COOLING PERFORMANCE DATA
176 Rev. 3
PERFORMANCE TEST
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:
If conditions vary from this, results will change as follows:
1.
As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (
∆
T). Low and
high side pressures, power will not change.
2.
As indoor CFM decreases, a slight increase will occur in indoor temperature drop (
∆
T). A slight decrease will
occur in low and high side pressures and power.
A properly operating unit should be within plus or minus 3 degrees of the typical (
∆∆∆∆∆
T) value shown.
A properly operating unit should be within plus or minus 7 PSIG of the head pressure shown.
A properly operating unit should be within plus or minus 3 PSIG of the suction pressure shown.
A properly operating unit should be within plus or minus 3 Amps of the typical value shown.