85 Rev. 3
COOLING PERFORMANCE DA
T
A
EXPANDED PERFORMANCE DATA
COOLING OPERATION
MODEL: RCB48A3B / CCA54F*C + TXV03A
Outdoor Ambient Temperature
65
75
85
95
105
115
Entering Indoor Wet Bulb Temperature
IDB*
Airflow
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
MBh
47.2
48.2
51.5
55.0
46.1
47.1
50.3
53.8
45.0
46.0
49.1
52.5
43.9
44.8
47.9
51.2
41.7
42.6
45.5
48.6
38.6
39.5
42.1
45.1
S/T
0.89
0.83
0.68
0.51
0.92
0.86
0.70
0.53
0.94
0.89
0.72
0.54
1.00
0.91
0.74
0.56
1.00
0.95
0.77
0.58
1.00
0.96
0.78
0.58
Delta T
21
21
18
14
22
21
18
14
22
21
18
14
22
21
18
15
21
21
18
14
20
19
17
13
1800
KW
3.08
3.16
3.27
3.39
3.35
3.43
3.56
3.69
3.59
3.68
3.81
3.95
3.80
3.89
4.04
4.19
3.98
4.08
4.23
4.38
4.13
4.24
4.39
4.56
AMPS
9.0
9.2
9.5
9.9
9.7
10.0
10.3
10.7
10.6
10.9
11.2
11.7
11.3
11.6
12.0
12.5
12.1
12.4
12.8
13.3
12.8
13.1
13.6
14.1
HI PR
153
165
174
181
172
185
195
203
195
210
222
231
222
239
253
263
250
269
284
296
276
297
314
327
LO PR
62
66
72
76
65
69
76
81
68
72
79
84
71
76
83
88
75
80
87
92
77
82
90
96
MBh
45.8
46.8
50.0
53.4
44.7
45.7
48.8
52.2
43.7
44.6
47.7
51.0
42.6
43.5
46.5
49.7
40.5
41.3
44.2
47.2
37.5
38.3
40.9
43.7
S/T
0.85
0.80
0.65
0.48
0.88
0.82
0.67
0.50
0.90
0.85
0.69
0.51
0.93
0.87
0.71
0.53
0.97
0.91
0.74
0.55
0.97
0.91
0.74
0.56
Delta T
22
21
19
15
23
22
19
15
23
22
19
15
23
22
19
15
22
22
19
15
21
20
17
14
80
1600
KW
3.06
3.13
3.24
3.36
3.32
3.40
3.53
3.66
3.56
3.65
3.78
3.92
3.77
3.86
4.00
4.15
3.94
4.04
4.19
4.34
4.10
4.20
4.35
4.51
AMPS
8.9
9.1
9.4
9.8
9.7
9.9
10.2
10.6
10.5
10.8
11.1
11.5
11.2
11.5
11.9
12.4
12.0
12.3
12.7
13.2
12.7
13.0
13.4
14.0
HI PR
151
163
172
179
170
183
193
201
193
208
220
229
220
237
250
261
248
266
281
293
273
294
311
324
LO PR
61
65
71
76
65
69
75
80
67
72
78
83
71
75
82
87
74
79
86
92
77
81
89
95
MBh
42.3
43.2
46.1
49.3
41.3
42.2
45.1
48.2
40.3
41.2
44.0
47.0
39.3
40.2
42.9
45.9
37.3
38.2
40.8
43.6
34.6
35.4
37.8
40.4
S/T
0.82
0.77
0.62
0.47
0.85
0.79
0.65
0.48
0.87
0.81
0.66
0.50
0.90
0.84
0.68
0.51
0.93
0.87
0.71
0.53
0.94
0.88
0.72
0.54
Delta T
23
22
19
15
23
22
19
15
23
22
19
15
23
22
19
15
23
22
19
15
21
20
18
14
1400
KW
2.97
3.04
3.15
3.27
3.23
3.31
3.43
3.55
3.46
3.55
3.67
3.81
3.66
3.75
3.89
4.03
3.83
3.93
4.07
4.22
3.98
4.08
4.23
4.39
AMPS
8.7
8.9
9.2
9.5
9.4
9.6
9.9
10.3
10.2
10.5
10.8
11.2
10.9
11.2
11.6
12.0
11.6
11.9
12.3
12.8
12.3
12.6
13.1
13.6
HI PR
147
158
167
174
165
177
187
195
187
202
213
222
213
230
243
253
240
258
273
285
