background image

  

Always 

O

n UPS Systems 

 

 

M1306_GES-242NX-R Operators and Install Manual V1.0 2012-06-12 

3.4.  Site & Environment Consideration 

 
 
Usually the life expectancy of the DC UPS system is 8 to 10 years. The optimal life expectancy 
of the DC UPS system can be achieved by careful consideration of the site and environment.  
 
The following precautions and recommendations should be checked when considering the site 
and environment for the DC UPS: 
 

a. 

The DC UPS should be located in a place with adequate ventilation (refer to the 

specification of the heat dissipation of the DC UPS). Should the DC UPS be installed in a 
sealed room, care must be taken to ensure adequate heat evacuation is provided.  
 

b. 

Void space is not required on all sides of the DC UPS system, but adequate space, a 

minimum of 1m (3’), should be allowed at the front for the door to open and a minimum of 
60cm (2’) should be allowed on the right side to allow for the door to open and removal of 
the side panels for operation or maintenance purposes (exceptions to space requirements 
would occur with approved layouts).  Adequate space, a minimum of 60cm (2’) 
[recommended 1m (3’)], should also be allowed at the top of the DC UPS system to allow for 
proper heat dissipation and ventilated through the top openings (optional ventilation booth is 
available upon request). 

 

c. 

Do not place any objects on the top of the DC UPS that might obscure the ventilation. Do 

not place the DC UPS near any heat source, or machinery, which may produce metallic 
particles, dust or powder.  Do not place the DC UPS near equipment that will produce 
corrosive substances or vapor. 
 

d. 

Do not place the DC UPS below the shower of a fire extinguishing system (optional drip 

shield available). Abnormal conditions of the DC UPS should be protected by a cutoff from 
the power supply. 
 

e. 

The user is required to guarantee the temperature and humidity values of the site into 

which the DC UPS will be installed, meet the required and published manufacturer 
specifications. The DC UPS should be installed within the range allowed by these 
specifications. The DC UPS is capable of continuous normal operation within a temperature 
range of 0°C (32°F) to 40°C (104°F). For optimal performance and reliability the 
recommended environment temperature is best at 25°C, with humidity < 80% non-
condensing. 

 

f. 

The floor loading capacity should be sufficient to endure the weight of the DC UPS and 

and its internal batteries.  

 

g. 

Walls, ceilings, floors or anything near to the DC UPS should be constructed of non-

combustible materials. A portable fire extinguisher should be accessible nearby. 

 
 

Содержание GES-242NX-R

Страница 1: ...M1306_GES 242NX R Operators and Install Manual V1 0 2012 06 12 GES 242NX R 24VDC UPS Installation and Operators Manual...

Страница 2: ...Always On UPS Systems M1306_GES 242NX R Operators and Install Manual V1 0 2012 06 12...

Страница 3: ...3 1 Transport 5 3 2 Delivery 5 3 3 Storage 6 3 4 Site Environment Consideration 7 3 5 Unpacking 8 3 6 Cable Selection 9 4 80KVA DC UPS SYSTEMS LAYOUT DRAWINGS 10 5 DC UPS WIRING DIAGRAMS 11 6 TERMINAL...

Страница 4: ...s is a manual for Installation purposes only Do not attempt the start up of the DC UPS or apply power to the input terminals Factory authorized personnel shall inspect installation prior to start up a...

Страница 5: ...irectly Do not use outdoors The use of accessory equipment not recommended by Always On may cause an unsafe condition WARNING RISK OF ELECTRICAL SHOCK use extreme caution when removing covers All main...

Страница 6: ...r heat sources gas or electric heaters STORAGE Store the DC UPS in a dry location free of contaminants Storage temperature must be within 25 C 13 F to 55 C 131 F If the unit is stored for a period exc...

Страница 7: ...de before work is started This manual is designed as an aid tool in diagnosing problems that may arise Always On does not assume responsibility if information causes injuries Apart from the front door...

Страница 8: ...e lifted by crane use suitable lifting straps and spreader bars 3 2 Delivery Upon receiving the DC UPS system inspect the packaging integrity and the physical condition of the cabinets carefully In th...

Страница 9: ...ature range of 25 C 13 F to 55 C 131 F Exceeding this temperature range may cause damage STORAGE OF BATTERIES Although this system includes maintenance free batteries keep in mind that they are subjec...

Страница 10: ...proper heat dissipation and ventilated through the top openings optional ventilation booth is available upon request c Do not place any objects on the top of the DC UPS that might obscure the ventila...

Страница 11: ...destination carefully remove all the packaging material from the DC UPS and place the DC UPS in its final position This DC UPS system has passed all stages of production testing and final QC testing...

Страница 12: ...has to be sized according to the UPS power rating Sizing of circuit breakers fuses and cables for input utility output load and battery must meet the requirements of local and national electrical cod...

Страница 13: ...S 242NX R Operators and Install Manual V1 0 2012 06 12 10 Figure 4 1 Front View of System with Door Open Single Wide 4 24VDC UPS SYSTEMS LAYOUT DRAWINGS RECTIFIER DC OUTPUT WARNING LOW BAT BAT STOP IN...

Страница 14: ...Always On UPS Systems M1306_GES 242NX R Operators and Install Manual V1 0 2012 06 12 11 Figure 5 1 DC UPS Single Line 5 DC UPS WIRING DIAGRAMS...

Страница 15: ...Always On UPS Systems M1306_GES 242NX R Operators and Install Manual V1 0 2012 06 12 12 Figure 5 2 DC UPS Power Cabling Diagram...

Страница 16: ...Always On UPS Systems M1306_GES 242NX R Operators and Install Manual V1 0 2012 06 12 13 6 TERMINAL STRIP LAYOUT Figure 6 1 Terminal Strip Layout...

Страница 17: ...Always On UPS Systems M1306 GES 242NX R Operators and Install Manual 2 16 2009 Approved Eng Mgr T Naito 14 7 C CHANNEL INSTALLATION...

Страница 18: ...breaker b Wait 5 seconds for the Charger LED to start flashing c Turn ON the BATTERY breaker d Turn ON the OUTPUT breaker 1 2 Shutdown Procedure a Turn OFF the OUTPUT breaker b Turn OFF the BATTERY b...

Страница 19: ...E DC OUTPUT VOLTAGE DC BATTERY CURRENT DC OUTPUT CURRENT METERING ALARM SILENCE RESET E Startup Procedure 1 Turn ON the INPUT breaker 2 Wait 5 seconds for the Charger LED to start flashing 3 Turn ON t...

Страница 20: ...bed below INPUT No AC Voltage is detected on the input of the UPS CHARGER The LED will illuminate continuously when the charger fails to deliver the necessary voltage to charge the batteries The LED w...

Страница 21: ...is repaired and functioning properly the buzzer will re activate letting the user know to put the toggle switch back into the normal operating mode F Buzzer outlet There is a buzzer located behind the...

Страница 22: ...th DC rectifiers have failed and that the DC UPS should be immediately shut down LOW BATTERY This alert is designed to inform the operator that the battery voltage is below 22 0 VDC and serve as a rem...

Страница 23: ...Always On UPS Systems M1306 GES 242NX R Operators and Install Manual 2 16 2009 Approved Eng Mgr T Naito 20 11 DIMENSIONAL DRAWING Figure 10 1 Figure 8 1 24VDC DC UPS Exterior Layout...

Страница 24: ...Fax 250 491 9775 Email qa alwayson com Website www alwayson com Software Questions Always On UPS Systems Inc 1 150 Campion Road Kelowna BC Canada V1X 7S8 Phone 250 491 9777 Ext 204 Fax 250 491 9775 Em...

Отзывы: