Installation and Start Up
Alpha Technologies
2.5
Starting and Testing the MBP System
TIP: If at any time the system does not perform as described, carry out trou-
bleshooting as described in Section 3.8, 3.9 and 5.2 of this manual.
Step 1: Turn on Line Power
1
Turn the MBP’s rotary switch to “Bypass.”
2
Verify the AC input & output and battery
circuit breakers on the UPS are off.
3
Turn on the upstream circuit breaker.
4
Verify the load is receiving power. If not,
perform troubleshooting.
Go to Step 2
Step 2: Turn on the UPS
1
Turn on the battery circuit breaker.
The LCD shows ”INVOFF”.
2
Turn the MBP rotary switch to “Transfer.”
Verify the load is receiving power. If not,
perform troubleshooting.
3
Turn on the AC input & output circuit
breaker.
Within 30 seconds the LCD display
changes to “LINE” showing line power is
within acceptable frequency and voltage
ranges. The UPS is operating on line
power.