ELECTRICAL POWER REQUIREMENTS
The GS6000 can be ordered for 115 Volts AC (VAC) or 230 VAC
operation. The AWG wire size for the electrical service depends on
the distance of the operator from the breaker panel. Refer to Table 1
to determine the correct wire size.
The DISTANCE column is the ideal distance from the breaker panel
to the operator for a given wire size and voltage.
NOTE! FOR A BI-PARTING INSTALLATION, THERE
WILL BE TWO OPERATOR UNITS OPERATING AT THE
SAME TIME. IF THESE WILL BE POWERED FROM THE
SAME SUPPLY IT WILL BE NECESSARY TO REDUCE THE
LENGTHS IN TABLE 1 BY A FACTOR OF TWO.
Class 2 low voltage wiring from external controls such as a key pad,
card reader, telephone entry device, etc. must be brought to the
GS6000 by a separate conduit from the 115 VAC electrical hook up
conduit. Low voltage control wires MUST NEVER be routed in the
same conduit as the HIGH VOLTAGE power wires.
Note!
If a wire set (connections between Master Open and
Master Close (Primary/Secondary operation terminals) is to
routed between a set of GS6000 operators for bi-parting
operation these wires ARE LOW VOLTAGE WIRES AND
MUST BE ROUTED IN A LOW VOLTAGE CONDUIT
TO THE CONTROL BOX.
OTHER VOLTAGES AND 3 PHASE SYSTEMS.
The GS6000 can operate at other voltages or on three (3) phase
systems. To operate at 440 VAC it will be necessary to install an
external step down transformer. The transformer should be located
in a separate electrical box and protected by suitable circuit breaker
and/or fusing. A 440 Volt rated switch should also be installed.
Follow local electrical codes or the National Electrical Code. The
transformer selected should be UL LISTED and be rated for a
minimum 600 Volt-Amperes (Watts).
IF TWO OPERATORS ARE TO BE USED FOR A BI-PARTING
GATE SYSTEM, THEN A 1000 VOLT-AMPERE/WATT
TRANSFORMER MUST BE USED.
Operating from a three (3) phase line will require the use of a 230
VAC rated GS6000, CHECK THE OPERATOR PRODUCT
LABEL!!! The GS6000 (rated for 230 VAC) may be operated from a
230 Volt "Delta" or "Y" line. In either case, ONLY one "leg" of the
three phase line will be used. The unbalance of the line will be
minimal since the full rate current of the GS6000 at 230 VAC is only
2.2 amperes. (4.4 Amperes for a bi-parting system.) Connect any
two wires of the three phase system to the 230 VAC GS6000. Tape
the third wire carefully so that it does not short to any other object.
(The "Y" system will have 4 wires, one of which will be the
"common". Make sure the common is NOT selected as one of the
wires connected to the GS6000.) It is always best to also pull a
ground wire from the electrical service box to the GS6000 to ensure
the frame is securely affixed to GROUND.
SERVICE CONDUIT
For new installations the conduit for the High Voltage may be
brought to a junction box near where the GS6000 will be located or it
may be brought directly to the GS6000’s Control Box.
WARNING!
AVOID ELECTROCUTION:
DO NOT ROUTE LOW VOLTAGE WIRES IN SAME
CONDUIT AS HIGH VOLTAGE WIRES. FOLLOW
ALL LOCAL ELECTRICAL CODES OR THE
NATIONAL ELECTRICAL CODE.
B:
PREPARING THE SITE
GS6000 Operator
Wood Pallet
with 4 lag bolts
Instruction Kit
Instruction Manual
Warning signs
Swing Arm Kit
Swing Arm
Crank Arm
Crank Arm Extension
Swing Gate Fittings
Swing Arm Bracket
Swing Arm Padlock with keys
Hardware Package
The GS6000 as shipped consists of the
components listed below.
UNPACKING
CHECKLIST
AC POWER SOURCE
TYPICAL CONNECTIONS
50 FT
#14
100 FT
#14
NOTE: DISTANCE IS TOTAL LENGTH OF
WIRE FROM CIRCUIT BREAKER IN THE
MAIN PANEL TO THE GATE OPERATOR.
600 FT
400 FT
250 FT
150 FT
#6
#10
#8
#12
#6
#10
#8
#12
300 FT
75 FT
125 FT
200 FT
DISTANCE
WIRE
SINGLE GATE
SIZE
DOUBLE GATE
WIRE
SIZE
DISTANCE
120 VAC, 15A
Dedicated Circuit
HIGH VOLTAGE TERMINALS
GND
L2
L1
Table 1
110112