56
American Dryer Corp.
113068 - 10
The water connection for the manual bypass is made to the “T” or “four way” fitting, which has a 1/2” F.P.T.
and a coupling
must be
used to provide the minimum 1/2-inch supply (feed) line.
If the rear area of the dryer, or the water supply is located in an area where it will be exposed to cold/freezing
temperatures, provisions
must be
made to protect these water lines from freezing.
WARNING:
If the water in the supply line or water solenoid valve freezes, the suppression system
will be
INOPERATIVE!!
The manual ball cock shutoff valve
must be
located outside of the dryer at a distance from the dryer where it
is easily accessible.
3. Electrical Requirements
No independent external power source or supply connection is necessary. The 24 volt power to operate the
suppression system is accomplished internally in the dryer (from the dryer controls).
WARNING:
ELECTRICAL POWER
MUST BE
PROVIDED TO THE DRYER AT
ALL
TIMES.
If the main electrical power supply to the dryer is disconnected, the suppression system
is INOPERATIVE!!
NOTE:
Suppression system water solenoid valve test can be performed by pressing the “STOP” key
and “A” key together.