification is sent to the indoor unit.

• 

Frost Control – The 850 Control references the 
outdoor temperature and structure integrity to offset 
the heating target relative humidity. This helps to 
limit the risk of frost or condensation from forming 
on interior walls and windows. A scale of 1 to 10 is 
provided based on the insulation properties and 
expected leakage of the home (1=Leaky with poor 
insulation, 10=Very Tight with good insulation). An 
outdoor temperature sensor must be connected and 
enabled for frost control to be available.

Frost Control Structure Integrity Scale

Leaky, Poor Insulation

Average

Good Insulation, Tight

1

2

3

4

5

6

7

8

9

10

The 850 Control can be setup to allow humidification 
anytime in heating mode or only when actively heating. 
The airflow during Humidifier-only is factory set to 100% 
but can be adjusted between 35%-100% (this requires a 
variable speed indoor blower). All humidifier control options 
are located in the Installer Setup>Accessories Settings.

7.7  recovery

The 850 control utilizes a Stage Inhibit to limit equipment 
staging. This inhibit can be defeated in the following two 
manners. See “6.7 Stage Inhibits” on page 14 for more 
information.

7.7.1 Aggressive recovery

Greater than 2

°

Setpoint Change

Disables stage inhibits in heating and cooling mode anytime 
the setpoint is adjusted more than 2°F

7.7.2 Heating Aggressive recovery

By Outdoor Temperature

Disable stage inhibit in heating mode only when the outdoor 
temperature falls below the selected outdoor temperature.
Note: If Aggressive Recovery is enabled, Heating 
Aggressive Recovery is disabled.

7.8  Ventilation Operation

The 850 has the ability to control a Ventilation system 
through the normally open dry AUX Contacts on the 
optional Relay Panel. The blower is not interlocked on a 
call for ventilation. The ventilation run time per hour can be 
adjusted to meet ASHRAE 62.2 standards. A temperature 
override can be set to prevent ventilation operation when 
the outdoor temperature exceeds the minimum or maximum 
outdoor temperature selections. If outdoor temperature 
overrides are enabled the user can select to accumulate 
the missed ventilation run time. Options are below:

• 

Accumulate missed ventilation run time in 4 
hour increments and make up when the outdoor 
temperature is within the min/max settings.

• 

Accumulate missed ventilation run time in 24 
hour increments and make up when the outdoor 
temperature is within the min/max settings

• 

Accumulate missed ventilation run time in 4 hour 
increments and make up at the end of 4 hour period.

• 

Accumulate missed ventilation run time in 24 hour 
increments and make up at the end of 24 hour period.

All Ventilation control options are located in the 
Installer Setup>Accessories Settings.

7.9  Warm Air Discharge

Enabling Warm Air Discharge will reduce the variable 
speed blower air flow by 20% when in compressor 
heating operation. Warm Air Discharge only applies to 
compressor heating and is disabled when hydronic, fossil 
fuel or electric heat (including supplemental heat) modes 
are activated. Warm Air Discharge can be enabled in 
Installer Setup>Comfort Settings.

7.10  Wet Heat (Hydronic) Operation

A hot water coil can be applied to either a variable speed 
or non-variable speed indoor unit. The hot water coil can 
be the sole source of heat or used as auxiliary heat when 
applied with a heat pump. When applied with a heat pump, 
wet heat is considered auxiliary heat and will operate in-
conjunction with heat pump heat. Switching the system 
mode to emergency heat would disable the heat pump and 
cycle the wet heat only. 
If applied with a variable speed air handler, the blower 
speed during wet heat only heating will vary based on the 
system load value. The airflow will range from 35% to 100% 
depending on the system load value. When applied with a 
heat pump, the blower speed during heat pump and wet 
heat operation will be the higher of the two air flows. There 
are separate blower “On” and “Off” delays for wet heat in 
the 850 Control. 
The 850 Control is designed to operate forced air systems 
and should not be applied to non-forced air systems (radiant 
floors, radiators, etc…)
The hydronic heat blower delay options can be accessed 
by navigating to Installer > Setup > Airflow Settings.

Содержание AccuLink Platinum 850

Страница 1: ...property and is to remain with this unit These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation Should furthe...

Страница 2: ...3 1 Overview 3 3 2 Contents 3 3 3 Accessories 3 4 Installation 4 4 1 Location 4 4 2 Network Connections 4 4 3 Mounting 4 4 4 Wiring 5 4 5 Field Wiring Connection Diagrams 6 5 System Setup 7 5 1 Power...

Страница 3: ...e 0 to 100 1 resolution Minimum Cycle Off Time Delay Compressor 5 minutes Indoor Heat 1 minute On every application 24VAC loads should be reviewed to be sure the indoor unit control power transformer...

Страница 4: ...e Control s communication i e wireless phones security systems wireless Internet cameras Do not mount the Control in recessed areas near metal objects or near structures i e doors appliances entertain...

Страница 5: ...s extend through the hole in the Sub base see Figure 4 on page 5 4 4 Wiring 1 Adjust the length and position of each wire to reach the proper terminal on the connector block of the Sub base Strip 1 4...

Страница 6: ...r Optional Remote Sensor Communicating Indoor w Non Communicating Outdoor COMMUNICATING INDOOR UNIT excluding TAM8 24V SINGLE STAGE COOLING OUTDOOR 850 COMFORT CONTROL Caution Do not run Outdoor Remot...

Страница 7: ...the navigational steps and screen prompts installer s are guided through the Time and Date Installer Setup see 5 4 Installer Setup Screens on page 8 for detailed descriptions of each of the Installer...

Страница 8: ...ment Settings MENU ITEM OPTIONS DEFAULT DESCRIPTION Compressor Cooling Cycles Per Hour 2 6 Cph 3 Select of cycles per hour during cooling operation 1st Stage Compressor Cooling Cycles Per Hour 2 6 Cph...

Страница 9: ...elect whether the indoor blower operates on a call for ventilation Ventilation Minimum Outdoor Temperature 10 F 50 F 0 Select the minimum outdoor temperature that ventilation is allowed Ventilation Ma...

Страница 10: ...or additional information Aggressive Recovery 2 Setpoint Change Enable Disable Select whether the 10 minute staging inhibit is disabled heating or cooling mode with a setpoint change greater than 2 Se...

Страница 11: ...minutes at 80 then 100 Non VS Blower On Delay Comp Htg No Delay 15 Seconds 30 Seconds Select the blower on delay for compressor heating operation VS Blower Off Delay Comp Htg No Delay 1 5 Minutes 100...

Страница 12: ...frost above this temperature Compressor Cooling 1st Stage Lockout Disable Enable Enable compressor cooling 1st stage lockout Compressor Cooling 1st Stage Lockout Setting 80 F 120 F Select an outdoor t...

Страница 13: ...0 475 Two Stage Heat Pump 3 Stage Gas Oil Heat 6 3 Load Value Cooling 0 100 Single Stage Compressor 0 200 Two Stage Compressor A Load Value of 50 represents a request of 50 demand for single stage co...

Страница 14: ...STAGE 3 AUX WET HEAT STAGING THRESHOLDS 100 125 100 125 200 215 200 215 Compressor to W1 Compressor to W1 W1 to W2 W1 to W2 6 7 Stage Inhibits When the stage threshold is exceeded a stage inhibit is...

Страница 15: ...only limit Daytime operation only limit Nighttime or limit Daytime and Nighttime to different demands Night mode affects operation from 10 PM until 9 AM at which point Day settings for Quiet Mode take...

Страница 16: ...hen indoor humidity exceeds the desired cooling RH This feature can be enabled in the Installer Settings Comfort Settings Smart Continuous Fan settings 7 3 Dehumidifier Operation The 850 has the abili...

Страница 17: ...outs The 850 has the following lockouts AN OUTDOOR TEMPERATURE SENSOR MUST BE ENABLED FOR LOCKOUT SETTINGS TO BE AVAILABLE Lockouts can be enabled in Installer Setup Lockout Settings Auxiliary Heat Lo...

Страница 18: ...ASHRAE 62 2 standards A temperature override can be set to prevent ventilation operation when the outdoor temperature exceeds the minimum or maximum outdoor temperature selections If outdoor temperat...

Страница 19: ...ated indoor blower speed to set verify sytem charge Use sub cooling tables in the outdoor unit Service Facts to determine correct charge levels Outdoor temperature must be within 55F to 120F and indoo...

Страница 20: ...Normal alerts are only displayed in the Diagnostic screen Diagnostics can be accessed by navigating to Service Menu Diagnostics 8 3 2 Summary Table The 850 Control has a Summary Table which lists all...

Страница 21: ...eens Operating State Stage Requested Capacity Delivered Compressor Speed Load Value Fan Mode Air Flow Indoor Outdoor Temperatures Heating Cooling Set Points Indoor RH Heating Cooling RH Set Points 8 6...

Страница 22: ...ating or Cooling is displayed but no warm or cool air is coming from the registers 1 There is a fan delay as the heating or cooling equipment turns on 2 Equipment is not working properly 1 Wait a minu...

Страница 23: ...cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the...

Страница 24: ...D1 9 EN The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Representative only illustrations...

Отзывы: