Rockwell Automation Publication 1789-UM002K-EN-P - January 2015
231
Communicate with Devices on a ControlNet Network
Appendix B
Produce a Tag to a PLC-5 Controller for the ControlNet Network
Complete these steps to produce a tag that a PLC-5 controller for the
ControlNet network can consume.
1.
Determine the type of data to produce..
2.
In RSNetWorx software, open the ControlNet configuration for the target
PLC-5 controller for the ControlNet network, insert a Receive Scheduled
Message and enter the following Message size.
3.
In the RSNetWorx software, reschedule and save the network.
The PLC-5 controller for the ControlNet network does not perform type
checking. Make sure the PLC-5 data type can correctly receive the SoftLogix
produced tag to be sure proper data is being received.
When a PLC-5 controller for the ControlNet network consumes a tag that is
produced by a Logix5000 controller, it stores the data in consecutive 16-bit
integers. The PLC-5 controller stores floating-point data, which requires 32-bits
regardless of the type of controller, as follows:
•
The first integer contains the upper (left-most) bits of the value.
•
The second integer contains the lower (right-most) bits of the value.
To reconstruct the floating point data within the PLC-5 controller, first reverse
the order of the integers and then copy them to a floating-point file.
If
And you are producing
Then
INT
N/A
Create a user-defined data type that contains an array of INTs with an even number of elements, such as
INT[2]. When you produce INTs, you must produce two or more.
Create a produced tag and choose the user-defined data type you created.
DINT or REAL
Only one DINT or REAL value
Create a produced tag and choose the DINT or REAL data type, as appropriate.
More than one DINT or REAL
Create a user-defined data type that contains an array of DINTs or REALs, as appropriate.
Create a produced tag and choose the user-defined data type you created.
If the produced tag contains
For the Message Size Enter
INTs
The number of integers in the produced tag
DINTs
Two times the number of DINTs or REALs in the produced tag. For example, if
the produced tag contains 10 DINTs, enter 20 for the Message size.
REALs
Содержание SoftLogix 5800
Страница 1: ...SoftLogix 5800 System Catalog Numbers 1789 L10 1789 L30 1789 L60 User Manual...
Страница 4: ...4 Rockwell Automation Publication 1789 UM002K EN P January 2015 Summary of Changes Notes...
Страница 104: ...104 Rockwell Automation Publication 1789 UM002K EN P January 2015 Chapter 5 Configure and Use Simulated I O Notes...
Страница 110: ...110 Rockwell Automation Publication 1789 UM002K EN P January 2015 Chapter 6 Execute External Routines 9 Click OK...
Страница 148: ...148 Rockwell Automation Publication 1789 UM002K EN P January 2015 Chapter 7 Develop External Routines Notes...
Страница 256: ...256 Rockwell Automation Publication 1789 UM002K EN P January 2015 Appendix E System Performance Tuning Guidelines Notes...
Страница 262: ...262 Rockwell Automation Publication 1789 UM002K EN P January 2015 Appendix G SoftLogix 5800 Revision History Notes...
Страница 270: ...270 Rockwell Automation Publication 1789 UM002K EN P January 2015 Index...
Страница 271: ......