6.6  Stage Thresholds

The threshold to allow operation is a Load Value greater 
than 5 and operation is always terminated with a Load 
Value less than 1. 
Load Value also determines when additional stages of 
operation are requested. To prevent rapid cycling between 
stages, a stage threshold is enforced. The stage threshold 
is dependent on the applied system.

LV=100

LV=200

STAGE 2

COMPRESSOR STAGING THRESHOLDS

100-115

100-115

100-125

100-125

100-110

100-110

Y1  to Y2 

Y1  to Y2 

HP to W1

HP to W1

HP to Dual Fuel

HP to Dual Fuel

ST

A

GE 3

ST

A

GE 1

LV=100

LV=200

LV=300

LV=400

ST

A

GE 5

ST

A

GE 1

STAGE 2

STAGE 3

STAGE 4

AUX ELECTRIC HEAT - STAGING THRESHOLDS

100-

115

100-

115

200-

215

200-

215

300-

315

300-

315

W1 to W2

W1 to W2

W2 to W3

W2 to W3

Compressor to W1

Compressor to W1

LV=100

LV=200

LV=300

ST

A

GE 4

ST

A

GE 1

STAGE 2

STAGE 3

AUX FOSSIL HEAT - STAGING THRESHOLDS

100-

125

100-

125

175-

190

175-

190

175-

190

175-

190

Inhibit - Compressor to W1

Inhibit - Compressor to W1

W1 to W2

W1 to W2

W2 to W3

W2 to W3

LV=100

LV=200

LV=300

ST

A

GE 4

ST

A

GE 1

STAGE 2

STAGE 3

AUX WET HEAT - STAGING THRESHOLDS

100-

125

100-

125

200-

215

200-

215

Compressor to W1

Compressor to W1

W1 to W2

W1 to W2

6.7  Stage Inhibits

When the stage threshold is exceeded, a stage inhibit is 
applied. The stage inhibit calculates the rate of recovery 
over a 10-minute period and determines if the next stage is 
required to meet the current demand. If the rate of recovery 
is great enough, a new 10-minute inhibit is enabled. The 
Control will not go to the next stage of operation until it 
determines that the current stage cannot satisfy the current 
demand. Stage inhibits only apply between compressor 
stages and compressor heat to indoor heat. Stage inhibits 
do not apply to indoor heat stages. 
Stage inhibits can be disabled in the 850 Control 
Installer Setup>Comfort Settings.

START INHIBIT

10 Minutes

Y1 “ON”

Y2 “ON”

Y1 “ON”

LV = 100

LOAD VALUE (LV)

LV = 110

Stage Inhibits - Compressor Staging

Stage Inhibits - Compressor to Aux Heat

START INHIBIT

10 Minutes

Y1 “ON”

W1 “ON”

W1 “OFF”

LV = 100

LOAD VALUE (LV)

LV = 115

START INHIBIT

10 Minutes

Y1 “ON”

W1 “ON”

Y1 “ON”

45 Second

Cool Down

LV = 100

LOAD VALUE (LV)

LV = 125

Stage Inhibits - Duel Fuel

Note: Stage Thresholds do not apply to Variable Speed 
Outdoor Unit operation.

Note: Stage Inhibits do not apply to Variable Speed 
Outdoor Unit operation.

Содержание AccuLink Platinum 850

Страница 1: ...property and is to remain with this unit These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation Should furthe...

Страница 2: ...3 1 Overview 3 3 2 Contents 3 3 3 Accessories 3 4 Installation 4 4 1 Location 4 4 2 Network Connections 4 4 3 Mounting 4 4 4 Wiring 5 4 5 Field Wiring Connection Diagrams 6 5 System Setup 7 5 1 Power...

Страница 3: ...e 0 to 100 1 resolution Minimum Cycle Off Time Delay Compressor 5 minutes Indoor Heat 1 minute On every application 24VAC loads should be reviewed to be sure the indoor unit control power transformer...

Страница 4: ...e Control s communication i e wireless phones security systems wireless Internet cameras Do not mount the Control in recessed areas near metal objects or near structures i e doors appliances entertain...

Страница 5: ...s extend through the hole in the Sub base see Figure 4 on page 5 4 4 Wiring 1 Adjust the length and position of each wire to reach the proper terminal on the connector block of the Sub base Strip 1 4...

Страница 6: ...r Optional Remote Sensor Communicating Indoor w Non Communicating Outdoor COMMUNICATING INDOOR UNIT excluding TAM8 24V SINGLE STAGE COOLING OUTDOOR 850 COMFORT CONTROL Caution Do not run Outdoor Remot...

Страница 7: ...the navigational steps and screen prompts installer s are guided through the Time and Date Installer Setup see 5 4 Installer Setup Screens on page 8 for detailed descriptions of each of the Installer...

Страница 8: ...ment Settings MENU ITEM OPTIONS DEFAULT DESCRIPTION Compressor Cooling Cycles Per Hour 2 6 Cph 3 Select of cycles per hour during cooling operation 1st Stage Compressor Cooling Cycles Per Hour 2 6 Cph...

Страница 9: ...elect whether the indoor blower operates on a call for ventilation Ventilation Minimum Outdoor Temperature 10 F 50 F 0 Select the minimum outdoor temperature that ventilation is allowed Ventilation Ma...

Страница 10: ...or additional information Aggressive Recovery 2 Setpoint Change Enable Disable Select whether the 10 minute staging inhibit is disabled heating or cooling mode with a setpoint change greater than 2 Se...

Страница 11: ...minutes at 80 then 100 Non VS Blower On Delay Comp Htg No Delay 15 Seconds 30 Seconds Select the blower on delay for compressor heating operation VS Blower Off Delay Comp Htg No Delay 1 5 Minutes 100...

Страница 12: ...frost above this temperature Compressor Cooling 1st Stage Lockout Disable Enable Enable compressor cooling 1st stage lockout Compressor Cooling 1st Stage Lockout Setting 80 F 120 F Select an outdoor t...

Страница 13: ...0 475 Two Stage Heat Pump 3 Stage Gas Oil Heat 6 3 Load Value Cooling 0 100 Single Stage Compressor 0 200 Two Stage Compressor A Load Value of 50 represents a request of 50 demand for single stage co...

Страница 14: ...STAGE 3 AUX WET HEAT STAGING THRESHOLDS 100 125 100 125 200 215 200 215 Compressor to W1 Compressor to W1 W1 to W2 W1 to W2 6 7 Stage Inhibits When the stage threshold is exceeded a stage inhibit is...

Страница 15: ...only limit Daytime operation only limit Nighttime or limit Daytime and Nighttime to different demands Night mode affects operation from 10 PM until 9 AM at which point Day settings for Quiet Mode take...

Страница 16: ...hen indoor humidity exceeds the desired cooling RH This feature can be enabled in the Installer Settings Comfort Settings Smart Continuous Fan settings 7 3 Dehumidifier Operation The 850 has the abili...

Страница 17: ...outs The 850 has the following lockouts AN OUTDOOR TEMPERATURE SENSOR MUST BE ENABLED FOR LOCKOUT SETTINGS TO BE AVAILABLE Lockouts can be enabled in Installer Setup Lockout Settings Auxiliary Heat Lo...

Страница 18: ...ASHRAE 62 2 standards A temperature override can be set to prevent ventilation operation when the outdoor temperature exceeds the minimum or maximum outdoor temperature selections If outdoor temperat...

Страница 19: ...ated indoor blower speed to set verify sytem charge Use sub cooling tables in the outdoor unit Service Facts to determine correct charge levels Outdoor temperature must be within 55F to 120F and indoo...

Страница 20: ...Normal alerts are only displayed in the Diagnostic screen Diagnostics can be accessed by navigating to Service Menu Diagnostics 8 3 2 Summary Table The 850 Control has a Summary Table which lists all...

Страница 21: ...eens Operating State Stage Requested Capacity Delivered Compressor Speed Load Value Fan Mode Air Flow Indoor Outdoor Temperatures Heating Cooling Set Points Indoor RH Heating Cooling RH Set Points 8 6...

Страница 22: ...ating or Cooling is displayed but no warm or cool air is coming from the registers 1 There is a fan delay as the heating or cooling equipment turns on 2 Equipment is not working properly 1 Wait a minu...

Страница 23: ...cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the...

Страница 24: ...D1 9 EN The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Representative only illustrations...

Отзывы: