
Always
O
n UPS Systems
M1306_GES-242NX-R Operators and Install Manual V1.0 2012-06-12
15
8. OPERATION INSTRUCTIONS
1.1. Startup
Procedure
a.
Turn ON the INPUT breaker.
b.
Wait 5 seconds for the “Charger LED” to start flashing.
c.
Turn ON the BATTERY breaker.
d.
Turn ON the OUTPUT breaker.
1.2. Shutdown
Procedure
a.
Turn OFF the OUTPUT breaker.
b.
Turn OFF the BATTERY breaker.
c.
Turn OFF the INPUT breaker.
CAUTION: Batteries will become damaged upon
over-discharge. Upon “BATTERY STOP ALARM”,
shutdown loads and the DC UPS System.