time.SWITCH SELECTABLE OPTIONS - Make sure the selectable
option on switch #3 is set in the ON position for the primary operator
and the OFF position for the secondary operator. Set the primary
operator’s other two switches to the desired position according to the
functions required. The settings of the secondary operator’s other
switches must be OFF.
When properly adjusted, the two operators will perform as if they were a
true Master/Slave installation. If the motor overload circuit in one
operator should respond to an obstruction not encountered by the other,
the gates will temporarily get out of sync. Synchronization will be
restored after the next input command cycle.
# NAME
DESCRIPTION
1 24 VAC
Provides maximum 10 VA auxiliary
power for accessories.
2 24 VAC
Provides maximum 10 VA auxiliary
power for accessories.
3 ALTERNATE
Momentary input, must be released
and re-entered to be recognized.
This input is used for “COMMAND OPEN/COMMAND CLOSE”
applications. The 1st signal will cause the gate to begin opening.
A 2nd signal received during the open cycle will stop the gate
immediately. A 3rd signal will close the gate. Connect
appropriate access control devices to this terminal and #16
COMMON. Disable the Close Timer (rotate pot fully counter-
clockwise).
4 RADIO OPEN
Momentary input, must be released
and re-entered to be recognized.
Once activated the gate will open fully. Activation while the gate is
closing will cause it to re-open.
5 FREE EXIT
Momentary or continuous input.
Preferred terminal for most HOLD
OPEN functions. Direct input to control
system, independent of the Loop
Sockets.
Once activated the gate will open fully. Activation while the gate is
closing will cause it to re-open. Continuous activation while the
gate is open will prevent the Timer-To-Close function from
automatically closing the gate.
6 OPEN
Momentary or continuous signal. On/
Off mode set by Switch #1
WITH SWITCH 1 ON:
Once activated the gate will open fully.
Activation while the gate is closing will cause it to re-open.
Continuous activation while the gate is open will prevent the
Timer-To-Close function from automatically closing the gate.
Continuous signal required to move the gate when in the alarm
mode.
WITH SWITCH 1 OFF:
Gate does not respond to
pushbutton input when in the normal mode. Continuous signal
required to move the gate when in the alarm mode.
TERMINAL STRIP REFERENCE CHART
CGA2K™
TECHNOLOGY
# NAME
DESCRIPTION
A FREE EXIT
LOOP
Continuous Signal, connected directly to
the loop socket block. Connect one end
of the free exit loop wire here, the other
end connects to Terminal B.
B FREE EXIT
LOOP
Continuous Signal, connected directly to
the loop socket block. Connect one end
of the free exit loop wire here, the other
end connects to Terminal A.
C REVERSING
LOOP
Continuous Signal, connected directly to
the loop socket block. Connect one end
of the reversing loop wire here, the other
end connects to Terminal D.
D REVERSING
LOOP
Continuous Signal, connected directly to
the loop socket block. Connect one end
of the reversing loop wire here, the other
end connects to Terminal C.
TERMINAL STRIP REFERENCE CHART
PROVEN
D: STARTING THE OPERATOR
17
Terminal Strip Reference Chart continued on next page