![Amana P1172401C Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/amana/p1172401c/p1172401c_service-manual_2916114019.webp)
19 Rev. 3
BBA/BBC BLOWER COIL SPECIFICA
TIONS
EHK/ECB ELECTRIC HEA
TER DA
T
A
CAUTI
O
N
To avoid the risk of fire, overcurrent protection must not exceed the value listed above.
Minimum Circuit Ampacity
Heater EHK05B/C EHK07B/C EHK10B/C EHK15B/C EHK20B/C EHK25B/C EHK30B/C ECB15B/C + ECB20B/C + ECB25B/C + ECB30B/C +
Model
ECB05B/C ECB07B/C ECB10B/C ECB15B/C ECB20B/C ECB25B/C ECB30B/C
SPK02A
SPK02A
SPK03A
SPK03A
L1/L2
27.8
41.3
53.8
53.8
53.8
79.8
105.7
BBA24A2A
L3/L4
26
52
L1/L2
29
42.4
55
55
55
55
55
80.9
106.9
132.8
158.8
BBA36A2A
L3/L4
26
55
55
52
L5/L6
26
55
L1/L2
29.7
43.2
55.7
55.7
55.7
55.7
55.7
81.6
107.6
133.6
159.5
BBA48A2A
L3/L4
26
55
55
55
L5/L6
26
55
L1/L2
30.9
44.4
56.9
56.9
56.9
56.9
56.9
82.8
108.8
134.8
160.7
BBA60A2A
L3/L4
26
55
55
52
L5/L6
26
55
L1/L2
31.3
44.8
57.3
57.3
57.3
57.3
57.3
83.3
109.2
135.2
161.2
BBC36A2A
L3/L4
26
55
55
52
L5/L6
26
55
L1/L2
34.7
48.2
60.7
60.7
60.7
60.7
60.7
86.6
112.6
138.6
164.5
BBC60A2A
L3/L4
26
55
55
52
L5/L6
26
55
Maximum Overcurrent Protection
Heater EHK05B/C EHK07B/C EHK10B/C EHK15B/C EHK20B/C EHK25B/C EHK30B/C ECB15B/C + ECB20B/C + ECB25B/C + ECB30B/C +
Model
ECB05B/C ECB07B/C ECB10B/C ECB15B/C ECB20B/C ECB25B/C ECB30B/C
SPK02A
SPK02A
SPK03A
SPK03A
L1/L2
30
45
60
60
60
80
110
BBA24A2A
L3/L4
30
60
L1/L2
30
45
60
60
60
60
60
90
110
150
175
BBA36A2A
L3/L4
30
60
60
60
L5/L6
30
60
L1/L2
30
45
60
60
60
60
60
90
110
150
175
BBA48A2A
L3/L4
30
60
60
60
L5/L6
30
60
L1/L2
35
45
60
60
60
60
60
90
110
150
175
BBA60A2A
L3/L4
30
60
60
60
L5/L6
30
60
L1/L2
35
45
60
60
60
60
60
90
110
150
175
BBC36A2A
L3/L4
30
60
60
60
L5/L6
30
60
L1/L2
35
50
70
70
70
70
70
90
125
150
175
BBC60A2A
L3/L4
30
60
60
60
L5/L6
30
60