D: 

STARTING THE OPERATOR 

17. Check the operation of the Loop Modules as applicable. 
 
CHECK OF THE INDICATOR LAMPS HAS BEEN COMPLETED.  
 

IF THE INDICATOR TEST PERFORMED SATISFACTORILY, 
TURN OFF THE AC POWER SWITCH AT THE GS6000 
CONTROL BOX AND RECONNECT THE WHITE HIGH 
VOLTAGE HARNESS CONNECTOR TO THE CONTROL 
BOARD.  RESET THE SWITCH SELECTABLE OPTIONS (S1, 
S2, S3) TO THE APPROPRIATE SETTINGS AS PER THE 
FUNCTIONS DESIRED (SEE PAGE 16).

 

 
PRE RUNNING CHECKLIST

 

 

Before running the GS6000, make sure: 
1.  The proper Left-or Right-hand or Bi-Parting wiring has been 

completed (if applicable). 

2.  The Limit Switch Cams have been preliminarily set. 

3.  The Overload Sensitivity has been preset. 

4.  The Switch Selectable Options have been set. 

5.  The Gate has been positioned in the center of it's travel. 

6.  The Torque Limiter is properly adjusted. 

7.  No other devices should be connected to the terminal strip         

until the powering-up procedures are completed. 

 

RUNNING THE GS6000

 

 

Turn ON the main power switch.  The Power Lamp will come on.  
The Alarm will sound for 1/2 second (a brief chirp), the Alarm 
indicator lamp will flash for 1/2 second.   The gate should not move.  
If the gate moves in either direction turn off the power and call 
Factory Service for assistance. 

 

1.  Give the GS6000 a command to open by connecting the jumper 

wire from Terminal #16 (COMMON) to Terminal #6 (OPEN).  
The gate should move to the fully open position. 

2.  If the TIMER TO CLOSE option has been selected, the timer will 

activate the gate to close within a maximum of 60 seconds 
depending on the setting of the TIMER TO CLOSE  potentiometer 
(See Figure 19, Page 16). 

3.  If the TIMER TO CLOSE is not to be used on this installation, 

activate the gate to Close by connecting the jumper wire from 
Terminal #16 (COMMON) to Terminal #7 (CLOSE).  The gate 
should move to the fully closed position. 

4.  Allow the gate to close and note the position of the gate. 

 
IF THE GATE HITS THE OPEN OR CLOSE STOPS OR 
EITHER THE MOTOR OPEN OR CLOSE LIGHT REMAINS 
ON AFTER REACHING THE MECHANICAL STOPS AND 
THE LIMIT SWITCH LIGHT IS "ON", TURN OFF THE MAIN 
POWER SWITCH. IF THE GATE HITS THE MECHANICAL 
LIMIT AND THE LIMIT SWITCH LIGHT DOES NOT COME 
ON, THE LIMIT CAM OR THE STOP WILL NEED TO BE 
READJUSTED. 

If the gate stops short of the desired fully open or closed position 
or if it bangs against the end stops, TURN OFF THE MAIN 
POWER and reset the appropriate Limit Switch Cam.  

After you 

have attained the final adjustment, run the GS6000 open and closed 
several times to ensure that the positions set will be retained.   
 

SMART™ SETTING - MAXIMUM RUN TIMER 

 

The GS6000 is equipped with a 

S

elf adjusting 

MA

ximum 

R

un 

T

imer, 

SMART™ , that will turn the GS6000 OFF if a Limit Switch 
command is not received within five seconds of the time required to 
fully Open or Close the gate.   The purpose of the Maximum Run 
Timer is to turn off the GS6000 if the gate should become jammed 
when opening or closing. In this case, the Limit Switch will not be 
activated.  Should this occur, the Torque Limiter will slip and the pads 
will be worn out prematurely.  The Maximum Run Timer will prevent 
this by turning OFF the GS6000.  Once the obstruction is removed, 
any command will reactive the GS6000. 

 

To set the Smart™ Maximum Run Time fully open and close the gate 
five (5) times.  The control board will sense the time required and add 
approximately four seconds. 

 

 
WHEN CHECKING OPERATION OF THE LIMIT 
SWITCHES, BE CERTAIN THE MOTOR IS BEING 
TURNED OFF BY THE LIMIT SWITCH AND NOT THE 
MAXIMUM RUN TIMER. SHOULD THE GATE REACH 
THE OPEN OR CLOSED POSITION AND THE 
RESPECTIVE LIMIT SWITCH LIGHT DOES NOT 
COME ON BUT THE MOTOR STOPS RUNNING, THEN 
THE MAXIMUM RUN TIMER IS TURNING OFF THE 
MOTOR.  TURNING THE GS6000 OFF BY THE 
MAXIMUM RUN TIMER WILL CAUSE THE TORQUE 
LIMITER TO SLIP FOR AN UNNECESSARY AMOUNT 
OF TIME EACH TIME THE GATE IS OPERATED.  THE 
TORQUE LIMITER PADS ARE NOT CAPABLE OF 
LONG LIFE UNDER THESE CONDITIONS.  
PREMATURE WEAR WILL OCCUR AND FREQUENT 
ADJUSTMENT OF THE TORQUE LIMITER WILL BE 
NECESSARY. 
 

        WARNING! 

RISK OF ENTRAPMENT 

OVERLOAD SENSITIVITY HAS NOT HAD 

A FINAL ADJUSTMENT. 

DO NOT ALLOW ANYONE NEAR THE GATE AND 

DO NOT LEAVE GATE AND GS6000 UNIT 

UNATTENDED UNTIL THE FOLLOWING 

PROCEDURES HAVE BEEN COMPLETED. 

USE CAUTION DURING THIS FINAL 

ADJUSTMENT PERIOD. 

19  

Содержание Gate Star 6000

Страница 1: ...fety Requirements for Vehicular gate operators GATE STAR 6000 Model GS6000 Heavy Duty Commercial Vehicular Swing Gate Operator READ THIS MANUAL CAREFULLY BEFORE INSTALLATION OR USE SAVE THESE INSTRUCT...

Страница 2: ...s throughout this manual are there to protect you and your equipment Pay close attention to these boxes as you follow the manual WARNING Indicates a MECHANICAL hazard of INJURY OR DEATH Gives instruct...

Страница 3: ...is activated before the Torque Limiter slips will depend upon the tightness of the adjustment of the Torque Limiter This adjustment will be explained in the final check out of the GS6000 Connections...

Страница 4: ...n to eliminate potential hazards For ORNAMENTAL GRILL TYPE GATES or any other type of open gate where a handhold or toehold may be achieved injuries may occur when people put arms through the openings...

Страница 5: ...TS AND PULLEYS when the operator cover is removed Apply power to the operator only when instructed to do so When the GS6000 cover is removed high voltage is exposed in the control box area EVEN IF THE...

Страница 6: ...LOOPS If Vehicle Detectors are to be used with the GS6000 the Loops to be buried in the drive should be installed during the site preparation phase of the installation Proper placement of the Vehicle...

Страница 7: ...UST BE HEAT AND WATER RESISTANT CROSS LINK POLYETHYLENE INSULATED TYPE XLPE IS BEST RHW IS O K DO NOT USE ANY PVC INSULATED WIRE PVC insulation will absorb moisture that may affect Detector operation...

Страница 8: ...00 VOLT AMPERE WATT TRANSFORMER MUST BE USED Operating from a three 3 phase line will require the use of a 230 VAC rated GS6000 CHECK THE OPERATOR PRODUCT LABEL The GS6000 rated for 230 VAC may be ope...

Страница 9: ...with gate and an isometric view of the gate arm assembly in a exploded fashion All dimensions are applicable to either the left hand or right hand views transpose them as necessary to your particular...

Страница 10: ...assembly into the outer through hole on the crank arm see Figure 10 Action C The release handle bolt assembly is inserted such that it points away from the gate Place the 3 8 internal tooth lock washe...

