MASTER/SLAVE CONFIGURATION 

 

Switch S3 controls the Master/Slave Terminals (#14 & 15) 
configuration setting.  The setting is used when two control boards 
(boxes) are used in conjunction with two mechanical units.   
 
With Switch S3 in the ON position terminals # 6 & 7 (OPEN and 
CLOSE inputs) are in the Slave (input) mode and could be coupled to 
and would be controlled by a Master control board (box).  In the Slave 
mode the Switch S1 and S2 must be OFF. 

 

CHECKING THE INDICATOR LIGHTS 

 
There are 16 indicator lights on the control board of the LPX1000 
operator.  See Figure 22.  These lights are used to verify proper 
operation of the LPX1000. 

 
 

TURN ON THE MAIN POWER SWITCH

 

 

Remove the white high voltage connector from the control board. 

• 

Turn all 3 digit switches ON for the test mode. 

• 

Note that the “POWER” lamp is lighted.  This indicates that power 
is applied to the control board and the power supply is functioning 

• 

Connect one end of a short piece of wire (not supplied) to terminal 
#16 (COMMON). 

• 

With the other end of this wire, (make sure that this loose end is free 
of insulation), touch the following terminals and observe the noted 
response of the lamps. 

 

1. 

Manually activate the Close Limit Switch:  Close Limit Switch 
light is ON. 

2. 

Manually activate the Open Limit Switch:  Open Limit Switch 
light is ON. 

3. 

Connect to Terminal #4, Radio Open.:  Radio Open light is ON, 
Motor Open light is ON. 

4. 

Remove wire from Terminal #4, Radio Open.  Radio Open light 
goes OUT, Motor Open light stays ON. 

5. 

Connect to Terminal #8, Stop :  Both Motor Open and Motor 
Close lights are momentarily ON, then both Motor Open and 
Motor Close lights go OUT.   The Stop Pushbutton light is ON 
as long as the wire is held on the terminal and the goes OUT 
when the wire is removed. 

6. 

Connect to Terminal #7, Close.:  Observe that the Motor Close 
light comes ON and the Close Pushbutton light is ON.  Remove 
the wire from terminal #7 and observe that the Close Pushbutton 
light goes OUT and the Motor Close light stays ON. 

7. 

Connect to Terminal #11, Reversing Loop,:  Observe that both 
Motor lights are ON momentarily and then the Motor Close light 
goes OUT and the Motor Open light stays ON.  

8. 

Connect to Terminal #8, Stop,:  Same as above, Sequence 5. 

9. 

Connect to Terminal #3, Alternate:  Alternate light is ON, Motor 
Close light is ON.  Remove wire and note that the Alternate light 
goes OUT but the Motor Close light stays ON. 

10. 

Connect to Terminal #3, Alternate again:  Note that the Alternate 

light comes ON, that the Motor Close light goes OUT and that 
the Motor Open light comes ON.  

11. 

Connect to Terminal #6, Open:  Observe that the Motor Open 
light comes ON and the Open Pushbutton light is ON.  Remove 
the wire from terminal #6 and observe that the Open Pushbutton 
light goes OUT and  the Motor Open light stays ON. 

12. 

Connect to Terminal #9, Open Non-contact Sensor: Note that the 
Open Non-contact Sensor light comes on & remains on until the 
connection is removed.  Observe that the both Motor Open and 
Motor Close lights are momentarily ON, then the Motor Open 
light goes out and the Motor Close light stays on for 
approximately  1 second then goes out. 

13. 

Connect to Terminal #6, Open: Same as above, Sequence #11. 

14. 

Connect to Terminal #12, Open Contact Sensor: Note that the 
Open Contact Sensor light comes on & remains on until the 
connection is removed.  Observe that the both Motor Open and 
Motor Close lights are momentarily ON, then the Motor Open 
light goes out and the Motor Close light stays on for 
approximately  1 second then goes out. 

15. 

Connect to Terminal #7, Close:  Same as above Sequence #6. 

16. 

Connect to Terminal #10, Close Non-contact Sensor: Note that 
the Close Non-contact Sensor light comes on & remains on until 
the connection is removed.  Observe that the both Motor Open 
and Motor Close lights are momentarily ON, then the Motor 
Close light goes out and the Motor Open light stays on for 
approximately  1 second then goes out. 

17. 

Connect to Terminal #7, Close:  Same as above Sequence 
#6.Connect to Terminal #13, Close Contact Sensor: Note that the 

110127 

Figure 22:  Indicator Lights 

INDICATOR LAMPS

D: STARTING THE OPERATOR  

15 

Содержание LEADER PLUS LPX1000 Series

Страница 1: ...ehicular gate operators READ THIS MANUAL CAREFULLY BEFORE INSTALLATION OR USE SAVE THESE INSTRUCTIONS Serial Date Installed Your Dealer PROVEN CGA2K TECHNOLOGY INSTALLATION AND OWNER S MANUAL LEADER P...

Страница 2: ...ou and your equipment Pay close attention to these boxes as you follow the manual WARNING Indicates a MECHANICAL hazard of INJURY OR DEATH Gives instructions to avoid the hazard CAUTION Indicates a ME...

Страница 3: ...00 control panel provides independent connections for Open and Close non contact photoelectric and contact edge sensors In this way a photoelectric sensor could be utilized to guard the gate area when...

Страница 4: ...CAN BE MINIMIZED BY INSTALLING A MESH SCREEN ON THE GATE It is strongly recommended that the entire gate and adjacent fence area the gate covers when open be meshed or guarded such that a handhold or...

Страница 5: ...RED POWER LIGHT IS NOT LIGHTED HIGH VOLTAGE AC IS STILL PRESENT NEVER LEAVE THE INSTALLATION WITH THE HANDY BOX OR OUTER COVERS REMOVED ALWAYS TURN OFF THE POWER BEFORE ATTEMPTING SERVICE OF EITHER T...

Страница 6: ...ng adjustment to prevent one operator from overloading the other The electrical hookup is made in the junction box located in the left front corner of the frame see Figure 7 Page 7 For conduit placeme...

Страница 7: ...o one detector See Figure 8 above Two different types of installations will usually be encountered 1 If the driveway material is already in place saw cuts will be needed to accommodate the loop wires...

Страница 8: ...INSULATED WIRE WIRE SIZE SHOULD BE 16zGA STRANDED OR LARGER C INSTALLING THE OPERATOR TOOLS REQUIRED The following tools and materials are required for proper installation of the operator 1 Two 3 4 wr...

Страница 9: ...purpose Run flexible conduit from the point where the conduit exits the pad and attach it to the bottom of the right junction box at the front of the frame Review Figure 5 Page 6 If the hook up exits...

Страница 10: ...e operator side wall The actual loop is installed in the concrete or asphalt surface in accordance with the manufacturer s instructions and the information outlined earlier in this manual see Page 7 C...

Страница 11: ...now complete Connect one of the two wires for the relay to terminal 4 RADIO OPEN or terminal 3 ALTERNATE depending on the function desired see descriptions on the chart on page 17 and 18 and the othe...

Страница 12: ...nd facing outwards if the operator is on the right side of the gate it s a right hand installation If the operator is on the left side of the gate it s a left hand installation The operator is shipped...

Страница 13: ...lug it into the connector labeled LEFT HAND Locate the 3 position limit switch wire harness connector midway down on the right side of the controller board Switch it to the position labeled LEFT HAND...

Страница 14: ...nuous signal required to move the gate when in the alarm mode SWITCH 1 ON Gate does not respond to pushbutton input when in the normal mode Continuous signal required to move the gate when in the alar...

Страница 15: ...he Motor Close light stays ON 7 Connect to Terminal 11 Reversing Loop Observe that both Motor lights are ON momentarily and then the Motor Close light goes OUT and the Motor Open light stays ON 8 Conn...

Страница 16: ...re the power to the operator Restart the gate and give the leading edge a firm blow with the heal of your palm Don t stand directly in the gate s path while testing the Overload Force The obstruction...

Страница 17: ...nal for most HOLD OPEN functions Direct input to control system independent of the Loop Sockets Once activated the gate will open fully Activation while the gate is closing will cause it to re open Co...

Страница 18: ...ld be connected here and to terminals 16 COMMON Multiple devices may be connected in parallel NAME DESCRIPTION 12 OPEN EDGE Momentary or continuous signal This input is active only when referenced to...

Страница 19: ...IO OPEN ALTERNATE 16 15 13 14 12 9 10 7 8 5 6 3 4 2 1 24 VAC 24 VAC YEL YEL YEL YEL SOLENOID OPEN LIMIT RH CLOSED LIMIT RH WHT YEL RED LIMIT WIRE CONNECTIONS WHT COM COMMON RED YEL NO TRANSFORMER YEL...

Страница 20: ...and observe that the REVERSING LOOP light comes ON the operator control board and the gate reopens 2 FREE EXIT VEHICLE DETECTOR Pre test Test the vehicle detector independently using the presence lamp...

Страница 21: ...e or other need to move the gate manually without disconnecting the operator chain Take off the operator cover by first removing any lock attached to the lock tab on the operator front then lift the c...

Страница 22: ...ers for exposed rollers Each safety feature is a separate component in your gate system Read and follow all instructions for each of the components of your unique system Ensure that all instructions f...

Страница 23: ...hanical problems on the gate and gate hardware before installing the gate operator Have a qualified service technician make repairs to the gate and gate hardware AVOID ENTRAPMENT Stay away from the pa...

Страница 24: ...from the date of purchase for multi family and commercial use To obtain service contact your dealer To obtain service under this warranty the buyer must obtain authorization instructions for the retu...

Отзывы: