GRID
Troubleshooting
Failures’ table
The table here below gives the exemples of presumed failures including the
remedical measures :
EXAMPLE OF TROUBLE 1 :
Operating mechanism does not perform
opening or closing operation
Cause of the presumed failure
Remedical measures
D
Tripping voltage lacking ?
D
Coil defective ?
D
Auxiliairy contacts do not transmit
the order ?
D
...
D
Secure the supply voltage
D
Replace the coil
D
Proceed to adjust the auxiliary
contacts
D
Position checking of spring condi-
tion
D
...
EXAMPLE OF TROUBLE 2 :
Spring operating mechanism does not
charge automatically
Cause of the presumed failure
Remedical measures
D
M.c.b. tripped ?
D
Supply voltage lacking ?
D
Motor defective ?
D
Relay defective ?
D
...
D
Switch the m.c.b. on
D
Secure the supply voltage
D
Replace the motor
D
Replace the relay
D
...
EXAMPLE OF TROUBLE 3 :
Incorrect contact in the operating mecha-
nism due to the corrosion
Cause of the presumed failure
Remedical measures
D
Heating m.c.b. tripped ?
D
Heating voltage lacking ?
D
Heating resistor defective ?
D
Mechanism housing not tight
D
...
D
Switch the m.c.b. on
D
Secure the heating voltage
D
Replace the heating plate
D
Check the housing seals, if neces-
sary replace them.
D
...
Continued on next page.
Содержание FKG1X
Страница 2: ......
Страница 7: ...GRID High Voltage Switchgear This page is intentionally blank...
Страница 13: ...GRID High Voltage Switchgear This page is intentionally blank...
Страница 17: ...GRID High Voltage Switchgear This page is intentionally blank...
Страница 21: ...GRID High Voltage Switchgear This page is intentionally blank...
Страница 75: ...This page is intentionally blank This page is intentionally blank...
Страница 191: ...GRID ALSTOM Grid SAS 130 rue L on Blum 69611 Villeurbanne France This page is intentionally blank...
Страница 197: ...GRID ALSTOM Grid SAS 130 rue L on Blum 69611 Villeurbanne France This page is intentionally blank...