Chapter 4 Parameter Index
40
Function
code
Parameter name
Setting range
Factory
setting
Modify
flag
Modbus
address
P9.16 AVR
function
0: Failure to actuate
1: Run all the time
2: Not act only during
deceleration
2 ×
0A10
P9.17
Overmodulation
action
0: Invalid
1: Valid
0 ×
0A11
P9.18
Droop control
(load
distribution)
0.00~10.00Hz 0.00Hz
○
0A12
P9.19
Output voltage
offset source
0: Digital setting
1: Terminal AI1
2: Terminal AI2
3: Terminal AI3 (reserve for
3004GB and below
models)
4: Pulse input
5: Communication setting
Maximum output voltage is
100%
Valid only in V / F separation
mode
0 ×
0A13
P9.20
Output voltage
offset
0.0%~100.0% 0.0%
○
0A14
P9.21
Oscillation
suppression
coefficient
0~100 0
○
0A15
PA: Motor Parameters
Function
code
Parameter name
Setting range
Factory
setting
Modify
flag
Modbus
address
PA.00 Motor
selection
0: Use motor 1
1: Use motor 2
0 ×
0B00
PA.01
Number of poles
of motor 1
2~56 4
×
0B01
PA.02
Rated power of
motor 1
0.4~999.9kW
Depend on
model
× 0B02
PA.03
Rated speed of
motor 1
0~24000r/min
○
0B03
PA.04
Rated current of
motor 1
0.1~999.9A ×
0B04
PA.05
No-load current
I0 of motor 1
0.1~999.9A ×
0B05
PA.06
Stator resistance
R1 of motor 1
0.001~65.000
Ω
○
0B06