Maintenance operations of circuit --breaker
(20000 guaranteed mechanical cycles)
Guide
The table below is a guide of the operations to be carried out at each mainte-
nance stage :
MAINTENANCE VISITS
(1 or 2 times a year)
INSPECTION
(every 5 years)
OVERHAUL
(OPERATING TIME : 20 years)
OVERHAUL
(ELECTRICAL WEAR : see “Electrical wear limits”,
module S51--051)
OVERHAUL
(MECHANICAL OPERATIONS :
10 000 cycles)
REVISION
for the ventilation (FKG1XP--XV--XW)
(SERVICE LIFE:
≥
25,000 hours/fan)
` J J J J
Operation counter reading.
` J J
Overall inspection : appearance (corrosion, paint-
work, signs of overheating).
J J J J
Inspect the insulating envelopes of poles.
` J J J J
Check the condition of crank lever assembly (axles,
retaining, clips,...).
` J J J J
Check operation of permanent heating. Check condi-
tion of air vents.
` J J
J
Check SF
6
pressure, (if the circuit breaker is supplied
with a permanent pressure gauge).
`
It is advisable to perform at least 2 CO duty cycles per
year,
when apparatus are scarcely used
, in order
to check that circuit--breaker and associated control
circuits are working properly.
` J J J
Check SF
6
densimeter thresholds. Then adjust pres-
sure to its rated value.
` J J J
Measure operating times of poles and auxiliary con-
tacts, at rated voltage and pressure.
` J J J
Measure resistance of main contacts.
J J
J
Check tightening of parts not subjected to pressure
(frame -- deck -- cubicle).
∗
J J
J
Check tightening of low voltage terminals (
∗
6 months
after commissioning).
J J
J
Check relay operation.
J J
J
Check latch operation.
J J J J
Carry out operations at recommended duties and
rated voltage.
J
J
Change doors seals, sidepanelsseal and roofs seals.
Legend : (
J
Compulsory) (
`
Recommended)
Continued on next page.
Содержание FKG1X
Страница 2: ......
Страница 7: ...GRID High Voltage Switchgear This page is intentionally blank...
Страница 13: ...GRID High Voltage Switchgear This page is intentionally blank...
Страница 17: ...GRID High Voltage Switchgear This page is intentionally blank...
Страница 21: ...GRID High Voltage Switchgear This page is intentionally blank...
Страница 75: ...This page is intentionally blank This page is intentionally blank...
Страница 191: ...GRID ALSTOM Grid SAS 130 rue L on Blum 69611 Villeurbanne France This page is intentionally blank...
Страница 197: ...GRID ALSTOM Grid SAS 130 rue L on Blum 69611 Villeurbanne France This page is intentionally blank...