017-230-B4 Rev B
82
Table T —
Electrical Specifications
Parameter
Value
Battery Charger Current,
Amps
FXM 650: 10
FXM 1100/2000: 15.
Battery Charger Temperature
Compensation
8
-5 mV/°C/Cell (factory default), user adjustable from 0 to -6 mV/°C/Cell in increments of
0.5.
Battery type
Anderson Power mating part SB50 or equivalent.
Table U — Regulatory
Parameter
Value
Electrical Safety
UL 1778, CSA 107.3, EN 62040-1-2, EN60950-1.
Emission
FCC Part 15, Subpart B, Class A, CSPR22, EN55022 Level A.
Marks
C
CSA
US
, CE (230 Vac versions only).
Packaging
Designed to meet requirements for ISTA program.
7.
Efficiency is measured at an ambient temperature of 25°C, full resistive condition and nominal Line and Battery voltage.
8. With external battery temperature probe assembly. For FXM650-48(Q), charger compensation is disabled.
Table V — Boost/Buck/Line Transfer Thresholds
Parameter
Value
120 VAC Units
230 VAC Units
High Line Transfer
High Line Retransfer
175 VAC
162 VAC
325 VAC
303 VAC
Buck 2 Transfer
Buck 2 Retransfer
152 VAC
146 VAC
282 VAC
272 VAC
Buck 1 Transfer
Buck 1 Retransfer
134 VAC
128 VAC
250 VAC
236 VAC
Boost 1 Retransfer
Boost 1 Transfer
116 VAC
112 VAC
210 VAC
207 VAC
Boost 2 Retransfer
Boost 2 Transfer
102 VAC
98 VAC
180 VAC
176 VAC
Low Line Retransfer
Low Line Transfer
97 VAC
88 VAC
162 VAC
151 VAC