background image

Final Installation & Adjustment

Before Connecting Main Airline from Compressor to Control Box.

Clear main airline from compressor from contamination and debris by slowly opening up valve at 
compressor and purging line.

If new installation, the main airline  may have slag or other 

contaminant’s which could cause damage to the valve and other internal components.

Before 

hooking up the main airline to the shut-off valve.

Turn off the

shut-off valve by turning the valve 

lever to 90

0

 

to the valve or Off.

Caution:

If the Shut-off valve is in the open position,

the door will start upward when you

 

apply air pressure to the operator system

.

Step 1

:HUHFRPPHQGUXQQLQJKDUGSLSHDLUOLQHVRXWWR\RXUFRQWUROER[DVVKRZQLQWKHGUDZLQJRQ

 

SDJH;;RU\RXFDQ

Install  3/8”

polyflow airline from your air compressor to the push-in fitting on the  

shut-off valve 

Other line sizes may be used.

Step 2

Back off the filter regulator by pulling up on the adjustment knob on top of regulator and turn counter

 

clockwise until it stops.

 

Open shut-off valve (inline with valve) Turn the regulator 

adjustment knob 

FORFNZLVH

 slowly until it reaches approximately 60-PSI (Recommended air 

pressure

between 45-PSI and 70 PSI).

Step 3

Plug in 110 volt power cord located on the bottom of the control box into receptacle or hardwire.

 

This should be connected to a grounded receptacle only!!!

Step 4

Adjust flow controls by starting with flow controls completely closed (Clockwise) with the locknut

 

loose.

Open each flow control valve approximately 5 complete turns (Counterclockwise).

Cycle the

 

door by pushing the open and close buttons located on the control box.

While cycling the door open

 

and closed continue to turn the flow control valves until the door opens and closes smoothly at the

 

top and bottom of each cycle.

It is recommended to keep both flow controls set equally.

For additional tuning, adjust flow controls and air pressure at the regulator until door operates to

 

your desired speed and smoothness.

Note

:

Each flow control valve will control the speed of it’s direction.

Tighten lock nut located on flow

 

control when adjusted completely.

For complete explanation of how the flow control works, see next page.

Step 5

Inspect entire operator cylinder assembly, chain, sprocket assembly and piston rods for proper align-
ment, adjust as needed.

12

Содержание Supralift II

Страница 1: ...Air Powered Operator Installation Manual 1 1 2020 American Garage Door Supply Inc 1 800 233 1487 1...

Страница 2: ...tem Installation should be performed by a trained professional 3 Follow equipment manufacturer s recommendations on tools ladders and other equipment used for installation 4 Any air powered opener mus...

Страница 3: ...ch pushes the piston rod assembly down The drive chain is attached to the top of each piston rod and loops over the sprocket on the doors torsion shaft On the open signal compressed air drives the ope...

Страница 4: ...Sample Installation Pictures Top of Cylinder View Top Assembly View Chain Sprocket View Bottom of Cylinder View Flow Control View Control Box View 4...

Страница 5: ...41 x 12 Tooth SS Sprocket 1 4 x 2 SS Key 900 3 8 x 1 4 NPT Push in Fitting Flow Control Kit 2 ea 1 ea 1 ea 4 ea 1 ea HARDWARE PACKAGE Part Number TBLTS1458 NUTFS14 SLAC SLSC12 SLJNUT SLSTBS CN41 CMLWP...

Страница 6: ...Components Identification Aluminum Collar with Set Screw Aluminum Collar Lock Nut Chain Master Links Sprocket with Set Screws 1 4 Key Push in Fitting Turnbuckle Track Bolt Nut Cylinders 6...

Страница 7: ...set screws at this time Slide sprocket near end bearing plate of the door Figure 2 Step 6 With the door closed hang the operator by the chain assembly over the sprocket onto the torsion shaft Keep th...

Страница 8: ...e piston rod on the cylinder closest to the wall close cylinder all the way down until the piston bottoms out in the cylinder then raise the piston rod 1 1 1 2 upward and tighten the set screw on the...

Страница 9: ...w Driver Phillips Screwdriver Hand Wrenches 1 4 7 16 1 2 9 16 5 8 3 8 Socket Set 7 16 1 2 9 16 5 8 Electric Impact or Drill with 3 8 and 7 16 Sockets 1 4 drill bit Small Pipe Wrench Wire Cutters Teflo...

Страница 10: ...Components Identification Control Box Flow Control 2 1 2 Nipple Porex Muffler 1HHGOH 9DOYH Filter Regulator Shut off Valve Assembly and Inline Dryer Optional 10...

Страница 11: ...viously installed push in fitting on the bottom of the cylinders to the push in fittings located on the top of the flow controls Plumb the line from cylinder nearest the jamb to the close and the line...

Страница 12: ...the regulator adjustment knob FORFNZLVH slowly until it reaches approximately 60 PSI Recommended air pressure between 45 PSI and 70 PSI Step 3 Plug in 110 volt power cord located on the bottom of the...

Страница 13: ...l slow the travel speed of the door The check ball in each valve allows each cylinder to breath freely as the piston is draw up mechanically by the chain on the reverse cycle Caution The Supralift ope...

Страница 14: ...62 PSI is common Heavier doors may need to have the pressure increased but if you must exceed 90 PSI you probably have a door problem Replacing the filter in the regulator is recommended every 6 mont...

Страница 15: ...g and Limits Opener to be equipped with a 1 x 12 tooth driven sprocket for the door shaft with 41 chain Limits to be set by mechanical means by adjustment of the pistons and aluminum collar Operator s...

Страница 16: ...10 high door under normal operating conditions will open and close 3 times a minute Stroke Lengths of Cylinder 8 Opener 47 1875 10 Opener 59 1875 12 Opener 71 1875 14 Opener 83 1875 16 Opener 95 1875...

Страница 17: ...17...

Страница 18: ...1 2 3 4 5 6 7 8 9 10 11 12 13 8 14 5 7 9 15 16 17 18 19 20 21 22 23 24 27 25 26 28 Supralift Parts Diagram 18...

Страница 19: ...p SS Track Bracket SS Bottom Plate Carriage Bolt 5 16 x 3 4 SS Flanged Hex Nut 5 16 18 SS Hex Head Bolt 5 16 x 5 8 SS Wear Sleeve Ring Piston Seals Seal Kit Supralift Piston Rod 8 Supralift Piston Rod...

Страница 20: ...Photo Eye Base Black White Black White Black Receiver White Black White Transmitter 20...

Страница 21: ...GGLQJ 6HFRQG 6HW RI 3KRWR HV ZLWK ORVH WLPHU 7KH QG VHW RI 3KRWR H HV ZLUHV GLUHFWO WR WKH 3LQ ORFN DV VKRZQ KHUH LULQJ WR QG 3 1 ORFN 5HG HOORZ 5HG HOORZ 21...

Страница 22: ...Control Box Wiring Diagram 1 800 233 1487 Old Style 22...

Страница 23: ...photo eye The Door should continue down and close If the door reverses check connections and repeat the process White Wire is Not Used Control Box Terminal Strip Wiring a Magnetic Contact Switch MCS T...

Страница 24: ...m Wiring Eyes Wire numbered terminals on contact block to appropriate numbers listed on Receiver Transmitter and Terminal Strip Once wired plug in amplifier to 11 pin socket located on contact block C...

Страница 25: ...ndard Control Box Macromatic Timer Wiring Diagram 1 2 3 4 5 6 7 8 9 1 0 1 1 1 8 Seconds Time ranges from 1 8 seconds to 180 seconds 30 60 90 120 150 180 Timer Toggle Switch OPTIONAL Wiring Diagram Wir...

Страница 26: ...timer to work Use 5 and 7 on the contact block for connection to your incoming signal This signal should be a continuous signal with the same voltage as the timer primary power For 120VAC one shot ti...

Страница 27: ...ote This wiring Diagram is set up for Supralift Magnelift Air Powered Operators only 1 800 233 1487 www carwashdoors com Banner Photoeye Sensors Emitter Blue 24V Brown Common Receiver Blue 24V Brown T...

Страница 28: ...t up for Supralift Magnelift Air Powered Operators only 2005 1 800 233 1487 www carwashdoors com Banner Photoeye Sensors Emitter Blue 110V From Transfomer Brown Common On 110V Transformer Receiver Blu...

Страница 29: ...er in lieu of all other warranties written oral or implied including any warranty of merchantability or fitness for purpose and all other obligations or liabilities on the part of the Company The Comp...

Отзывы: