Alpha CD18S/24S/30S - Commissioning
5
COMMISSIONING
When commissioning the boiler, ensure the Benchmark Checklist is completed.
5.1
FILL THE SYSTEM
1.
The boiler is fitted with an automatic air vent positioned on the pump (see Fig. 2). The vent is always open and has no
sealing cap.
2.
Open the central heating flow and return valves (slot in-line with valve) (see Fig. 13).
3.
Open the fill point valve on the filling loop until water is heard to flow. To aid venting, the boiler drain point (see Fig. 2) may
be opened until water flows out. Close the drain point as soon as water appears.
4.
To remove the air - Vent each radiator in turn, starting with the lowest in the system.
5.
It is important that the pump is properly vented to avoid it running dry and damaging its bearings. Unscrew and remove the cap
from the centre of the pump. Using a suitable screwdriver rotate the exposed spindle about half a turn, then replace the cap.
6.
Check the operation of the pressure relief valve (see Fig. 2) by turning the head anti-clockwise until it clicks. The click is
the valve lifting off its seat allowing water to escape from the system - check that this is actually happening.
7.
Continue to fill the system until the pressure gauge indicates 1.0 bar. Close the fill point valve and check the system for
water soundness, rectifying where necessary. Disconnect the filling loop from the mains supply.
Water may be released from the system by manually operating the drain point (see Fig. 2) until the system design
pressure is obtained. The system design pressure (cold) should be between 0.75 and 1.25 bar.
Refer to Sections 3.7 and 3.8. System volume, Flushing and Filling the system.
8.
Open the mains water inlet valve (see Fig. 13). Turn on all hot water taps and allow water to flow until no air is present.
Turn off taps.
9.
Ensure that the condensate trap has been filled with water. Refer to Section 4.5, paragraph 4.
5.2
BOILER CONTROLS - Fig. 22
Fig. 22
5.3
TEST FOR GAS SOUNDNESS AND PURGE THE SUPPLY
1.
With the boiler gas service cock closed (slot at right angles to valve). Pressure test the gas supply and inlet pipework
connection to the boiler gas service cock for soundness in accordance with BS 6891.
2.
Loosen the gas inlet pressure test point screw on the gas valve (see Fig. 24). Ensure the gas supply is on and open the
boiler service cock to purge in accordance with BS 6891.
3.
Retighten the test point screw and test for gas soundness. Close the boiler gas service cock.
5.4
INITIAL LIGHTING - Refer to Fig. 22
1.
Ensure that the gas and electrical supplies to the boiler are off and that the mains water inlet valve and the central heating
flow and return valves are open.
2.
Turn on the gas and electrical supplies to the boiler.
3.
Ensure all external controls are calling for heat.
If the optional clock is fitted, refer to the clock's User instructions, set the time and ensure the clock is in an 'on' mode.
4.
Set the central heating thermostat to maximum.
5.
Set the boiler selector switch to 'ON'. The boiler will now run in the central heating mode. The pump will start, the fan will
start and the main gas valve solenoid will open allowing the main burner to light.
Содержание Alpha CD18S
Страница 11: ...11 Alpha CD18S 24S 30S General Boiler Information Fig 9 External soakaway Fig 8 External gully ...
Страница 29: ...29 9 1 ILLUSTRATED WIRING DIAGRAM Alpha CD18S 24S 30S Wiring Diagrams 9 WIRING DIAGRAMS ...
Страница 30: ...30 Alpha CD18S 24S 30S Wiring Diagrams 9 2 FUNCTIONAL FLOW WIRING DIAGRAM ...
Страница 32: ...32 10 2 FAULT FINDING SOLUTIONS A to E Alpha CD18S 24S 30S Fault Finding ...
Страница 33: ...33 Alpha CD18S 24S 30S Fault Finding 10 3 FAULT FINDING SOLUTIONS F to K ...