RBE2-8 User Manual
ADVANCED MICRO CONTROLS INC.
38
4.2 Add the RBE2-8 (continued)
6) Set the following parameters in the Module Properties window. All parameters not listed here are optional.
Figure T4.3 shows a completed screen.
Figure T4.3 Configuration Screen - Generic Device
Name:
A descriptive name for the RBE2-8
Comm Format:
Data - INT
The Comm Format defaults to Data - DINT. The RBE2-8 will not be able to communi-
cate with the host controller if this format is not changed when the device is added to the
system. Once added, the Comm Format cannot be changed. The device must be deleted
and again added to the project if the Comm Format is incorrect.
IP Address:
Must be the address you set for the RBE2-8. Refer to the
Set the IP Address and Protocol
task chapter starting on page 25 for information on setting the IP Address of the unit.
Input:
Assembly Instance = 100, Size = 2 words.
Output:
Assembly Instance = 150, Size = 2 words.
Configuration:
Assembly Instance = 110, Size = 0
7) Verify that the “Open Module Properties” check box is selected and click on [OK]. The Module Properties
window will open. You can set the RPI time as required for your system in this window. The minimum RPI
time for an RBE2-8 is one millisecond. When done, click on [OK] to complete the setup.
Error Code 16#0109
The PLC will generate an Error Code 16#0109 when the Comm Format parameter is not changed from its
default of “Data-DINT” to “Data-INT”. This is the most common cause of communication failures with the
RBE2-8.
Содержание RBE2-8
Страница 14: ...RBE2 8 INTRODUCTION RBE2 8 User Manual ADVANCED MICRO CONTROLS INC 14 Notes ...
Страница 30: ...PROTOCOL SPECIFIC INFORMATION RBE2 8 User Manual ADVANCED MICRO CONTROLS INC 30 Notes ...
Страница 48: ...MODBUS TCP CONFIGURATION RBE2 8 User Manual ADVANCED MICRO CONTROLS INC 48 Notes ...
Страница 54: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC ...