Care of the unit

You can use a damp cloth and standard cleaning products to 
clean the outer surfaces of the unit.

Do not use cleaning or care products that contain abrasives, 
acids and/or chlorine. Such products would irreparably 
damage the surfaces and could also cause technical damage 
to the unit.

Maintenance of the unit

The cooling circuit of the heat pump does not require any 
regular technical maintenance.

According to EU regulation (EC) 842/2006, certain heat 
pumps must be checked for leakage and a log book of the 
inspections must be kept!

The criteria for whether or not it is necessary to check 
for leakage and keep a log book are the hermetic tightness 
of the refrigerating circuit (hermetically sealed system) and 
the refrigerant capacity of the heat pump! Heat pumps with 
refrigerant capacity < 3 kg do not require a log book. For 
all other heat pumps, the log book is supplied with the heat 
pump.

  Log book for heat pumps, “Information on use of 

the log book” section.

The components of the heating circuit and the heat source 
(valves, expansion vessels, circulation pumps, filters, dirt 
traps) should be checked and cleaned as necessary, but 
at least by qualified personnel (heating or cooling system 
fitters).

It is best to sign a maintenance agreement with a suitably 
competent company. It will arrange for the necessary main-
tenance work at regular intervals.

 ATTENTION

 

Check regularly to ensure that the condensate can 
drain out of the unit freely, without obstruction. To 
this end, check the condensate pan in the unit and 
the condensate drain regularly for dirt / blockages 
and clean as necessary.

CLEANING AND FLUSHING UNIT COMPONENTS

 CAUTION!

 

Unit components may be cleaned and 
flushed only by customer service personnel 
authorised by the manufacturer. Only use 
liquids recommended by the manufacturer.

 

After flushing the condenser with chemical 
cleaning agent, any residues must be neu-
tralised and the system flushed intensively 
with water.  Always note and follow the tech-
nical data of the respective heat exchanger 
manufacturer.

Malfunctions

In the event of a fault, you can read out the cause of the 
fault from the diagnostic program of the heating and heat 
pump controller.

  Operating manual of the heating and heat pump 

controller.

 CAUTION

 

Only customer service personnel authorised 
by the manufacturer may carry out service 
and repair work on the components of the 
unit.

  “Customer service” overview.

Note that no fault is displayed if the safety temperature 
limiter on the electric heating element has triggered 
(depending on model).

 “Commissioning”, “Safety temperature limiter” 

section.

Содержание LW 160H/V

Страница 1: ...t to technical change without notice 83054800bUK Translation into English of the original German operating manual ait deutschland GmbH HEAT PUMPS Operating Manual Indoor installation AIR WATER UK LW 1...

Страница 2: ...e parameters for the respective model This operating manual is intended only for persons assigned to work on or with the unit Treat all its constituent parts confidentially They are protected by copyr...

Страница 3: ...CIRCULATION PUMP 17 BUFFER TANK 17 WATER HEATING 17 HOT WATER TANK 17 ELECTRICAL CONNECTION WORK 18 FLUSHING FILLING ANDVENTING THE SYSTEM 19 Water quality of the fill and make up water toVDI 2035 19...

Страница 4: ...to current state of the art standards all relevant DIN VDE regulations and all relevant safety regulations Every person who carries out work on the unit must have read and understood the operating man...

Страница 5: ...wage gases flue gases can cause damage to the heat pump which can result in complete failure irreparable total damage to the heat pump Can be installed near the coast CAUTION In the air outlet area th...

Страница 6: ...ng is mandatory for air water heat pumps Heat metering for brine water and water water heat pumps only has to be installed for a flow temperature 35 C The heat metering must record the total thermal e...

Страница 7: ...checked and cleaned as necessary but at least by qualified personnel heating or cooling system fitters It is best to sign a maintenance agreement with a suitably competent company It will arrange for...

Страница 8: ...UP 25 85 PWM What to do first Check the delivery for outwardly visible signs of damage Check to make sure that the delivery is complete Any defects or incorrect deliveries must be reported immediatel...

Страница 9: ...410A 0 44 kg m Technical data scope of supply overview General unit data section Minimum room volume Refrigerant capacity kg Limit value kg m NOTE If several heat pumps of the same type are installed...

Страница 10: ...nd secure it against slipping Put down the unit at the place of installation Make sure that the unit s baseframe is in full contact with the surface of the floor Remove the tube handles If the electri...

Страница 11: ...wer facing panel on the fan side and remove it from the unit To do this undo the quick release screws Turn through 90 to the left 1 Quick release screws 2 Lower facing panel Pull the lower facing pane...

Страница 12: ...rods and re attach all facing panels to the unit INSTALLATION Place the unit on a stable solid and horizontal preferably structural sound insulated surface Make sure that the floor is designed for the...

Страница 13: ...by bricking around the penetration NOTE Install wall penetrations 1 cm above the finished external fa ade 1 Outside of the building masonry 2 Inert the wall penetration in the masonry 1 cm above the f...

Страница 14: ...tion the air duct on the respective air opening of the air inlet side At the air inlet side of the heat pump hook 4 of the tension springs supplied in the holes provided for this purpose Hook the tens...

Страница 15: ...FRAME TRIM Screw the frame trim onto the wall penetration on the air inlet and air outlet side NOTE The frame trim does not fulfil any technical function it is merely for establishing a visually attr...

Страница 16: ...n the unit For details on how to position the connections refer to the dimensioned drawing for the respective unit model 8 x NOTE Attach the weather louvre if the wall penetration is above ground leve...

Страница 17: ...he hot water tank must be dimensioned so that the heating capacity of the heat pump is transferred with minimum temperature drop We offer a variety of hot water tanks for you to choose from They are o...

Страница 18: ...at least 3 mm contact spacing to IEC 60947 2 Residual current circuit breaker type A is sufficient Technical data scope of supply overview Electrics section NOTE In units with integrated electric heat...

Страница 19: ...limescale deposits form on the heat transfer surfaces of the heating Efficiency falls and energy costs rise A rule of thumb is that 1 millimetre of limescale deposit causes an efficiency loss of 10 In...

Страница 20: ...e if the system is operated with salty i e softened water Even drinking water softened beforehand contains dissolved corrosive salts which due to the use of different materials in the heating system a...

Страница 21: ...at the rear of the control unit which are used to hook the control unit onto the front panel of the unit Hook the control unit s hooks into the openings of the front panel either in the upper or lower...

Страница 22: ...delivered condition so that the control unit can be inserted in the upper openings of the front panel If the control unit has been inserted in the lower openings of the front panel you must remove the...

Страница 23: ...ual the electrical installation work has been completed properly The power supply for the heat pump must be equipped with an all pole automatic circuit breaker with at least 3 mm contact spacing to IE...

Страница 24: ...low valve menu item is pre set to No The overflow valve setting function is deactivated Control signal UWP is the display of the currently re quested pump delivery in Actual flow is the current flow m...

Страница 25: ...us dem W rmepumpenregler ausgelesen werden Volumenstrom Spreizung 2000 1 2000 2 2000 3 2000 4 2000 5 2000 6 2000 7 2000 8 2000 9 0 5 10 15 20 25 1 2 3 4 5 6 7 8 9 Heizleistung in kW Spreizung in K Ein...

Страница 26: ...l pressure m h 4400 Maximum external pressure Pa 25 Heating circuit Flow rate pipe sizing l h 2000 Free compression Pressure loss Flow rate bar bar l h 0 513 0 157 2000 Control range circulating pump...

Страница 27: ...35 C 50 C 65 C 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 0 0 5 1 1 5 2 2 5 3 m h p bar Bezeichnung Seite 1 D ring 05 09 2014 823233a Datei 823233a Leistungs Druckverlustkurven LW 160H AV xls nd M Erste...

Страница 28: ...a innotec de D 95359 Kasendorf Industriestra e 3 Alpha InnoTec GmbH Schutzvermerk nach DIN 34 beachten Ers d Ers f A B C D E F 4 3 2 1 Benennung Ma bild LW 140 180 LW 819355 a Zust nderungstext PEP 02...

Страница 29: ...ories Rain louvre 1045x1050 KA Condensate drain G Detail of installation in the light well 7 provided on site by the customer Light well with water outlet min free cross section 0 75 m Tipping dimensi...

Страница 30: ...Accessories Air duct bend 900x1050x1450 LR Air direction 5 Installation above ground level Accessories Weather louvre 1045x1050 LRR Air direction of units with fan right hand side LRL Air direction of...

Страница 31: ...units with fan right hand side LRL Air direction of units with fan left hand side BS Operating side 6 Installation in the light well Accessories Rain louvre 1045x1050 FWS Finished wall thickness KA C...

Страница 32: ...ground level Accessories Weather louvre 1045x1050 LRR Air direction of units with fan right hand side LRL Air direction of units with fan left hand side BS Operating side FWS Finished wall thickness...

Страница 33: ...ntactor electric heating element hot water or buffer tank X3 2 IN2 FP1 IN4 AOUT2 External return sensor A3 A3 A1 MIS TRL ext MZ1 MIS BUP X3 1 Out6 HUP IN5 STB FBH Safety temperature limiter for underf...

Страница 34: ...y heating Compressor 1 Operating materials Line reactors M1 Q1 ZW1 Terminal in switch box heat pump ws 3 ZW1 PE 2 3 VD1 5 br ge Q6 sw 3 N PE 400V 50Hz E22 VENT sw 1L1 1L2 1L3 1N PE power supply additi...

Страница 35: ...ion Q6 K50 K22 K23 Contactor for auxiliary heating Defrosting valve L N PE power supply controller K50 EXL High pressure switch 230VAC Q1 1 N PE 230V 50Hz Controller board cooling circuit Operating ma...

Страница 36: ...EVI UK817395 TVL Suction sensor condenser TWE HD K50 R4 Operating materials B10 K50 Flow sensor Controller board cooling circuit R2 Heat source input sensor Function EVI 05 03 2014 3 Achim Pfleger 3...

Страница 37: ...R6 A A GND LIN bus K30 12V LIN Modbus B K30 GND LIN 12V M6 Return sensor Function Heating pump energy efficiency TRL Controller board Attention I max 6A 230VAC Operating materials UK817395 HUP Legend...

Страница 38: ...8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Bl von Anz Name Datum Zustand Blatt Nr Bearb Datum nderung Subject to change without notice 83054800bUK Translation into English of the...

Страница 39: ...LW 160H V 100 623 2006 42 EG LW 180H A 100 540 100 542 100 543 100 544 100 545 100 546 LW 180A LW 251A LW 310A LW 100H A confirms that the following designated device s as designed and marketed by us...

Страница 40: ...DE ait deutschland GmbH Industriestrasse 3 D 95359 Kasendorf E mail info alpha innotec com www alpha innotec com...

Отзывы: