Page 28
CLEARANCE REQUIREMENTS
ADJACENT MATERIAL COMPOSITION
NON-COMBUSTIBLE
COMBUSTIBLE
SIDE :
2 inches
50 mm
2 inches
50 mm
TOP
:
2 inches
50 mm
6 inches
300 mm
FLOOR :
12 inches
300 mm
12 inches
300 mm
FRONT :
24 inches
600 mm
24 inches
600 mm
BACK :
zero
zero
1 inch (25 mm) fireproof
Insulating panel required
MOUNTING
The heater MUST be installed in a vertical position with fuel gas inlet at
the bottom and exhaust vent positioned at the top. Installation in any
other orientation will result in damage and will void warranty.
1.
Identify a suitable location per the “Location and Clearance Guidelines”. Ensure that the
heater will be attached in a manner that is sufficient to support the weight of the heater in
operation.
2.
The system should only be mounted on a fire rated wall or piece of fire rated board that is
mounted with spacers 1/3in (10mm) off the wall and protrudes at least 4in (100mm)
beyond the sides of the water heater will have to be mounted. (Check with local codes)
3.
Measure and mark the center locations for three (3) holes according to the installation
measurements below.
23
.9
4"
(6
08
)
23
.3
1"
(5
92
)
3.94"(100)
0.31"(φ8)
2.36"(60)
0.47"(φ12)