2. Transport unit on the handcart.
Carrying the unit
"
Housing panels are dismantled.
1. Dismantle module box and carry it by the
support lugs to the place of installation.
2. Carry the unit horizontally wherever possible.
5.4 Installation
Installation room and space requirements
NOTE
Note and follow the local regulations and
standards regarding the installation room
and space requirements. The table shows
the regulations as per EN 378-1 relevant in
Germany.
Refrigerant
Limit value [kg/m³]
R 134a
0.25
R 404A
0.48
R 407C
0.31
R 410A
0.44
(
!
“Technical data/Scope of supply” on page 22).
Minimum room
volume =
<0I4/604,-1$3,?,3/1&$b56c
$$$$P/'/1$D,*:0$b56d'ec
NOTE
If several heat pumps of the same type are
installed only one heat pump need to be
1,50-$ /-1)$ ,33):-1"$ SI$ +0D04,*$ B0,1$ ?:'?+$ )I$
different types are installed, only the heat
pump with the largest refrigerant volume
-00.+$1)$(0$1,50-$/-1)$,33):-1"
"
Minimum
volume
corresponds
to
the
requirements for the refrigerant used.
"
Installation inside the building only.
"
Installation room is dry and frost-free.
"
Clearance dimensions are met (
!
“Installation
plans” on page 29).
"
QB0$ +:4I,30dE))4$ /+$ +:/1,(*0$ I)4$ /-+1,**,1/)-$ )I$
the unit:
–
level and horizontal
–
load-bearing capacity for the unit's weight
Aligning the unit
J
Align the unit horizontally and stably in the
installation site using the height-adjustable feet
and a spanner size SW 13. Adjustment range:
25 mm.