265
285
301
314
LO PR
59
63
69
73
63
67
73
78
65
69
76
81
68
73
80
85
72
76
83
89
74
79
86
92
MBh
48.0
48.9
51.2
54.7
46.9
47.8
50.0
53.4
45.8
46.6
48.8
52.1
44.6
45.5
47.7
50.8
42.4
43.2
45.3
48.3
39.3
40.0
41.9
44.7
S/T
0.93
0.90
0.81
0.66
0.97
0.93
0.84
0.68
0.99
0.96
0.86
0.70
1.00
0.99
0.89
0.72
1.00
1.00
0.92
0.75
1.00
1.00
0.93
0.76
Delta T
23
22
21
18
23
23
21
19
23
23
22
19
23
23
22
19
22
22
21
18
20
20
20
17
1800
KW
3.11
3.19
3.30
3.42
3.38
3.47
3.59
3.72
3.62
3.71
3.85
3.99
3.84
3.93
4.07
4.23
4.02
4.12
4.27
4.43
4.17
4.28
4.43
4.60
AMPS
9.1
9.3
9.6
10.0
9.8
10.1
10.4
10.8
10.7
11.0
11.3
11.8
11.4
11.7
12.1
12.6
12.2
12.5
12.9
13.4
12.9
13.2
13.7
14.2
HI PR
154
166
175
183
173
186
197
205
197
212
224
234
224
242
255
266
252
272
287
299
279
300
317
331
LO PR
62
66
73
77
66
70
77
82
69
73
80
85
72
77
84
89
75
80
88
93
78
83
91
97
MBh
46.6
47.5
49.7
53.1
45.5
46.4
48.6
51.8
44.4
45.3
47.4
50.6
43.3
44.2
46.3
49.4
41.2
42.0
44.0
46.9
38.1
38.9
40.7
43.4
S/T
0.89
0.86
0.77
0.63
0.92
0.89
0.80
0.65
0.94
0.91
0.82
0.67
0.98
0.94
0.85
0.69
1.00
0.98
0.88
0.72
1.00
0.98
0.89
0.72
Delta T
24
23
22
19
24
24
22
19
24
24
22
19
24
24
23
20
24
24
22
19
22
22
21
18
85
1600
KW
3.08
3.16
3.27
3.39
3.35
3.43
3.56
3.69
3.59
3.68
3.81
3.95
3.80
3.89
4.04
4.19
3.98
4.08
4.23
4.38
4.13
4.24
4.39
4.56
AMPS
9.0
9.2
9.5
9.9
9.7
10.0
10.3
10.7
10.6
10.9
11.2
11.7
11.3
11.6
12.0
12.5
12.1
12.4
12.8
13.3
12.8
13.1
13.6
14.1
HI PR
153
165
174
181
172
185
195
203
195
210
222
231
222
239
253
263
250
269
284
296
276
297
314
327
LO PR
62
66
72
76
65
69
76
81
68
72
79
84
71
76
83
88
75
80
87
92
77
82
90
96
MBh
43.0
43.8
45.9
49.0
42.0
42.8
44.8
47.8
41.0
41.8
43.8
46.7
40.0
40.8
42.7
45.6
38.0
38.7
40.6
43.3
35.2
35.9
37.6
40.1
S/T
0.86
0.83
0.75
0.61
0.89
0.86
0.77
0.63
0.91
0.88
0.79
0.64
0.94
0.91
0.82
0.66
0.98
0.94
0.85
0.69
0.98
0.95
0.86
0.70
Delta T
24
24
23
19
25
24
23
20
25
24
23
20
25
24
23
20
24
24
23
20
23
22
21
18
1400
KW
3.00
3.07
3.18
3.30
3.26
3.34
3.46
3.59
3.49
3.58
3.71
3.84
3.70
3.79
3.92
4.07
3.87
3.96
4.11
4.26
4.02
4.12
4.27
4.43
AMPS
8.8
9.0
9.3
9.6
9.5
9.7
10.0
10.4
10.3
10.6
10.9
11.3
11.0
11.3
11.7
12.1
11.7
12.0
12.4
12.9
12.4
12.8
13.2
13.7
HI PR
148
160
169
176
166
179
189
197
189
204
215
224
216
232
245
255
242
261
276
287
268
288
304
318
LO PR
60
64
70
74
63
67
74
78
66
70
76
81
69
74
80
86
72
77
84
90
75
80
87
93
* Entering Indoor Dry Bulb Temperature
NOTE: Shaded area is ARI Rating Conditions