Technical features and dimensions
3
INSTRUCTIONS FOR
INSTALLATION
3.1 GENERAL RECOMMENDATIONS
ATTENTION!
This
boiler must only be employed for its explicitly
intended use. Any other use must be considered
improper and therefore dangerous.
This
boiler is used to heat water to below boiling
temperature in atmospheric pressure.
ATTENTION!
These appliances are designed exclusively for
installation inside suitable technical compartments.
Before connecting the boiler, have professionally
authorised company:
a) Accurately washing all of the pipes in the system
to remove any residues or sediments could stop
the boiler form running e
ffi
ciently, even in terms
of health and hygiene.
b) Making sure the boiler is set up to operate with the
available type of fuel.
Th
e type of fuel is stated on the
packaging and technical characteristics plate.
c) Make sure that the chimne
y/fl
ue has an adequate
draught, that it is not choked, and that there are no
other exhausts for other appliances, unless the
fl
ue
is designed for multiple utilities, in accordance with
standard spe
cific
ations and requirements in force.
Only once this check has been carried out can the
fi
tting between boiler and chimne
y/fl
ue be set up.
ATTENTION!
In rooms with aggressive vapour or dust, the
appliance must operate independently of the air in
the room of installation!
ATTENTION!
The
appliance must be installed by an authorised
company possessing professional-technical
qua
lifi
cations in accordance with the law, who, under
his/her own responsibility, enforces the observance of
regulations according to the rules of good practice.
ATTENTION!
Assemble the appliance in observance of the minimum
required distances for installation and maintenance.
Th
e boiler must be connected to a heating system
compatibly with its spe
cific
ations and power.
3.2 REGULATIONS FOR INSTALLATION
Installation must be carried out by a
professionally authorised company
,
who is in charge of enforcing observance of all local and/or national
laws published in the
Offici
al Gazette, as well as all applicable technical
regulations.
3.3 PREVENTATIVE CHECKS AND
ADAPTATION OF THE SYSTEM
When the appliance is installed on existing systems, make sure that:
-
Th
e
fl
ue is suitable for condensation appliances, for the temperatures
of the combustion products, calculated and built in accordance with
regulations in force.
Th
at is it a straight as possible, water-tight and
insulated and does not have any obstructions or constrictions.
-
Th
e
fl
ue is equipped with an attachment to evacuate the condensation.
Th
e boiler room is equipped with a pipe for the evacuation of the
condensation produced by the boiler.
-
Th
e electrical system is built in accordance with spe
cific
regulations
and by professionally authorised company.
-
Th
e
flo
w rate, head and direction of
flo
w of the circulation pumps is
appropriate.
-
Th
e fuel feed line and any existing tanks are set up in accordance with
regulations in force.
-
Th
e expansion vessels ensure complete absorption of the dilation of
th
e fl
uid contained in the system.
- Slurry and build-up have been cleaned out of the system.
If it is possible to schedule the replacement, the system must be washed
preventively with alkaline dispersants.
Washing must be carried out four weeks prior to replacement, with a
system operating between 35°C - 40°C.
Attention! If the new boiler has been replaced in an old system without
having preventively washed it as described above, do not wash the sy-
stem, as any residues of the product in the circuit may
fi
ll the generator
with residues a
ft
er replacement.
It is advisable to contact a company specialised in water treatment.