37
017-230-B4 Rev B
Table D — Parameters/ Default Settings
End minute of rush hour of time of day action period #2
00
Format setting of date display on LCD
YY-MM-DD
Line qualify time (sec)
3
Inverter off delay setting
(sec)
0
Number of weeks setting of periodical self-test
4
Day of the week setting of periodical self-test
Monday
Time of the day setting of periodical self-test
00:00:00
Battery low warning threshold setting: Standard charge mode (%)
40
Self test depth-of-discharge setting: Standard charge mode (%)
20
Temperature setting to turn on cooling fan (
°C)
55
Load shed timer1 duration
2:
00:00
Load shed timer2 duration
2:
00:00
Load shed timer3 duration
2:
00:00
Programmable dry contact #1 setting
On Batt
Programmable dry contact #2 setting
Low Batt
Programmable dry contact #3 setting
Low Batt
Programmable dry contact #4 setting
Timer 1
Programmable dry contact #5 setting
Alarms
Password setting
1111