5
Subject to change without notice.
83054800bUK – Translation into English of the original German operating manual ait-deutschland GmbH Subject to change without notice.
Subject to change without notice.
83054800bUK – Translation into English of the original German operating manual ait-deutschland GmbH
Dimensioned drawing and installation plan for the
respective model.
WARNING!
Never switch on the unit if air ducts are
mounted on the unit.
Take precautions on the fan side to prevent
injuries caused by the rotating fan (air duct
outlet above ground level: weather louvre,
air duct outlet below ground level: rain
louvre, each not included in the accessories
supplied).
ATTENTION
It is not permitted to integrate the heat pump
in ventilation systems. Use of the cooled air for
cooling purposes is not permitted.
ATTENTION
The ambient air at the place in which the heat
pump is installed, as well as the air drawn in as a
heat source, must not contain any corrosive con-
stituents!
Constituents (such as ammonia, sulphur, chlorine,
salt, sewage gases, flue gases…) can cause damage
to the heat pump, which can result in complete
failure / irreparable total damage to the heat pump!
Can be installed near the coast.
CAUTION!
In the air outlet area the air temperature is
approx. 5° K below the ambient temperature.
Under certain climatic conditions an ice layer
can therefore form in the air outlet area.
Install the heat pump so that the air blower
does not discharge into footpath areas.
Customer service
For technical information please contact a qualified installer
or the manufacturer's local partner.
SERVICE ADDRESSES
For a current list and additional partners of the
manufacturer, please visit
DE: www.alpha-innotec.de
EU: www.alpha-innotec.eu
Warranty/Guarantee
For warranty and guarantee conditions, please refer to your
purchase documents.
NOTE.
Please contact your dealer about all matters
concerning warranties and guarantees.
Disposal
When decommissioning the old unit, always comply with
local applicable laws, directives and standards concerning
the recovery, recycling and disposal of materials and
components of cooling units.
“Dismantling”.