130
Rockwell Automation Publication 750-UM006C-EN-P - March 2022
Chapter 4
Configure and Start Up the Drive
Specify the Motor Data Source
The Motor Data Source is where you tell the axis where the motor
configuration values are originating. You can select a motor from the database,
nameplate, or nonvolatile memory. The nameplate option requires that you
enter the motor specification information. You can find the information on the
hardware nameplate or product data sheets.
1. Double-click on the axis (PF755_CIP_Turntable) to open the Axis
Properties dialog box.
2. Choose the Motor page.
3. Enter the motor data recorded during
Prepare for Initial Drive Startup
. Rotary Permanent Magnet and Rotary Induction are
supported.
4. Click Apply.
5. Choose the Motor Feedback page.
Содержание The PowerFlex 755 On-Machine
Страница 1: ...User Manual Original Instructions PowerFlex 755 On Machine Drive Bulletin Number 26G...
Страница 208: ...208 Rockwell Automation Publication 750 UM006C EN P March 2022 Appendix B Startup Information Notes...
Страница 216: ...216 Rockwell Automation Publication 750 UM006C EN P March 2022 Index Notes...
Страница 217: ...Rockwell Automation Publication 750 UM006C EN P March 2022 217 PowerFlex 755 On Machine Drive User Manual...