Section 7 Gas Burner Conversion Procedures
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the dryer(s) before servicing.
• Close gas shut-off valve to gas dryer(s) before servicing.
• Never start the dryer(s) with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be
reconnected to ensure that the dryer is properly grounded.
W001R1
WARNING
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
(1) Loosen air shutter lockscrew. Refer to
(2) Turn air shutter to the right or left as
necessary to obtain proper flame intensity.
Refer to Figure 44.
(3) After air shutter is adjusted for proper
flame, tighten air shutter lockscrew firmly.
p. Be sure and observe at least two complete
ignition and burn cycles before reinstalling
access door.
q. Reinstall the access door and screw.
Figure 43
APPLY NO. 60515
CONVERSION
PLATE
HERE
NAMEPLATE
For personal safety, access door must be in
place during normal operation.
WARNING
Figure 44
DRY965S
MANOMETER
10 ± 1.5
INCHES
GAS VALVE
PRESSURE TAP
AIR
SHUTTER
AIR SHUTTER
LOCKSCREW
Содержание AE4113