15
4.7
EXTENDING THE FLUE - Fig. 19
Note:
The maximum horizontal flue assembly length must not exceed a length of 12 metres.
1.
When the flue length required is more than the maximum or less than the minimum stated in Section 4.6, paragraph 1,
refer to the table below.
Alpha CD18S/24S/30S - Installation
Fig. 18 - Rear flue
2.
Use the template (supplied with the boiler) to mark the required flue position and cut a 130 mm diameter hole for the flue
(use a 127 mm core drill). The size of the hole provides sufficient clearance for the clamps on the flue extension to pass
through the hole.
3.
Determine the overall flue length as described in Section 4.6, paragraph 2 to determine the number of Alpha CD 750/1000 mm
flue extensions required.
4.
Assemble the flue extensions together by locating the inner duct into the seal joint and secure each extension together
with the clamps supplied (three screws). Ensure that the clamps are positioned centrally over the joints.
Note:
If it is required to cut an extension,
DO NOT
cut the end of the inner duct that incorporates the seal joint. Ensure the
inner duct end without the seal joint is cut so that it is 15 mm longer than the outer duct.
5.
Adjust the telescopic section of the Easy-Flue to the required length and secure the Easy-Flue with the sealing tape
supplied. Fit the Easy-Flue to the extensions by locating the inner duct into the seal joint and secure with the clamp (three
screws), ensuring it is located centrally over the joint.
6.
Mark the end of the flue assembly 'TOP' where it is connected to the boiler,so that the 'TOP' of the flue terminal is aligned
with the 'TOP' at the boiler end of the flue assembly.
7.
Pass the complete flue assembly through the wall.
Flue Length
Up to maximum:-
Between:-
Between:-
Between:-
Less than:-
Rear Flue (B)
11.83 m
675 mm and 915 mm
520 mm and 675 mm
280 mm and 520 mm
280 mm
Side Flue (B + C)
11.77 m
615 mm and 855 mm
460 mm and 615 mm
220 mm and 460 mm
220 mm
Comments
Alpha CD 750 mm or 1000 mm flue extension
(Part No. 6.2000750 or 6.2001050) is required to
extend the range of telescopic flue.
Refer to Section 4.7 paragraph 2 for instructions
on how to extend the flue.
Note:
A 130 mm flue hole (127 mm core drill) is
required in the wall.
Within the standard Easy-Flue 1000 mm
(Part No. 6.20001000) telescopic range.
Use an Easy-Flue 1000 mm (Part No. 6.20001000)
and the terminal may protrude somewhat from the
outside wall.
Within standard Easy-Flue 500 mm
(Part No. 6.2000500) telescopic range.
Terminal may protrude somewhat from the outside
wall.
Содержание Alpha CD18S
Страница 11: ...11 Alpha CD18S 24S 30S General Boiler Information Fig 9 External soakaway Fig 8 External gully ...
Страница 29: ...29 9 1 ILLUSTRATED WIRING DIAGRAM Alpha CD18S 24S 30S Wiring Diagrams 9 WIRING DIAGRAMS ...
Страница 30: ...30 Alpha CD18S 24S 30S Wiring Diagrams 9 2 FUNCTIONAL FLOW WIRING DIAGRAM ...
Страница 32: ...32 10 2 FAULT FINDING SOLUTIONS A to E Alpha CD18S 24S 30S Fault Finding ...
Страница 33: ...33 Alpha CD18S 24S 30S Fault Finding 10 3 FAULT FINDING SOLUTIONS F to K ...