18
Current transformer clipping
Clipping the current transformers onto the service
side cable:
1. Match the labelled CTs with their corresponding
labelled service supply cable.
2. Confirm correct polarity of the CT by ensuring
the arrow on the CT head matches the current
flow direction on the service supply cable.
3. Clip CT over service supply cable.
Important:
Make sure that each CT is clipped
to the corresponding unit.
Important:
The CT must be connected on the service
side of the point of connection of solar
supply, as per diagram.
* The point of connection of the solar may appear
different in your case depending on the Project SLD.
In any case, the CT must be on the line side of the
point of connection of the solar supply.
POLARITY
OF CURRENT
TRANSFORMERS
DOWN TOWARDS
LOAD
1(L1)
1(L1)
1(L2)
FROM
SOLAR
TO UNIT
SERVICE
SIDE
LOAD
SIDE