RBE2-8 I
NTRODUCTION
RBE2-8 User Manual
ADVANCED MICRO CONTROLS INC.
10
Status LED’s (continued)
Module Status (MS) LED
The Module Status LED is a bi-color red/green LED. For its location on the relay board, see item
in figure
R1.1 on page 8. The unit will blink the Module Status LED green during initialization. After initialization, the
state of the LED depends on the state of the network adapter and the configured protocol.
Table R1.4 Module Status LED States
Network Status (NS) LED
The Network Status LED is a bi-color red/green LED. For its location on the relay board, see item
in figure
R1.1 on page 8. The state of the LED depends on the state of the network adapter on the protocol the RBE2-8
is configured to for.
Table R1.5 Network Status LED States
LED State
EtherNet/IP Definition
Modbus TCP Definition
PROFINET Definition
Off
No Power
No Power
No power
Alternating
Red/Green
Initializing: Power up Self-Test
Communications failure. There is a communications error between the main processor and
the ethernet co-processor within the unit. You must cycle power to the RBE2-8 to attempt
to clear this fault, or press the “Reset Module” push button to reset the relay board.
Flashing
Green
Initializing: Waiting for valid physical connection to the
network.
Steady Green
Module and Network are operational.
Device Name or IP Address
are set.
Flashing Red
Initializing: IP Address conflict
Initializing: Device Name or
IP Address are not set.
If the Network Status LED is also flashing, the IP Address or Network Protocol has been
changed. Cycle power to the unit or press the “Reset Module” push button to continue.
LED State
EtherNet/IP Definition
Modbus TCP Definition
PROFINET Definition
Off
No Power
No power or no TCP
connections
No power, duplicate IP
address on the network,
mismatch in Device Name,
or no connection to IO
Controller.
Alternating
Red/Green
Power up Self-Test
Power up Self-Test
Power up Self-Test
Blinking
Green
Ethernet connection, but
no CIP connections
Indicates number of connec-
tions with 2 second delay
between group. The
RBE2-8 supports up to four
concurrent connections.
On-line, Stop state. A
connection with the IO
Controller is established and
it is in its STOP state.
Steady Green
Valid Ethernet network
and CIP connections
Not Implemented
On-line, Run state. A
connection with the IO
Controller is established and
it is in its RUN state.
Blinking Red
If the MS LED is steady
green: Network
Connection Timeout
Not Implemented
Not Implemented
If the MS LED is blinking green: IP Address or Network Protocol changed: Cycle
power
Steady Red
Duplicate IP address on network.
Not Implemented.
Содержание RBE2-8
Страница 14: ...RBE2 8 INTRODUCTION RBE2 8 User Manual ADVANCED MICRO CONTROLS INC 14 Notes ...
Страница 30: ...PROTOCOL SPECIFIC INFORMATION RBE2 8 User Manual ADVANCED MICRO CONTROLS INC 30 Notes ...
Страница 48: ...MODBUS TCP CONFIGURATION RBE2 8 User Manual ADVANCED MICRO CONTROLS INC 48 Notes ...
Страница 54: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC ...