SS-AMVC8
www.amana-hac.com
9
8
www.amana-hac.com
SS-AMVC8
p
roDuCT
S
peCiFiCATionS
p
roDuCT
S
peCiFiCATionS
ADVC8 A
irFlow
D
ATA
(
ConT
.)
H
eATing
S
peeDS
ADVC80603B**
(Rise Range: 30° - 60°F)
ADVC80805C*B
(Rise Range: 35° - 65°F)
Cooling
Speed Tap
Adjust
Tap
Low-Stage
CFM¹
High-Stage
CFM¹
Rise
(°F)
Cooling
Speed Tap
Adjust
Tap
Low-Stage
CFM¹
High-Stage
CFM¹
Rise
(°F)
A
Minus (-)
660
945
55
A
Minus (-)
850
1,215
55
Normal
735
1050
49
Normal
945
1,350
49
Plus (+)
810
1155
45
Plus (+)
1,040
1,485
45
B
Minus (-)
725
1035
50
B
Minus (-)
915
1,305
51
Normal
805
1150
45
Normal
1,015
1,450
46
Plus (+)
885
1265
41
Plus (+)
1,115
1,595
42
C
Minus (-)
790
1125
46
C
Minus (-)
975
1,395
48
Normal
875
1250
41
Normal
1,085
1,550
43
Plus (+)
960
1375
38
Plus (+)
1,195
1,705
39
D
Minus (-)
850
1215
43
D
Minus (-)
1,040
1,485
45
Normal
945
1350
38
Normal
1,155
1,650
40
Plus (+)
1040
1485
35
Plus (+)
1,270
1,815
37
ADVC81005C**
(Rise Range: 35° - 65°F)
Cooling
Speed Tap
Adjust Tap
Low-Stage
CFM¹
High-Stage
CFM¹
Rise
(°F)
A
Minus (-)
975
1395
61
Normal
1085
1550
55
Notes
• These charts are for furnaces installed at 0’- 4,500’. At higher alti-
tudes, a properly de-rated unit will have the same temperature rise
at a particular CFM, while the ESP at that CFM will be lower.
• The installation must be adjusted to obtain a temperature rise
within the range listed on the furnace nameplate.
• Do not operate above .5” w.c. ESP in heating mode.
• Propane gas installations will have a high-stage rise approximately
4°F lower than shown in the tables.
Plus (+)
1195
1705
50
B
Minus (-)
1040
1485
57
Normal
1155
1650
52
Plus (+)
1270
1815
47
C
Minus (-)
1105
1575
54
Normal
1225
1750
49
Plus (+)
1350
1925
44
D
Minus (-)
1135
1620
53
Normal
1260
1800
47
Plus (+)
1385
1980
43
¹ @ .1” to .8” W.C. ESP
C
onTinouS
F
An
S
peeDS
Model
Furnace
Maximum CFM
Continuous
Fan Speed¹
,
²
ADVC80603B**
1760
530
ADVC80805C**
2000
600
ADVC81005C**
2000
600
¹ Continuous fan speed is 25% of furnace maximum CFM
² Three continuous fan speeds are possible with the CTK01AA thermostat:
25%, 50%, and 75% of furnace maximum CFM