PROFINET N
ETWORK
C
ONFIGURATION
RBE2-8 User Manual
ADVANCED MICRO CONTROLS INC.
52
7.5 Set the I/O Configuration
The RBE2-8 units require 2 Input Words (4 Input Bytes) and 2 Output Words (4 Output Bytes). All required
Input and Output Bytes are defined by the GSDML file and divided into suitable modules. These settings are
shown in the Table T7.1.
Table T7.1 PROFINET I/O Configuration
1) With the RBx2-8 icon selected on the PROFINET bus, click on the “Device view” tab. The view in the
Hardware Catalog will change. Expand the Module tree to show both the Input and Output modules.
2) To map the I/O bytes to the CPU, double click on the “4 bytes IN” and “4 bytes OUT” icons in the
Hardware Catalog. The system will automatically assign the next I and Q addresses to the data table.
Figure T7.4 I/O Byte Mapping
7.6 Verify and Download the New Configuration
1) Continue by adding any remaining devices to your PROFINET network.
2) Compile and download the project to the CPU.
Input / Output Bytes
of an RBE2-8
Input / Output Modules
of an RBE2-8
4 Input Bytes
Input Module - Slot 1: 4 bytes
4 Output Bytes
Output Module - Slot 2: 4 bytes