M1306_GES-242NX-R Operators and Install Manual V1.0 2012-06-12
18
C. Rectifier LED:
This LED is lit when the rectifier is operating, the supply is within operating
parameters, and the input breaker is closed.
D. Output LED:
This LED is lit when there is DC power present at the output terminals.
E
:
Callback Switch:
Is installed to allow the user to silence the buzzer when a fault arises while
they are working on the unit. Once the system is repaired and functioning
properly the buzzer will re-activate letting the user know to put the toggle switch
back into the normal operating mode.
F: Buzzer outlet:
There is a buzzer located behind the LCD Display. The buzzer will allow for a
continuous audile notification during an abnormal condition. The buzzer will
be activated under one of the following conditions: (During some conditions,
the buzzer is mutable. These functions are described for your reference.)
•
INPUT BREAKER IS OPEN
Mutable
•
ABNORMAL CHARGER CONDITION
Un-Muteable
•
ABNORMAL RECTIFIER CONDITION
Un-Muteable
•
LOW BATTERY
Mutable
•
BATTERY SHUTDOWN
Un-Muteable
•
OUTPUT BREAKER IS OPEN
Mutable