# NAME
DESCRIPTION
7 CLOSE
Momentary or continuous signal. On/
Off mode set by Switch #1
WITH SWITCH 1 OFF:
Once activated the gate will close fully.
Activation while the gate is opening has no effect. Continuous
signal required to move the gate when in the alarm mode.
WITH SWITCH 1 ON:
Gate does not respond to pushbutton
input when in the normal mode. Continuous signal required to
move the gate when in the alarm mode.
8 STOP
Momentary or continuous signal.
Overrides all other signals. Once activated, the gate will
immediately stop and await a new command. If the STOP
input is continuously activated, the gate will not move.
9 OPEN PHOTO
Momentary or continuous signal.
This input is active only when referenced to the opening
direction, it has no effect on the gate when closing or about to
close. If activated when the gate is opening the gate will stop,
pause and reverse in the close direction for 1/2 second
(approx. 2 inches) and stop. Continuous activation will
prevent the gate from moving in the open direction. When the
input is removed normal operation is resumed. This input is
intended for photoelectric eye systems and other non-contact
devices as appropriate. Connect here and to terminal #16
COMMON. Multiple devices may be connected in parallel.
10 CLOSE PHOTO Momentary or continuous signal.
This input is active only when referenced to the closing
direction, it has no effect on the gate when opening or about to
open. If activated when the gate is closing the gate will stop,
pause and reverse in the open direction for 1/2 second
(approx. 2 inches) and stop. Continuous activation will
prevent the gate from moving in the close direction. When the
input is removed normal operation is resumed. If the Timer-
To-Close function initiated the close movement and Switch S2
(Re-close) is ON, the gate will automatically re-close from a
partially closed position after the input to Close Photo is
removed. Continuous activation while the gate is open will
prevent the Timer-To-Close function (if enabled) from
automatically closing the gate. This input is intended for
photoelectric eye systems and other non-contact devices as
appropriate. Connect here and to terminal #16 COMMON.
Multiple devices may be connected in parallel.
11 REVERSE
Momentary or continuous signal.
This input is active only when the gate is closing or when it’s
fully open and the Close Timer is operative. All stand-alone
vehicle detectors, photo-eyes and active edges should be
connected here and to terminals #16 COMMON. Multiple
devices may be connected in parallel.
# NAME
DESCRIPTION
12 OPEN EDGE
Momentary or continuous signal.
This input is active only when referenced to the opening direction,
it has no effect on the gate when closing or about to close. If
activated when the gate is opening the gate will stop, pause and
reverse in the close direction for 1/2 second (approx. 2 inches) and
stop. Continuous activation will prevent the gate from moving in the
open direction. If a second activation occurs before the limit switch
is activated the gate will stop and a require a renewed, intended
input to move in the open direction and before an automatic
activation device (timer, etc.) will operate. This input is intended for
Electric Gate Edge systems and other minimum-contact devices as
appropriate. Connect here and to terminal #16 COMMON.
Multiple devices may be connected in parallel.
13 CLOSE EDGE
Momentary or continuous signal.
This input is active only when referenced to the closing direction, it
has no effect on the gate when opening or about to open. If
activated when the gate is closing the gate will stop, pause and
reverse in the open direction for 1/2 second (approx. 2 inches) and
stop. Continuous activation will prevent the gate from moving in
the close direction. Continuous activation while the gate is open
will prevent the Timer-To-Close function (if enabled) from
automatically closing the gate. If a second activation occurs before
the limit switch is activated the gate will stop and a require a
renewed, intended input to move in the close direction and before
an automatic activation device (timer, etc.) will operate. This input
is intended for Electric Gate Edge systems and other minimum-
contact devices as appropriate. Connect here and to terminal #16
COMMON. Multiple devices may be connected in parallel.
14 MASTER OPEN Momentary or continuous signal. Master
(output configuration).
This terminal is used to coordinate two independent systems (two
control box/mechanical unit combinations controlling separate gate
leaves). Connects to terminal #6 (OPEN) in the companion control
box and controls the direction of movement in the companion box
(Switch S3 ON).
15 MASTER CLOSE Momentary or continuous signal. Master
(output configuration).
This terminal is used to coordinate two independent systems
controlling separate gate leaves. Connects to terminal #7
(CLOSE) in the companion control box and controls the direction of
movement in the companion box (Switch S3 ON).
16 COMMON
Common connection for low voltage
signal inputs, terminals 3 through 15.
TERMINAL STRIP REFERENCE CHART
D
: STARTING THE OPERATOR