American Standard AccuLink Platinum 850 Скачать руководство пользователя страница 8

Installation Guide

8  

11-HD14D1-9-EN

INSTALLATION WIZ-
ARD MENU ITEMS

DESCRIPTION

Date and Time

Set the current date, time and select whether Daylight Savings Time is on or off.

Installer Setup

Configure the basic equipment components installed and customize how the control operates. See Sections 5.4.1 
through 5.4.7 for detailed information on installer setup options.

Service Reminders

Various service reminders can be enabled on the 850 control based on the system configured. Reminder options 
are System, Filter, Ventilation, UV Light and Humidifier. The frequency of each reminder can be selected based on 
calendar or run time days.

Dealer Identification Code

The dealer identification code is used to populate the Dealer Contact Information and associate this device with a 
Nexia Dealer Portal account. Enter the primary phone number of the dealership to activate this feature. Only controls 
connected to the Internet will auto-populate the dealer information.

5.4  Installer Setup Screens

From the Installer Setup screens, individual parameters are configured and modified. Use the up and down arrows to scroll 
through the groups of settings. To change a setting contained in a particular group, press Edit and press Next to navigate to 
the desired setting. Press Save to save changes or Exit to discard changes.

5.4.1 Group 1 Standard Settings

MENU ITEM

OPTIONS [DEFAULT]

DESCRIPTION

Outdoor Unit Type

None, Cooling Only, Heat Pump

Select the type of outdoor unit installed

Outdoor Unit Stages

Single Stage, Two Stage, Variable

Select the number of outdoor unit stages

Compressor Type

Single Compressor Two Stage, Two Compressor 
Two Stage

Select the compressor type for multi-stage outdoor units

Indoor Unit Type

Gas/Oil, Electric, Hydronic

Select the type of indoor unit installed

Indoor Heat Stages

1, 2, 3, Modulating

Select the number of indoor heat stages

Indoor Blower Type

Non-Variable, Variable

Select the indoor blower type (Constant Torque motors are 
considered non-variable speed)

5.4.2 Group 2 equipment Settings

MENU ITEM

OPTIONS [DEFAULT] DESCRIPTION

Compressor Cooling Cycles Per Hour

2 - 6 Cph [3]

Select # of cycles per hour during cooling operation

1st Stage Compressor Cooling Cycles Per Hour

2 - 6 Cph [3]

Select # of cycles per hour during 1st stage cooling operation

2nd Stage Compressor Cooling Cycles Per Hour

2 - 6 Cph [3]

Select # of cycles per hour during 2nd stage cooling operation

Compressor Heating Cycles Per Hour

2 - 6 Cph [3]

Select the minimum runtime (MRT) of stage 1 indoor heat

1st Stage Compressor Heating Cycles Per Hour

2 - 6 Cph [3]

Select the minimum runtime (MRT) of stage 2 indoor heat

2nd Stage Compressor heating Cycles Per Hour

2 - 6 Cph [5]

Select the minimum off time (MOT) for indoor heat operation

Indoor Heater Cycles Per Hour

2 - 6 Cph [5]

Select # of cycles per hour during indoor heat operation

1st Stage Indoor Heat Cycles Per Hour

2 - 6 Cph [5]

Select # of cycles per hour during 1st stage indoor heat operation

2nd Stage Indoor Heat Cycles Per Hour

2 - 6 Cph [5]

Select # of cycles per hour during 2nd stage indoor heat operation

3rd Stage Indoor Heat Cycles Per Hour

2 - 6 Cph [5]

Select # of cycles per hour during 3rd stage indoor heat operation

5.3  Smart Optimization

The 850 Control is equipped with Smart Optimization. By 
executing a series of blower tests, Smart Optimization will 
customize the 850 Control to each unique environment and 
increase the accuracy of the sensed indoor temperature 
and overall system performance.
Smart Optimization is enabled by default and will 
automatically execute approximately 18 hours after initial 
power up. Smart Optimization takes 90 minutes to complete 
and during the process, heating and cooling operations are 
disabled. The screen will indicate that the 850 Control is in 

Smart Optimization mode.
To delay Smart Optimization for an additional 18 hours, 
touch the 850 Control Screen and hold for five seconds.
To disable Smart Optimization altogether, navigate to 
Home>Smart Optimization and select Disable and press 
Apply.
To enable Smart Optimization, navigate to Home>Smart 
Optimization and select Enable and press Apply. Smart 
Optimization will execute in approximately 18 hours.
To manually trigger Smart Optimization, first disable, then 
re-enable the feature.

Содержание AccuLink Platinum 850

Страница 1: ...property and is to remain with this unit These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation Should furthe...

Страница 2: ...3 1 Overview 3 3 2 Contents 3 3 3 Accessories 3 4 Installation 4 4 1 Location 4 4 2 Network Connections 4 4 3 Mounting 4 4 4 Wiring 5 4 5 Field Wiring Connection Diagrams 6 5 System Setup 7 5 1 Power...

Страница 3: ...e 0 to 100 1 resolution Minimum Cycle Off Time Delay Compressor 5 minutes Indoor Heat 1 minute On every application 24VAC loads should be reviewed to be sure the indoor unit control power transformer...

Страница 4: ...e Control s communication i e wireless phones security systems wireless Internet cameras Do not mount the Control in recessed areas near metal objects or near structures i e doors appliances entertain...

Страница 5: ...s extend through the hole in the Sub base see Figure 4 on page 5 4 4 Wiring 1 Adjust the length and position of each wire to reach the proper terminal on the connector block of the Sub base Strip 1 4...

Страница 6: ...r Optional Remote Sensor Communicating Indoor w Non Communicating Outdoor COMMUNICATING INDOOR UNIT excluding TAM8 24V SINGLE STAGE COOLING OUTDOOR 850 COMFORT CONTROL Caution Do not run Outdoor Remot...

Страница 7: ...the navigational steps and screen prompts installer s are guided through the Time and Date Installer Setup see 5 4 Installer Setup Screens on page 8 for detailed descriptions of each of the Installer...

Страница 8: ...ment Settings MENU ITEM OPTIONS DEFAULT DESCRIPTION Compressor Cooling Cycles Per Hour 2 6 Cph 3 Select of cycles per hour during cooling operation 1st Stage Compressor Cooling Cycles Per Hour 2 6 Cph...

Страница 9: ...elect whether the indoor blower operates on a call for ventilation Ventilation Minimum Outdoor Temperature 10 F 50 F 0 Select the minimum outdoor temperature that ventilation is allowed Ventilation Ma...

Страница 10: ...or additional information Aggressive Recovery 2 Setpoint Change Enable Disable Select whether the 10 minute staging inhibit is disabled heating or cooling mode with a setpoint change greater than 2 Se...

Страница 11: ...minutes at 80 then 100 Non VS Blower On Delay Comp Htg No Delay 15 Seconds 30 Seconds Select the blower on delay for compressor heating operation VS Blower Off Delay Comp Htg No Delay 1 5 Minutes 100...

Страница 12: ...frost above this temperature Compressor Cooling 1st Stage Lockout Disable Enable Enable compressor cooling 1st stage lockout Compressor Cooling 1st Stage Lockout Setting 80 F 120 F Select an outdoor t...

Страница 13: ...0 475 Two Stage Heat Pump 3 Stage Gas Oil Heat 6 3 Load Value Cooling 0 100 Single Stage Compressor 0 200 Two Stage Compressor A Load Value of 50 represents a request of 50 demand for single stage co...

Страница 14: ...STAGE 3 AUX WET HEAT STAGING THRESHOLDS 100 125 100 125 200 215 200 215 Compressor to W1 Compressor to W1 W1 to W2 W1 to W2 6 7 Stage Inhibits When the stage threshold is exceeded a stage inhibit is...

Страница 15: ...only limit Daytime operation only limit Nighttime or limit Daytime and Nighttime to different demands Night mode affects operation from 10 PM until 9 AM at which point Day settings for Quiet Mode take...

Страница 16: ...hen indoor humidity exceeds the desired cooling RH This feature can be enabled in the Installer Settings Comfort Settings Smart Continuous Fan settings 7 3 Dehumidifier Operation The 850 has the abili...

Страница 17: ...outs The 850 has the following lockouts AN OUTDOOR TEMPERATURE SENSOR MUST BE ENABLED FOR LOCKOUT SETTINGS TO BE AVAILABLE Lockouts can be enabled in Installer Setup Lockout Settings Auxiliary Heat Lo...

Страница 18: ...ASHRAE 62 2 standards A temperature override can be set to prevent ventilation operation when the outdoor temperature exceeds the minimum or maximum outdoor temperature selections If outdoor temperat...

Страница 19: ...ated indoor blower speed to set verify sytem charge Use sub cooling tables in the outdoor unit Service Facts to determine correct charge levels Outdoor temperature must be within 55F to 120F and indoo...

Страница 20: ...Normal alerts are only displayed in the Diagnostic screen Diagnostics can be accessed by navigating to Service Menu Diagnostics 8 3 2 Summary Table The 850 Control has a Summary Table which lists all...

Страница 21: ...eens Operating State Stage Requested Capacity Delivered Compressor Speed Load Value Fan Mode Air Flow Indoor Outdoor Temperatures Heating Cooling Set Points Indoor RH Heating Cooling RH Set Points 8 6...

Страница 22: ...ating or Cooling is displayed but no warm or cool air is coming from the registers 1 There is a fan delay as the heating or cooling equipment turns on 2 Equipment is not working properly 1 Wait a minu...

Страница 23: ...cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the...

Страница 24: ...D1 9 EN The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Representative only illustrations...

Отзывы: