CONNECTING THE TESTER 

 

Connect the tester to the service outlet via a fire hose to the inlet connection.  The tester is now ready 
for use. 

 

4.

 

STATIC & RESIDUAL (DYNAMIC) PRESSURE TEST

 

 

For Static Pressure Test 

 

If fitted (as optional extra) CLOSE the outlet valve on the tester.  If valve is not fitted, cap the 
outlet with a blanking cap.  

For Residual (Dynamic) Pressure Test  

A diffuser should be fitted to the valve & then the valve partially opened. 

 

5.

 

Open the service outlet valve and the 

‘static’ (no flow) pressure will be indicated on the pressure 

gauge. 

 

6.

 

FULL (UNRESTRICTED) FLOW TEST

 

Continue on from step 4 (above) and open the test box outlet valve.  The flow meter will now 
 Indicate the available flow in L.P.M. (or LPS if supplied).  During this test the pressure gauge will  
indicate zero or just above zero. 

 

7.

 

FULL RESTRICTED FLOW TEST

 

After selecting and fitting the appropriate hosereel nozzle repeat the test as in step 5 (above). The flow 
meter  will  once  again  indicate  the  available  flow  rate  via  this  nozzle  and  the  pressure  gauge  will 
indicate at what pressure. 
 

8. 

OPERATION OF DIGITAL DISPLAY TOTALIZER (type 8150) 

 

The 8150-1 display shows the flow rate in large numerals and a totalizer value in smaller  

 

numerals. Any one of three different totalizers can be selected as the standard display. 

Press the UP or DOWN keys to scroll through all three totalizer values during normal  

 

operation. 

 

 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

  
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 