$0/%&/4"5&%*4$)"3(&
The condensate from the air must be discharged frost-
free via a condensate pipe with a minimum diameter of
50 mm. For underlying surfaces that are permeable to
water, it is sufficient to insert the condensate pipe verti-
cally at least 90 cm into the ground. If the condensate is
discharged into drainage or sewage systems, install frost-
free with gradient.
Discharge of the condensate into the sewage system is
permitted only via a funnel siphon, which must be acces-
sible at all times.
-8w-8w-8)w
1 Hot water inflow
(return flow) connection
2 Hot water outflow
(forward flow) connection
3 Condensate water hose
-8"w5)306()-8w
1 Hot water inflow
(return flow) connection
2 Hot water outflow
(forward flow) connection
3 Condensate water hose
Install the condensate water hose in the unit so that
there is no contact with refrigerant pipes…
Make sure that frost-free condensate discharge is
ensured…
Installation plan for respective unit model.
“Heat pump guide”.
Seal empty pipes on unit side.