Страница 11: ...l installation the torque limiter adjustment nut is still loosened if resetting use the OPEN CLOSE and STOP buttons to place the operator into position Temporarily immobilize the gate in this FULLY CL...

Страница 12: ...st lightning strikes attempt to enter an appliance through the power lines Effective protection requires that the surge current from the lightning strike be shunted to ground This must be done without...

Страница 13: ...iary equipment devices must be of the type that require both sides of the transformer supplying power be floating and not grounded The GS6000 auxiliary equipment low voltage power terminals 1 2 is not...

Страница 14: ...losing the gate In general two wires or terminals are provided by the device to operate the gate Follow the manufacturers instructions on locating these connections If one of the connections at the de...

Страница 15: ...ng first physically mount the device according to the manufact urer s instructions Follow Figure 16C for connections to the GS6000 terminal strips Ensure the device power is s u p p l i e d separately...

Страница 16: ...s on a limit will prevent operation in that direction Continuous signal required to move the gate when in the alarm mode SWITCH 1 ON Gate does not respond to pushbutton input when in the normal mode C...

Страница 17: ...tput mode and could be coupled to and would control a Secondary control board box APPLYING POWER TO THE GS6000 PRE POWER CHECK LIST Before applying power to the GS6000 for the first time go through th...

Страница 18: ...o Terminal 4 Radio Open Radio Open light is ON Motor Open light is ON 6 Remove wire from Terminal 4 Radio Open Radio Open light goes OUT Motor Open light stays ON 7 Connect to Terminal 8 Stop Both Mot...

Страница 19: ...CH LIGHT IS ON TURN OFF THE MAIN POWER SWITCH IF THE GATE HITS THE MECHANICAL LIMIT AND THE LIMIT SWITCH LIGHT DOES NOT COME ON THE LIMIT CAM OR THE STOP WILL NEED TO BE READJUSTED If the gate stops s...

Страница 20: ...E TRY ADJUSTING THE POTENTIOMETERS SEVERAL TIMES BY SMALL INCREMENTS TESTING THE OVERLOAD BY STRIKING THE GATE WITH YOUR PALM IN BOTH DIRECTIONS OF TRAVEL REPEAT THIS TEST UNTIL YOU ARE SATISFIED YOU...

Страница 21: ...DESCRIPTION 10 CLOSE PHOTO CONT Momentary or continuous signal 12 OPEN EDGE Momentary or continuous signal This input is active only when referenced to the opening direction it has no effect on the g...

Страница 22: ...ur gate system Read and follow all instructions for each of the components of your unique system Ensure that all instructions for mechanical components safety features and the Allstar GS6000 are avail...

Страница 23: ...prevent injury or entrapment Loop detectors may be installed to detect vehicular traffic and prevent vehicular damage MAINTAIN THE GATE AND GATE HARDWARE A damaged gate or one that cannot be easily op...

Страница 24: ...ate to begin moving in the Open direction If the gate is moving in an Open direction an Open Non Contact Sensor Open Contact Sensor input or an Open Overload activation will cause the gate to stop pau...

Страница 25: ...cover Action B Slide the turret cover down the gate arm an appropriate length to complete Actions C D Action C Rotate the release handle 180 degrees away from the gate arm assembly Action D Pull the r...

Страница 26: ...OPERATOR EXPLODED VIEW 26 Figure 24 GS6000 Exploded View 008029 006043 111673 112539 010172 112485...

Страница 27: ...107307 Screw 10 24 x 3 8 HX SL WA T F SS 110132 Receptacle Duplex Outlet Switch 120 VAC 111673 Control Box GS6 HDSWG 111674 Control Box Bottom GS6 HDSWG 111725 Socket Octal 11 Pin DIN Panel Mounting 1...

Страница 28: ...the goods The goods must be returned with complete identification with copy of proof of purchase freight prepaid and in accordance with Allstar s instructions or they will not be accepted In no event...

Отзывы: