ISTRIBUTED
C
LOCK
- SYNC0 S
ETUP
Networked Indexer/Driver User Manual
ADVANCED MICRO CONTROLS INC.
106
3.2 Create New PLC Task
You only have to follow this step if the Main PLC task timing verified in step 3.1 above is not the correct
update time for the Networked Driver and the correct time is not an integer multiple of the Main PLC task
timing.
1) In the
Solutions Explorer
, expand out
System
Tasks
so that the tasks are visible. Right click on
Tasks
and
select “Add New Item...”.
2) In the window that opens, name the new task and select “TwinCAT Task With Image” as the
Type
. Click
the [OK] button to accept the values.
Figure T3.2 Create New Task
3) In the window that open, enter the desired update time in Cycle Ticks. By default, each Cycle Tick is 1
millisecond.
4) If needed, expand out the new task so that the Outputs icon is visible.
5) Right click on the Outputs icon and select “Add New Item...”. The
Insert Variable
window will open.
6) Name the new variable. Under
>Data Type
, select “UINT”. Click the [OK] button to close the
Insert
Variable
window.
Figure R8.3 Setting Task Variable Name and Size
Содержание SD17060E-K
Страница 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0S301...
Страница 20: ...UL CUL RECOGNIZED INSTALLATIONS Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 20 Notes...
Страница 40: ...MOTION CONTROL Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 40 Notes...
Страница 50: ...CALCULATING MOVE PROFILES Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 50 Notes...
Страница 56: ...HOMING AN AMCI NETWORKED DRIVER Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 56 Notes...
Страница 64: ...CONFIGURATION DATA FORMAT Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 64 Notes...
Страница 84: ...COMMAND MODE DATA FORMAT Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 84 Notes...
Страница 110: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...