background image

4211-195  05-22-12

Page 10

AI

 SERIES STEAM BOILER WITH T100  CONTROL

INSTALLATION INSTRUCTIONS

IMPORTANT

The steam line should be pitched away from the boiler so any condensate will drain from the steam line. For best results, the boiler should 

be installed as close to the steam room as possible, with its steam outlet valve higher than the steam heads in the steam room and the steam line run 
straight to the steam heads with a pitch of at least ¼” per foot (6.4 mm per 305 mm) to drain into the room. Do not allow sags, dips or other low sections 
in the steam line: these may block the steam fl ow or cause spitting of very hot water into the steam room. 

As with any steam bath steam boiler, spitting, reduced steam and other problems can occur if too many elbows or tees are placed in the steam line, if the 
line is too long, if the line has large rises or if there are low area or traps in the line. The effects depend on the number and size of these practices in a 
particular installation.

To reduce noise or improve the distribution of steam in larger rooms, additional steam heads may be 
installed. Two steam heads are supplied with each boiler. Space steam heads at 6” (150 mm) intervals, 
minimum. The steam heads should be located to ensure they do not discharge steam or drip condensate 
where the user may come in contact with the hot moisture – 

contact may cause injuries from scalding to 

severe burns

!

AT THE STEAM ROOM: Drill/prepare a 1

3

/

8

" (35 mm) hole at each steam head location for steam line entry 

15” to 18” (380 to 460 mm) above the 

fl

 oor. Terminate the steam line from the boiler with a tee at the steam 

room then plumb each side of the tee to a steam head location and through the wall. Center the 

3

/

4

” copper 

steam pipe in the 1

3

/

8

” (35 mm) hole. Terminate the steam line with a 

3

/

4

” NPT male adapter. Stub the line out 

into the room 

3

/

8

” (9.5 mm) from the 

fi

 nished surface. Secure the steam lines to structural members.

INSTALL STEAM HEAD INSULATOR(S): Fill in gaps using 100% Silicone caulk between steam pipe and 

fi

 nished wall surface at point of entry (

see drawing

). Apply silicone caulk to the 

fi

 nished wall side of the 

steam head insulator and screw on hand tight until 

fl

 ush with the wall with the opening pointing down. If a 

hand tight 

fi

 t does not align with the opening pointing down, use te

fl

 on tape on the steam line threads to 

adjust the 

fi

 t. Protect the steam head 

fi

 nish from damage while handling and tightening.

INSTALL STEAM HEAD: Slide the steam head on until it rests 

fi

 rmly against the 

fi

 nished wall. Tighten 

the hex head screw underneath the steam head to secure it in place with the Allen 
wrench provided. The steam head should be level with its fragrance reservoir at the top. 

IMPORTANT Check all of the standard fi xtures in the steam  room. All fi xture penetrations 

and steam head insulators must be sealed with 100% silicone caulk to avoid moisture dam-

age within walls.

When the steam line is in an area where the temperature will be below 40°F (4.4°C) or if 
the line is more than 20 feet (6 m) long, best results can be obtained by insulating the steam 
pipe. Any insulation must be suitable for temperatures of at least 250°F (120°C).

3. INSTALL SAFETY VALVE LINE All AI boilers are equipped with a factory installed 15 psi ( 1.1 bar) pressure relief safety valve. This must be plumbed 
to a ¾” indirect waste line. Do not install a shut off device in this line. Do not reduce this line. Do not form a trap in this line! Discharge from the safety 
valve may be at over 240°F (120°C). Do not plumb this line into the steam room! Plumb this waste line per local plumbing codes.

4. INSTALL DRAIN All AI boilers are equipped with a factory installed manual ball valve to allow draining the tank. An optional electronic drain may be 
installed after the manual valve. Plumb the drain to a ¾” indirect waste line. If the drain is opened while the boiler is under pressure, discharge
from the drain may be at over 240°F (120°C) and near 15 psi (1.1 bar). Do not plumb this line into
the steam room! Plumb this waste line per local plumbing codes. A (customer supplied) expansion
tank or blowdown cooling tank may be required by local code.

ELECTRICAL
Refer to the ID plate on the boiler’s switch panel to determine voltage and current requirements.

 

Electrical service for all models requires two (single phase) or three (3 phase) hot leads plus a suit-
able ground connection. Models operating on 208V, 240V, 415V or 480V also require a 14 AWG 
Neutral for the boiler controls circuit. Models operating on 480V require a separate 120V (14AWG)
service for the controls circuit. Route the copper supply wire with appropriate strain relief through the 
hole marked POWER ENTRIES. A multiple knockout is provided at this point for electrical service 
using up to 2” conduit. A second knockout, ½” to ¾”, is provided for the 120V controls circuit, if needed. 

CAUTION

Loose wire connections can cause heat damage to wires, terminal blocks and other 

components and may void the warranty.

12in (300mm) MIN

15 to 18in 

(380 to 460mm) 

from nearest

surface

6in (150mm) min

L1

L2

L3

3-Phase Power

120V (240V~)

NEUTRAL

120V (240V~)

NEUTRAL

L1

L2

L3

1-Phase Power

3/8" (9.5 mm)

from wall

Steam Head Face

Fragrance

Reservoir

1-3/8" (35 mm)
Diameter hole
[fill gap with silicone]

3/4" NPT

Fitting

Steam Head Insulator
[seal back surfaces with silicone]

Содержание AI12

Страница 1: ...4211 195 05 22 12 INSTALLATION INSTRUCTIONS FOR THE AI SERIES STEAM BOILER WITH T100 B TOUCH CONTROL MODELS AI12 AI18 AI24 and MODELS AI30 AI36 AI42 AI48 ...

Страница 2: ...TROLS 11 12 TEMPERATURE SENSOR 11 12 STARTING THE BOILER 12 13 OPERATING INSTRUCTIONS 13 15 BOILER START 14 STEAM ROOM OPERATION 14 LIGHTS AND SWITCHES 14 15 ROUTINE MAINTENANCE 15 16 WATER LEVEL CONTROL 15 BLOWDOWN AUTODRAIN 15 16 WIRING DIAGRAM AI12 AI24 208 240 480V 60Hz 17 WIRING DIAGRAM AI12 AI24 240 415V 50Hz 18 WIRING DIAGRAM AI30 AI48 208 240 480V 60Hz 19 WIRING DIAGRAM AI30 AI48 415V 50Hz...

Страница 3: ...y pregnant women should consult a physician regarding correct exposure e Obese persons and persons with a history of heart disease low or high blood pressure circulatory system problems or diabetes should consult a physician before using a steambath f Persons using medication should consult a physician before using a steambath since some medication may induce drowsiness while other medications may...

Страница 4: ... enclosures are properly sealed to avoid water damage from escaping steam It is recommended that 100 silicone caulk be used to seal all pipes and fittings Steam must be prevented from escaping into the wall cavity Avoid traps and valleys in the steam line where water could collect and cause a steam blockage The hot steam line must be insulated against acciden tal user contact Centering the steam p...

Страница 5: ...ntrols for these boilers including the T100 s interface box will operate on 120VAC 60Hz Boilers designed typical international voltages of 220 380V 230 400V or 240 415V operate at 240V N for single phase mains and 415V for three phase mains These boilers may be used safely at the common lower voltages All controls for these boilers including the T100 s interface box will operate on 230V N 50Hz The...

Страница 6: ...ng installation using a factory supplied cable An access hole and knockouts trade size are provided for room control wiring The T100 may be mounted inside or outside the steam room and its temperature sensor must be mounted inside the steam room Temperature sensors require factory supplied 25 foot 4 6 m long cables for connection to the T100 s adapter box and a 25 foot 4 6 m long shielded cable is...

Страница 7: ...000 208 3 84 1250 35 91 17 1 2 x 27 x 24 444 5 x 685 8 x 609 6 30 240 240 73 30 415 415 43 30 480 480 36 AI36 36 208 36 000 208 3 101 1500 43 109 36 240 240 88 415 51 36 480 480 43 AI42 42 208 42 000 208 3 118 1750 50 127 42 240 240 102 415 59 42 480 480 51 AI48 48 240 48 000 240 3 117 2000 57 145 415 68 48 480 480 58 Notes All models use 120VAC 60 Hz or 240V 50 Hz control circuits 208V 240V and 4...

Страница 8: ...n 444mm 18in 460mm Minimum Access 21in 533mm Minimum Access with optional LWCO installed 41in 1 04M without LWCO 61in 1 55M with LWCO 1in 25mm Minimum Clearance without LWCO ELECTRICAL ACCESS LWCO ACCESS 2 1 4in 57mm 5 1 2in 140mm 20in 508mm 25in 635mm 23 1 2in 597mm 6in 150mm Minimum Service Access Electric Power Low Voltage Control Wiring Run Timer optional Drain Timer optional 14 3 4in 375mm 22...

Страница 9: ...ure may be between 20 and 100 psi 1 4 to 7 bar Feedwater pressure should be limited to approximately 20 psi 1 4 bar for best performance A water hammer prevention device is factory installed on all steam boiler boilers Excessive water hammer can damage a water valve preventing it from shutting off the water supply to the boiler Special water treatment may be required in your area see AUTODRAIN sec...

Страница 10: ...crew underneath the steam head to secure it in place with the Allen wrench provided The steam head should be level with its fragrance reservoir at the top IMPORTANT Check all of the standard fixtures in the steam room All fixture penetrations and steam head insulators must be sealed with 100 silicone caulk to avoid moisture dam age within walls When the steam line is in an area where the temperatu...

Страница 11: ...er adapter provided which connects to a nearby 120VAC or 230V outlet Select a location which is convenient to the boiler power control and temperature sensor then mount the box on the wall This loca tion should be dry and keep the box safe from damage Remove the box s cover before mounting by gently pulling out on the sides of the box cover until it slides off Locate the two mounting holes inside ...

Страница 12: ...1 at the boiler 2 to 2 and 3 to 3 Use a cable strain relief provided to secure the cable to the interface box 5 INSTALL BYPASS The T100 connects to its own temperature sensor through the interface so the normal boiler tempera ture sensor is not connected Instead a sensor bypass supplied must be plugged into the TEMP SENS jack on the boiler s circuit board as shown at right Orient the bypass plug t...

Страница 13: ...he boiler is set to RUN On the boiler the room steam valve should be closed and the ROOM STATUS lights should be off At the Control touch the bottom of the T100 screen to light the display With the icon lit brightly on the display press the OK switch A small should light below the T100 display the interface board s two lights should be lit left light shows power is on right light indicates room sh...

Страница 14: ...not build up any pressure during this period When the boiler is started with an empty tank the steam outlet valve s will open to release air pressure created by adding water If not released this air pressure could be sensed by the pressure switch preventing heating When the water reaches the safe heating level the heat will turn on and if the steam bath is not turned on the steam valve s will clos...

Страница 15: ...urn off and the heat contactor will open This is the low water cut off level Set the BOILER OPERATION switch to off close the drain and reset all switches to their NORMAL position Reset the thermostat to its original position The boiler is now ready for normal oper ation again BOILER BLOWDOWN AUTODRAIN The boiler is supplied with a manual drain valve and may be equipped with an optional electronic...

Страница 16: ...The drain cycle will not operate again until power has been reset To manually drain the generator with an electronic Autodrain installed set the ELECTRONIC DRAIN switch to the MANUAL OPEN position When an electronic drain is installed make sure that the manual drain ball valve is always left in the open position Do not touch the safety valve when the boiler is hot the valve will be dangerously hot...

Страница 17: ...CUIT FUSE 3 AMP NON TIME DELAY BOILER OPERATION MANUAL RUN CLOCK RUN STEAM VALVE OPEN LIGHT MANUAL OPEN AUTODRAIN CLOCK OPTION M 3241 02x POWER LEVEL CONTROL PRINTED CIRCUIT BOARD H M L DRAIN RELAY DRAIN VALVE OPEN LIGHT ROOM STATUS LEDS DRN AUTODRAIN SOLENOID OPTION OFF ROOM2 LOCKOUT NORMAL STOP FILL ROOM1 LOCKOUT ROOM 2 RELAY ROOM 1 RELAY HEAT HEAT RELAY FEEDWATER RELAY R OFF STM STM STEAM VALVE...

Страница 18: ...T FUSE 3 AMP NON TIME DELAY BOILER OPERATION MANUAL RUN CLOCK RUN STEAM VALVE OPEN LIGHT MANUAL OPEN AUTODRAIN CLOCK OPTION M 3241 04x POWER LEVEL CONTROL PRINTED CIRCUIT BOARD H M L DRAIN RELAY DRAIN VALVE OPEN LIGHT ROOM STATUS LEDS DRN AUTODRAIN SOLENOID OPTION OFF ROOM2 LOCKOUT NORMAL STOP FILL ROOM1 LOCKOUT ROOM 2 RELAY ROOM 1 RELAY HEAT HEAT RELAY FEEDWATER RELAY R OFF STM STM STEAM VALVE OP...

Страница 19: ...WATER OFF NEUTRAL CONTROL CIRCUIT FUSE 3 AMP NON TIME DELAY BOILER OPERATION MANUAL RUN CLOCK RUN STEAM VALVE OPEN LIGHT MANUAL OPEN AUTODRAIN CLOCK OPTION M 3241 02x POWER LEVEL CONTROL PRINTED CIRCUIT BOARD H M L DRAIN RELAY DRAIN VALVE OPEN LIGHT ROOM STATUS LEDS DRN AUTODRAIN SOLENOID OPTION OFF ROOM2 LOCKOUT NORMAL STOP FILL ROOM1 LOCKOUT ROOM 2 RELAY ROOM 1 RELAY HEAT HEAT RELAY FEEDWATER RE...

Страница 20: ...ILER OPERATION MANUAL RUN CLOCK RUN STEAM VALVE OPEN LIGHT MANUAL OPEN AUTODRAIN CLOCK OPTION M 3241 04x POWER LEVEL CONTROL PRINTED CIRCUIT BOARD H M L DRAIN RELAY DRAIN VALVE OPEN LIGHT ROOM STATUS LEDS DRN AUTODRAIN SOLENOID OPTION OFF ROOM2 LOCKOUT NORMAL STOP FILL ROOM1 LOCKOUT ROOM 2 RELAY ROOM 1 RELAY HEAT HEAT RELAY FEEDWATER RELAY R OFF STM STM STEAM VALVE OPEN LIGHT NORMAL CLOSE VALVE WA...

Страница 21: ...e boiler should be ON or the drain should be open and away from the center for OFF or drain closed periods When the clock s pointer is in an area with orange showing its switch will close and turn the boiler ON or open the Autodrain for blowdown NOTE The clocks operate on 120VAC supplied by the boiler s control circuit If this circuit loses power the clocks must be reset to the correct time CONNEC...

Страница 22: ...4211 195 05 22 12 Page 22 AI SERIES STEAM BOILER WITH T100 CONTROL INSTALLATION INSTRUCTIONS This page intentionally left blank ...

Страница 23: ...em with the primary switch Check the primary switch operation by creating pressure in the boiler Also verify that the pressure gauge shows a smooth and steady pressure increase If the primary switch does not open at the correct pressure or the gauge shows rapid pressure increases release all pressure and remove line voltage from the boiler and clean or repair the pressure control assembly as neede...

Страница 24: ...4211 195 05 22 12 Page 24 AI SERIES STEAM BOILER WITH T100 CONTROL INSTALLATION INSTRUCTIONS This page intentionally left blank ...

Страница 25: ...TIONS 4211 195 05 22 12 Page 25 Always confirm pattern as printed is to scale before using as a template Some printers will change pattern size during printing APPENDIX 2 T100 ROUGH IN 2 5 8 2 5 8 5 5 3 4 Step 1 Drill four 3 4 holes level and plumb as shown below ...

Страница 26: ...ote dashed line shows outside edge of T100 control for reference Always confirm pattern as printed is to scale before using as a template Some printers will change pattern size during printing APPENDIX 2 T100 ROUGH IN continued Step 2 Cut straight edges from hole to hole as shown CUT CUT CUT CUT ...

Отзывы: