M1306_GES-242NX-R Operators and Install Manual V1.0 2012-06-12 

 

2. IMPORTANT SAFETY INSTRUCTIONS 

 
 

READ AND FOLLOW ALL SAFETY INSTRUCTIONS. 

SAVE THESE INSTRUCTIONS. 

 
 

This manual contains important safety instructions that should be followed during installation and 
maintenance of the N Series DC UPS system and optional packages. Before the installation 
process begins, we recommend that the installer read through the safety precautions, operators 
manual and the option installation instructions, taking all necessary safety precautions to protect 
themselves and the equipment being installed. 
 

 
 
GENERAL 

-

 

Move the DC UPS in an upright position, in its original packaging, to its final destination. 
To lift the cabinets, use a forklift or lifting belts with spreader bars. 

Check for sufficient floor and elevator loading capacity. 

Check the integrity of the DC UPS equipment carefully. 

 

If visible damage is evident, 

do not

 attempt to install or start the DC UPS. Contact the transport 

delivery company immediately, file a claim with the transport company and inform Always 

O

directly. 

Do not use outdoors 

-  The use of accessory equipment not recommended by Always 

O

n may cause an unsafe 

condition 

- WARNING! 

RISK OF ELECTRICAL SHOC

K: use extreme caution when removing covers. 

-  All maintenance and service work should be performed by qualified and trained service 

personnel. The DC UPS may contain its own energy source, (batteries) which can be 
dangerous to the untrained person. This DC UPS contains potentially hazardous voltages 

The field-wiring terminals may be electrically live, even when the DC UPS is not connected to 
the utility. 

Use caution when servicing batteries. A battery can present a risk of electrical shock, burn from 
high short-current. Battery acid can cause burns to skin and eyes. If acid is spilled on skin or in 
eyes, flush with fresh water and contact physician immediately. 

When replacing batteries use the same number and type (sealed-cell lead acid). 

Proper disposal of batteries is required. Refer to your local codes for disposal requirements. 

-  Dangerous voltages may be present during battery operation. The batteries must be 

disconnected during maintenance or service work. (Open battery breaker of fuses) 

Be aware that the inverter can restart automatically after the utility voltage is restored. 

Do not use this equipment for other than intended use. 

Содержание GES-242NX-R

Страница 1: ...M1306_GES 242NX R Operators and Install Manual V1 0 2012 06 12 GES 242NX R 24VDC UPS Installation and Operators Manual...

Страница 2: ...Always On UPS Systems M1306_GES 242NX R Operators and Install Manual V1 0 2012 06 12...

Страница 3: ...3 1 Transport 5 3 2 Delivery 5 3 3 Storage 6 3 4 Site Environment Consideration 7 3 5 Unpacking 8 3 6 Cable Selection 9 4 80KVA DC UPS SYSTEMS LAYOUT DRAWINGS 10 5 DC UPS WIRING DIAGRAMS 11 6 TERMINAL...

Страница 4: ...s is a manual for Installation purposes only Do not attempt the start up of the DC UPS or apply power to the input terminals Factory authorized personnel shall inspect installation prior to start up a...

Страница 5: ...irectly Do not use outdoors The use of accessory equipment not recommended by Always On may cause an unsafe condition WARNING RISK OF ELECTRICAL SHOCK use extreme caution when removing covers All main...

Страница 6: ...r heat sources gas or electric heaters STORAGE Store the DC UPS in a dry location free of contaminants Storage temperature must be within 25 C 13 F to 55 C 131 F If the unit is stored for a period exc...

Страница 7: ...de before work is started This manual is designed as an aid tool in diagnosing problems that may arise Always On does not assume responsibility if information causes injuries Apart from the front door...

Страница 8: ...e lifted by crane use suitable lifting straps and spreader bars 3 2 Delivery Upon receiving the DC UPS system inspect the packaging integrity and the physical condition of the cabinets carefully In th...

Страница 9: ...ature range of 25 C 13 F to 55 C 131 F Exceeding this temperature range may cause damage STORAGE OF BATTERIES Although this system includes maintenance free batteries keep in mind that they are subjec...

Страница 10: ...proper heat dissipation and ventilated through the top openings optional ventilation booth is available upon request c Do not place any objects on the top of the DC UPS that might obscure the ventila...

Страница 11: ...destination carefully remove all the packaging material from the DC UPS and place the DC UPS in its final position This DC UPS system has passed all stages of production testing and final QC testing...

Страница 12: ...has to be sized according to the UPS power rating Sizing of circuit breakers fuses and cables for input utility output load and battery must meet the requirements of local and national electrical cod...

Страница 13: ...S 242NX R Operators and Install Manual V1 0 2012 06 12 10 Figure 4 1 Front View of System with Door Open Single Wide 4 24VDC UPS SYSTEMS LAYOUT DRAWINGS RECTIFIER DC OUTPUT WARNING LOW BAT BAT STOP IN...

Страница 14: ...Always On UPS Systems M1306_GES 242NX R Operators and Install Manual V1 0 2012 06 12 11 Figure 5 1 DC UPS Single Line 5 DC UPS WIRING DIAGRAMS...

Страница 15: ...Always On UPS Systems M1306_GES 242NX R Operators and Install Manual V1 0 2012 06 12 12 Figure 5 2 DC UPS Power Cabling Diagram...

Страница 16: ...Always On UPS Systems M1306_GES 242NX R Operators and Install Manual V1 0 2012 06 12 13 6 TERMINAL STRIP LAYOUT Figure 6 1 Terminal Strip Layout...

Страница 17: ...Always On UPS Systems M1306 GES 242NX R Operators and Install Manual 2 16 2009 Approved Eng Mgr T Naito 14 7 C CHANNEL INSTALLATION...

Страница 18: ...breaker b Wait 5 seconds for the Charger LED to start flashing c Turn ON the BATTERY breaker d Turn ON the OUTPUT breaker 1 2 Shutdown Procedure a Turn OFF the OUTPUT breaker b Turn OFF the BATTERY b...

Страница 19: ...E DC OUTPUT VOLTAGE DC BATTERY CURRENT DC OUTPUT CURRENT METERING ALARM SILENCE RESET E Startup Procedure 1 Turn ON the INPUT breaker 2 Wait 5 seconds for the Charger LED to start flashing 3 Turn ON t...

Страница 20: ...bed below INPUT No AC Voltage is detected on the input of the UPS CHARGER The LED will illuminate continuously when the charger fails to deliver the necessary voltage to charge the batteries The LED w...

Страница 21: ...is repaired and functioning properly the buzzer will re activate letting the user know to put the toggle switch back into the normal operating mode F Buzzer outlet There is a buzzer located behind the...

Страница 22: ...th DC rectifiers have failed and that the DC UPS should be immediately shut down LOW BATTERY This alert is designed to inform the operator that the battery voltage is below 22 0 VDC and serve as a rem...

Страница 23: ...Always On UPS Systems M1306 GES 242NX R Operators and Install Manual 2 16 2009 Approved Eng Mgr T Naito 20 11 DIMENSIONAL DRAWING Figure 10 1 Figure 8 1 24VDC DC UPS Exterior Layout...

Страница 24: ...Fax 250 491 9775 Email qa alwayson com Website www alwayson com Software Questions Always On UPS Systems Inc 1 150 Campion Road Kelowna BC Canada V1X 7S8 Phone 250 491 9777 Ext 204 Fax 250 491 9775 Em...

Отзывы: