GRID
Detail of maintenance operations of disconnector, earthing switch and (or)
starting disconnector
(where applicable)
General condition of
equipment
To be dealt with during the foreseen circuit--breaker interventions.
Condition of control
rod system
Inspection of the control rod system will be performed at the same time as the
foreseen circuit--breaker interventions.
Mechanical control
mechaism
Check condition of the mechanical control mechanism -- tightness of seals,
moving parts, protection of the various elements...
Tightening of
mountings
To be dealt with during the foreseen circuit--breaker interventions.
Relay operation
To be dealt with during the foreseen circuit--breaker interventions.
Pole insulating
supports
Check the condition of insulating supports ; these should be free from impact
marks, splintering, cracks, dust deposits, pollution etc...
Clean with a dry rag.
If anomalies are found on pole insulating supports, contact
ALSTOM Grid
S.A. Customer Service
.
Pole contacts
These contacts are inspected with the cover removed, the disconnector de--
energized and earthed ; this state is equallyvalid for the previous inspections.
Measurecontactresistancebetween thedisconnector’s input andoutput ter-
minals to appreciate how the condition of these contacts has evolved.
Inspect silver-plating of contact fingers and tube no patches of copper should
be visible. If this is not the case, contact
ALSTOM Grid S.A. Customer Ser-
vice
.
Operating times
Measure operating times of poles and auxiliary contacts as explained in sec-
tion entitled : “PRE-COMMISSIONING INSPECTIONS AND TESTS”.
If the values found are outside those given in the document “Acceptation Cri-
teria”, contact
ALSTOM Grid S.A. Customer Service
.
Measurement of con-
tact resistance
To be dealt with during the foreseen circuit--breaker interventions.
Replacing the earth-
ing switch
In case of an anomaly following a guaranteed maximum overcurrent, contact:
ALSTOM Grid S.A., Customer Service
, in order to envisage changing the
deteriorated parts.
Overhauling necessitates
de--energizing
the equipment.
Содержание FKG1X
Страница 2: ......
Страница 7: ...GRID High Voltage Switchgear This page is intentionally blank...
Страница 13: ...GRID High Voltage Switchgear This page is intentionally blank...
Страница 17: ...GRID High Voltage Switchgear This page is intentionally blank...
Страница 21: ...GRID High Voltage Switchgear This page is intentionally blank...
Страница 75: ...This page is intentionally blank This page is intentionally blank...
Страница 191: ...GRID ALSTOM Grid SAS 130 rue L on Blum 69611 Villeurbanne France This page is intentionally blank...
Страница 197: ...GRID ALSTOM Grid SAS 130 rue L on Blum 69611 Villeurbanne France This page is intentionally blank...